- Assembly occupancy definition
- An occupancy or portion thereof used for gathering of 50 or more persons for purposes such as civic, social, religious, educational, or recreational activities, as defined in NFPA 101.
- Concentrated assembly occupant load factor
- For assembly areas with tables and chairs, the occupant load factor is 7 square feet per person, used to calculate the total occupant load for egress design.
- Unconcentrated assembly occupant load factor
- For assembly areas without fixed seating, such as standing areas or exhibit halls, the occupant load factor is 15 square feet per person for egress calculations.
- Egress capacity factor for level components
- In assembly occupancies, level egress components (corridors, aisles) must provide 0.2 inches of clear width per person of occupant load.
- Egress capacity factor for risers
- Stairs and risers in assembly occupancies require 0.3 inches of clear width per person, reflecting the slower movement on stairs compared to level surfaces.
- Assembly travel distance without sprinklers
- The maximum travel distance to an exit in an unsprinklered assembly occupancy is 200 feet, measured along the path of egress travel.
- Assembly travel distance with sprinklers
- In a fully sprinklered assembly occupancy, the maximum travel distance to an exit is increased to 250 feet along the path of egress.
- Common path of travel limit
- In assembly occupancies, the common path of travel is limited to 75 feet without sprinklers and 100 feet with sprinklers, ensuring two distinct egress paths.
- Crowd manager requirement
- Assembly occupancies with an occupant load exceeding 500 (or 250 in some conditions) must have at least one crowd manager per 250 occupants, per NFPA 101.
- Interior finish Class A requirement
- Class A interior wall and ceiling finish is required in exits and in rooms with occupant load over 100, limiting flame spread and smoke development.
- Minimum clear egress width
- The minimum clear width for new construction egress paths in assembly occupancies is 28 inches, though larger widths may be required based on occupant load.
- Visible notification appliances
- In assembly occupancies, visible alarm notification appliances must be provided in public and common areas to alert hearing-impaired occupants, per NFPA 72.
- Assembly exit access corridor width
- Corridors serving assembly occupancies must be at least 44 inches wide, or wider if required by occupant load calculations using the capacity factor.
- Assembly seating aisle width
- Aisles in assembly seating must be at least 36 inches wide for rows of seats, increasing with the number of seats served, per NFPA 101.
- Assembly stage exit requirement
- Stages in assembly occupancies require at least two exits when the stage area exceeds 1,000 square feet or has an occupant load over 50.
- Assembly occupancy separation
- Assembly occupancies must be separated from other occupancies by fire barriers with a fire-resistance rating based on the occupant load and sprinkler protection.
- Residential occupancy definition
- An occupancy providing sleeping accommodations for occupants, including hotels, motels, dormitories, apartments, and lodging or rooming houses, as defined by NFPA 101.
- Residential Group R-1
- Hotels and dormitories where occupants are primarily transient and sleeping accommodations are provided, typically with 24-hour staff and fire alarm systems.
- Residential Group R-2
- Lodging or rooming houses with sleeping accommodations for more than 16 occupants, where occupants are not primarily transient and cooking may be shared.
- Residential Group R-3
- Apartment buildings and other residential occupancies where occupants are primarily permanent and each unit has independent cooking and sanitary facilities.
- Residential Group R-4
- Residential care or assisted living facilities with sleeping accommodations for more than 5 but not more than 16 occupants, excluding staff, who require personal care.
- Residential Group R-5
- One- and two-family dwellings and townhouses not classified as R-3, typically with not more than two dwelling units and no shared egress.
- Smoke alarm location requirement
- Smoke alarms must be installed in all sleeping rooms and in the immediate vicinity of sleeping areas, and they must be interconnected in new residential construction.
- Carbon monoxide alarm requirement
- Carbon monoxide alarms are required in residential occupancies containing fuel-burning appliances or attached garages, per NFPA 720 and NFPA 101.
- Residential travel distance limit
- In residential occupancies, travel distance to an exit is limited to 125 feet without sprinklers and 200 feet with sprinklers, measured along the egress path.
- Secondary means of escape
- Each sleeping room in a residential occupancy must have access to at least two means of escape, which may include a door or window leading directly outside.
- Fire escape stairs permitted
- Fire escape stairs and ladders are allowed as secondary means of escape in existing residential buildings of three stories or less, subject to NFPA 101 7.2.8.
- Emergency lighting illumination level
- Emergency lighting in residential common areas such as corridors and stairways must provide a minimum of 1 footcandle (10 lux) at floor level.
- Residential corridor fire separation
- In R-1 and R-2 occupancies, sleeping rooms must be separated from corridors by smoke-tight construction to limit smoke spread during a fire.
- Portable extinguisher requirement
- Residential occupancies generally do not require portable extinguishers except in hazardous areas such as boiler rooms and common kitchens, per NFPA 101 29.3.6.
- Residential cooking equipment protection
- In residential occupancies, cooking equipment in common areas must be protected by a fire suppression system or listed extinguishing unit when required by code.
- Residential fire alarm system
- R-1 and R-2 occupancies require a manual fire alarm system with initiation devices in corridors and notification throughout, unless exempted by occupant load.