Quick reference

Public Assembly Code Enforcement (PACE)

  • NFPA 101 defines assembly occupancy as use of a building for gathering of 50 or more persons for purposes such as civic, social, religious, educational, or recreational activities.

  • Assembly occupancies are classified as Group A by NFPA 101; occupant load factors for concentrated assembly (tables/chairs) are 7 sq ft per person and unconcentrated (standing) is 15 sq ft per person.

  • Means of egress capacity: 0.2 in per person for level components, 0.3 in per person for risers, and 0.2 in per person for ramps; minimum clear width is 28 in for new construction.

  • Travel distance to an exit in assembly occupancies without sprinklers is limited to 200 ft; with sprinklers, 250 ft (NFPA 101 Table 28.2.6).

  • Common path of travel in assembly areas is limited to 75 ft without sprinklers and 100 ft with sprinklers (NFPA 101 28.2.5).

  • Required egress width for assembly occupancies is computed using the occupant load and the capacity factor; the total width must be at least the largest of (occupant load × factor) for the egress components.

  • Crowd manager requirements apply to assembly occupancies with occupant load over 500 (or 250 in some cases); NFPA 101 12.7.6 requires at least one crowd manager per 250 occupants.

  • Fire alarm systems in assembly occupancies must be provided with voice evacuation or audible/visual notification per NFPA 72; visible notification appliances are required in public and common areas.

  • Interior finish requirements: Class A interior wall and ceiling finish is required in exits and rooms with occupant load over 100; Class B is permitted in rooms with occupant load 50-100.

Quick reference

Residential Property (RP)

  • NFPA 101 defines residential occupancies as those providing sleeping accommodations for occupants; examples include hotels, motels, dormitories, apartments, and lodging/rooming houses.

  • Residential occupancies are divided into five groups: Hotels and Dormitories (R-1), Lodging/Rooming Houses (R-2), Apartments (R-3), Residential Care/Assisted Living (R-4), and One- and Two-Family Dwellings (R-5).

  • Smoke alarm requirements: NFPA 101 29.3.4 requires smoke alarms in all sleeping rooms and in the immediate vicinity of sleeping areas; they must be interconnected in new construction.

  • Carbon monoxide alarms are required in residential occupancies where fuel-burning appliances or attached garages exist, per NFPA 720 and NFPA 101 29.3.5.

  • Means of escape: residential occupancies must have at least one exit and a second means of escape (secondary means) from each sleeping room; travel distance to an exit is limited to 125 ft without sprinklers and 200 ft with sprinklers.

  • Fire escape stairs and ladders are permitted as secondary means of escape in existing residential buildings of 3 stories or less, subject to NFPA 101 7.2.8.

  • Emergency lighting is required in residential occupancies in corridors, stairways, and other common areas serving sleeping rooms; minimum illumination is 1 footcandle (10 lux) at floor level.

  • Fire extinguishers: residential occupancies are not generally required to have portable extinguishers unless required by other codes; however, NFPA 101 29.3.6 requires extinguishers in hazardous areas (e.g., boiler rooms, kitchens in common areas).

  • Separation of sleeping rooms from other occupancies: in R-1 and R-2, sleeping rooms must be separated from corridors by smoke-tight construction; in R-3, dwelling unit separation is required by the building code.