Authority Having Jurisdiction

The organization, office, or individual with legal authority to enforce the fire code, approve plans, witness tests, and grant interpretations; in Oklahoma this is often the State Fire Marshal or a local fire department.

Related: NFPA 13, Acceptance Test
NFPA 13

The installation standard for automatic sprinkler systems, covering hazard classification, design methods, water supply, materials, hangers, acceptance testing, and maintenance; Oklahoma adopts an edition of this standard as the technical basis for sprinkler work.

Related: Occupancy Hazard Classification, Density/Area Method
Oklahoma Sprinkler Contractor License

A state-issued credential required to contract for sprinkler installation, alteration, or testing in Oklahoma; applicants typically qualify through documented experience and examination, and the work still requires local permits and inspections.

Related: Authority Having Jurisdiction, Working Plan
Design Density

The selected water application rate, in gallons per minute per square foot of floor area, that the system must deliver over the design area; it is read from the density/area curves for the occupancy hazard.

Related: Density/Area Method, Remote Area
Density/Area Method

A design method pairing a discharge density with a remote area size taken from the occupancy hazard curves, then verifying by hydraulic calculation that the supply can meet the resulting demand.

Related: Design Density, Remote Area, Hydraulic Calculation
Occupancy Hazard Classification

Grouping of occupancies by fuel load and expected fire severity into light, ordinary (Groups 1 and 2), and extra hazard classes, which set the density, area, and sprinkler requirements used in design.

Related: Design Density, Density/Area Method
Remote Area

The portion of the system, usually the hydraulically most demanding, assumed to have all sprinklers flowing at design density; its size depends on hazard, construction, ceiling height, and sprinkler response type.

Related: Design Density, Hydraulic Calculation, Quick-Response Sprinkler
Hydraulic Calculation

A pressure-loss analysis that starts at the most remote flowing sprinkler, adds friction and elevation losses through pipe and fittings, and compares total demand with the available water supply.

Related: Hazen-Williams C Factor, Remote Area, Safety Margin
Hazen-Williams C Factor

A roughness coefficient in the Hazen-Williams friction formula; NFPA 13 assigns values such as about 100 for unlined ferrous pipe, 120 for galvanized, and 140 for cement-lined, with lower values producing greater loss.

Related: Hydraulic Calculation, Residual Pressure
Residual Pressure

The pressure reading at a gauge while water is discharging during a flow test; subtracting it from static pressure, together with the measured flow, defines the available water supply curve.

Related: Safety Margin, Hydraulic Calculation
Safety Margin

The extra pressure required at the design flow beyond the calculated system demand, covering supply test uncertainty, future demand growth, and minor piping changes; often a modest fixed increment.

Related: Residual Pressure, Hydraulic Calculation
Wet Pipe System

Piping kept full of pressurized water so an opened sprinkler discharges immediately; the simplest and most common arrangement, used wherever the building is reliably protected from freezing.

Related: Dry Pipe System, Alarm Check Valve
Dry Pipe System

Piping charged with pressurized air or nitrogen that holds a dry pipe valve closed against the water supply; air must vent through an open sprinkler before water arrives, adding delay.

Related: Dry Pipe Valve, Preaction System
Preaction System

A dry system in which fire detection first opens a valve to fill the piping, and water discharges only when a sprinkler also opens; the double interlock reduces accidental discharge risk.

Related: Dry Pipe System, Deluge System
Deluge System

A system using open sprinklers or nozzles connected to a deluge valve, so detection actuation admits water to all heads in the zone at once, intended for high-hazard or special fire challenges.

Related: Preaction System, Design Density
ESFR Sprinkler

Early Suppression Fast Response sprinkler designed to suppress high-challenge storage fires with high-momentum discharge; permitted only within strict limits on ceiling height, storage height, clearance, and commodity.

Related: K-Factor, Maximum Coverage Area
Maximum Coverage Area

The largest floor area one sprinkler may protect, set by hazard class, sprinkler type, and ceiling construction; it works together with maximum spacing limits to fix the layout.

Related: Deflector, ESFR Sprinkler
K-Factor

A sprinkler's nominal discharge coefficient linking pressure to flow through the relation Q equals K times the square root of pressure; larger K values deliver more water at the same pressure.

Related: Design Density, Temperature Rating
Control Mode Density/Area Sprinkler

A sprinkler intended to control a fire by delivering the density/area design over the assumed remote area, typically a standard spray head; the default choice for most hazard-classified designs.

Related: Density/Area Method, Quick-Response Sprinkler
Quick-Response Sprinkler

A sprinkler with a fast thermal element and low response time index, operating earlier than standard-response heads; it can allow reduced design areas where the code permits.

Related: Remote Area, Temperature Rating
Temperature Rating

The nominal temperature at which a sprinkler's heat-responsive element operates, identified by color coding; it is selected well above normal ceiling temperatures to avoid premature activation.

Related: Quick-Response Sprinkler, Deflector
Deflector

The metal plate or frame part that shapes and spreads sprinkler discharge into the intended pattern; its orientation and distance from the ceiling affect coverage and obstruction rules.

Related: Maximum Coverage Area, Temperature Rating
Alarm Check Valve

A wet-pipe check valve with a trim port that directs water to a hydraulic alarm or pressure switch when flow occurs, while preventing reverse flow into the supply.

Related: Wet Pipe System, Waterflow Switch
Dry Pipe Valve

A valve holding supply water back from air-pressurized piping, opening when air pressure drops after a sprinkler operates; often a differential clapper design with an intermediate chamber.

Related: Dry Pipe System, Inspector's Test Valve
Waterflow Switch

A paddle or vane device sensing sustained water movement in the pipe and sending an alarm signal to the fire alarm panel; its delay and placement follow NFPA 72 and NFPA 13.

Related: Alarm Check Valve, Inspector's Test Valve
Inspector's Test Valve

A valve and orifice at the end of the most remote branch line that simulates one sprinkler flowing, used to confirm waterflow switch operation and alarm delay times during testing.

Related: Waterflow Switch, Acceptance Test
Fire Department Connection

An exterior siamese connection letting a responding pumper supplement the sprinkler supply; it needs a check valve, clear access, and signage identifying the system it serves.

Related: Fire Pump, Riser
Riser

The vertical supply pipe connecting the underground main to the overhead system, carrying the main control valve, check valve, drain, gauges, and alarm attachments.

Related: Alarm Check Valve, Hydraulic Placard
Branch Line

The smallest sprinkler pipe, running from the cross main and serving sprinklers directly; its diameter and the number of heads it supplies are limited by code tables or calculations.

Related: Pipe Schedule Method, Inspector's Test Valve
Pipe Schedule Method

A prescriptive way to size piping from tables based on how many sprinklers a pipe serves, allowed only for limited hazards and tree layouts; it does not verify water supply adequacy.

Related: Branch Line, Hydraulic Calculation
Grooved Coupling

A mechanical joint formed by grooves rolled or cut into pipe ends, joined with a gasket and clamp housing; it permits rapid assembly and slight flexibility and requires listed components.

Related: Hanger, Sway Bracing
Hanger

A support that carries the dead weight of pipe and water at code-specified intervals, using listed rods, clevis hangers, or trapeze assemblies attached to structural members.

Related: Sway Bracing, Grooved Coupling
Sway Bracing

Lateral and longitudinal bracing that resists seismic or thrust forces, separate from gravity hangers; required in seismic design categories and coordinated with flexible couplings and clearances.

Related: Hanger, Grooved Coupling
Fire Pump

A listed pump, usually centrifugal, that boosts pressure and flow from a water supply to meet sprinkler demand; it is rated at a specific flow, head, and speed.

Related: Fire Department Connection, Safety Margin
Working Plan

Scaled drawings submitted for approval showing piping layout, sizes, sprinkler locations, hangers, and details, accompanied by hydraulic calculations and water supply data before installation begins.

Related: Hydraulic Placard, Authority Having Jurisdiction
Hydraulic Placard

A sign at the riser stating design density, remote area, required flows and pressures, and supply information; it guides inspectors and future alterations to hydraulically calculated systems.

Related: Design Density, Remote Area
Hydrostatic Test

A water pressure test of installed piping at a level above normal working pressure, held for a specified time, to reveal leaks in joints and fittings before acceptance.

Related: Acceptance Test, Grooved Coupling
Acceptance Test

The post-installation testing and documentation required before final approval, including hydrostatic, flow, alarm, and supervisory checks, often witnessed by the authority having jurisdiction.

Related: Hydrostatic Test, Inspector's Test Valve
Impairment

Any condition leaving a system or part of it out of service; it triggers notification, tagging, a documented impairment program, fire watch where required, and prompt restoration.

Related: Hot Work Permit, Wet Pipe System
Hot Work Permit

Written authorization for welding, cutting, or grinding after combustible hazards are removed, with a fire watch, extinguishing equipment, and checks before and after the work.