NFPA PACE / RP · Put your knowledge to work in context.

All case studies

Church Fellowship Hall Dinner: One Chained Exit and an Indoor Propane Oven

A 1958 church fellowship hall is rented out for a Saturday community dinner and dance. The hall is a single-story, unsprinklered room of 2,900 ft²; the dining and dance area is about 2,600 ft² with a 300 ft² kitchen. Two ways out exist: a 72 in. double door at the front with panic hardware, and a 36 in. rear door opening from a short corridor beside the kitchen. On inspection, the rear door is chained shut and a chest freezer placed in the corridor leaves 18 in. of clear width. The corridor has a 7 in. step and no exit sign. The front door opens into a lobby and vestibule. The organizer has set 96 chairs at 12 tables plus a buffet line and expects 150 guests. A portable pizza oven with a 20 lb propane cylinder sits inside the hall next to the buffet, and two extension cords run across the dance area to the DJ table. The organizer says the hall has been used this way for years.

1. Calculate the occupant load. Given that the rear exit cannot be restored before the event, what is the maximum number of persons that may be admitted, and what is the code basis for that number?

Read the worked answer

Occupant load: 2,600 ft² of tables, chairs and dance area ÷ 15 ft² per person (tables and chairs, net) = 173 persons. Seating supplied (96 chairs) is below the calculated load, but the calculated load is what governs the required egress, because the room can be re-arranged.

With the rear exit unusable, the maximum is 49 persons. The assembly chapters require two separate means of egress where the occupant load exceeds 49. With a single usable exit, the room is limited to 49 occupants no matter how wide that door is - the 72 in. front door (72 ÷ 0.2 = 360 persons of capacity) is irrelevant because the number of exits, not the width, is the controlling failure. The 7 in. step, the missing exit sign and the chained door all confirm the rear path is not a functioning exit tonight.

Practical application: cap attendance at 49, count at the door, remove the excess tables so the layout cannot quietly revert to 150, and staff the single exit. Alternatively, restore the rear exit - cut the chain, relocate the freezer to provide full clear width, sign the door, and address the step as a change in elevation with a handrail - and the 173-person load becomes supportable on exit count (front 360 + rear 180 = 540 of capacity for 173 persons). That fix is achievable in an afternoon; the chain and the freezer are the cheapest compliance the owner will ever buy.

2. Evaluate the propane pizza oven and the extension cords, and state what authority the inspector has to act on them immediately.

Read the worked answer

Propane oven. A 20 lb propane cylinder feeding an open-flame appliance inside a public assembly room is the highest-consequence item on the list: it introduces a fuel-gas leak and fire hazard into a crowded, unsprinklered room whose second exit is already chained. Cylinders of this size are not permitted inside assembly occupancies for this kind of portable cooking use; the correct location is outdoors, away from exits and air intakes, with the cylinder secured upright and the appliance listed for the application. Action: stop the use and remove the cylinder and appliance from the building before anyone is admitted. This is an imminent hazard, not a scheduled correction.

Extension cords. Flexible cords may not be used as a substitute for permanent wiring, may not run through doorways, walls or under floor coverings, and may not be daisy-chained. Two cords across a dance floor are both an ignition source (overloading, abrasion, damaged insulation) and a trip/egress obstruction in the path people will use in a dark, smoke-filled room. Action: require the DJ table to be served by fixed receptacles or a properly protected cord kept out of the egress path.

Authority: these are conditions creating immediate danger to life, which supports an immediate stop-work/stop-use order for the cooking equipment, a written notice, and refusal to allow occupancy until corrected. Document with photographs, note the time of the order, and give the organizer the specific corrective step rather than a general prohibition.

3. The organizer argues that the hall has always been used this way and that the church is grandfathered. How should the AHJ handle that argument and sequence enforcement so the event can still occur safely?

Read the worked answer

Answer the legal argument first, on the record. "Always done it this way" is not a defense - a longstanding violation is still a violation, and an unsprinklered assembly room does not acquire compliance through repetition. "Grandfathered" is equally unhelpful as stated: an existing building is judged against the existing-occupancy provisions, but those provisions still require two means of egress over 49 occupants, unobstructed egress, exit signs and no chained exits. The rear door being chained is not a legacy construction feature; it is an active, correctable condition.

Sequence enforcement so the event survives:

  1. Tonight: order removal of the propane appliance and cylinder, removal of the chain, relocation of the freezer, and capping attendance at 49 if the rear exit is not restored.
  2. Give the achievable fix in writing: restore the rear exit (chain, freezer, exit sign, step/handrail), correct the cords, then the 173-person load is supportable. State that this can be verified by re-inspection before the event.
  3. Document findings, the order, the corrective options and the re-inspection date; provide a single point of contact.
  4. Follow up after the event with a formal notice for the remaining deficiencies (exit sign, step, corridor obstructions, posted occupancy) and a compliance date, so the file reflects a durable correction rather than a one-night fix.
  5. If the organizer proceeds in violation, escalate to the fire chief's authority to close the assembly and, if applicable, refer to the rental/licensing authority.

The tone matters: the goal is a safe event, not a cancelled one, so lead with the path that lets them open legally.