CCB license bond amount
Oregon requires a $20,000 surety bond for a residential general contractor and $10,000 for a residential specialty contractor, filed with the CCB before the license is issued.
Right to cure notice
Before suing over a residential construction defect, the owner must give the contractor written notice and a reasonable chance to inspect and offer to repair.
Oregon lien recording deadline
A construction lien must be recorded within 75 days after the claimant last furnishes labor, materials, or equipment to the project.
Written contract threshold
Oregon residential contracts over $2,000 must be in writing and include the CCB number, scope of work, price, and payment schedule.
CCB license renewal cycle
Oregon contractor licenses renew every two years; renewal requires a current surety bond and completion of required continuing education hours.
Oregon residential code scope
The Oregon Residential Specialty Code applies to one- and two-family dwellings and townhouses, while commercial and larger multi-family work follows the Oregon Structural Specialty Code.
HVAC rough-in inspection
Rough-in inspection covers ductwork, refrigerant lines, gas piping, and venting before concealment; final inspection follows equipment startup and controls completion.
Permit before HVAC work
Installing, altering, or replacing HVAC equipment, ducts, or gas piping requires a permit from the jurisdiction before work begins.
Combustion air opening sizing
When both combustion air openings communicate with outdoors, each is sized at 1 square inch per 1,000 Btu/h of total appliance input.
Sensible heat formula
Sensible Btu/h equals 1.08 times CFM times the dry-bulb temperature difference across the coil or air handler.
Latent heat formula
Latent Btu/h equals 0.68 times CFM times the difference in humidity ratio measured in grains of moisture per pound of dry air.
Manual J and Manual D
ACCA Manual J calculates building heating and cooling loads; Manual D sizes the duct system to deliver that airflow at acceptable static pressure.
External static pressure limit
Total external static pressure equals supply plus return static; it must stay within the air handler's rated limit or airflow drops and the coil may freeze.
Heat pump balance point
The balance point is the outdoor temperature where heat pump capacity equals building heat loss; below it, supplemental heating stages operate.
Superheat definition
Superheat is the evaporator outlet temperature minus the saturated suction temperature at the measured suction pressure; typical target is 8 to 12 degrees F.
Subcooling definition
Subcooling is the saturated condensing temperature minus the liquid line temperature; typical target on a TXV system is 8 to 12 degrees F.
TXV function
A thermostatic expansion valve modulates refrigerant flow to hold a constant evaporator superheat as load and suction pressure change.
Recovery cylinder fill limit
A refrigerant recovery cylinder must not be filled above 80 percent of its capacity by weight, leaving room for liquid expansion.
R-410A pressure behavior
R-410A is a near-azeotropic HFC blend operating at roughly 60 percent higher pressure than R-22, so gauges and components must be rated for it.
Suction accumulator purpose
A suction accumulator traps liquid refrigerant and meters it back as vapor, protecting the compressor from liquid slugging on long or variable-load systems.
Ohm's law and power
Voltage equals current times resistance; power in watts equals voltage times current for a resistive load, with 746 watts per horsepower.
Run capacitor failure signs
A failed run capacitor reduces motor torque, raises running current, and causes the compressor or fan motor to overheat and trip overloads.
Thermostat terminal letters
R is 24-volt power, W is heat, Y is compressor, G is fan, O or B is the reversing valve, and C is common for thermostat power.
Locked rotor amps
LRA is the current drawn at startup with the rotor stalled; start capacitors and relays supply extra torque until the motor reaches running speed.
Disconnect within sight
The NEC requires a disconnecting means within sight of HVAC equipment and a branch circuit sized to the nameplate minimum circuit ampacity.
Sediment trap location
A sediment trap is installed downstream of the appliance shutoff valve and ahead of the gas controls to catch dirt and pipe scale.
Vent category definitions
Category I vents operate under negative pressure non-condensing, Category III positive pressure non-condensing, and Category IV positive pressure condensing.
Manifold pressure check
Natural gas appliances commonly require 3.5 in. w.c. manifold pressure and LP appliances 10 to 11 in. w.c., verified at the appliance regulator outlet.
Gas piping leak test
New gas piping is pressure-tested with air or inert gas at the code's specified test pressure and duration before gas is introduced.
Nitrogen purge while brazing
Flowing nitrogen through tubing during brazing prevents internal oxidation scale that can clog metering devices and contaminate compressor oil.
A2L refrigerant handling
A2L refrigerants are mildly flammable; service requires ignition-source control, ventilation, and leak detection per ASHRAE 15 and the equipment listing.
Acetylene regulator limit
Acetylene working pressure must never exceed 15 psig, and the torch valve should be opened no more than one and a half turns.