PE Electrical Power study materials
PE Electrical Power study resources

PE Electrical Power cheat sheet

PE Electrical Power · Keep the key ideas within reach.

Quick reference

General Power Engineering: Circuit Analysis, Measurement, and Instrumentation

  • Per-unit conversion: Z_pu = Z_actual / Z_base, where Z_base = V_base^2 / S_base; the per-unit impedance of a transformer is identical whether computed from either winding's base quantities.

  • Balanced three-phase relations: S_3φ = √3 · V_LL · I_L; P = √3 · V_LL · I_L · cos θ; Q = √3 · V_LL · I_L · sin θ; wye V_L = √3 V_ph, delta I_L = √3 I_ph.

  • Thevenin equivalent: V_th is the open-circuit terminal voltage, Z_th = V_oc / I_sc; maximum real power transfers to a load when R_L = |Z_th|.

  • Series resonance occurs at f_r = 1/(2π√(LC)); at resonance X_L = X_C, the impedance is purely resistive, and voltage across L and C can greatly exceed the source voltage (Q magnification).

  • Two-wattmeter method on a balanced three-phase load: P_total = W1 + W2, Q_total = √3 (W1 − W2); a negative reading on one meter indicates power factor below 0.5.

  • Instrument accuracy: percent error = (measured − true)/true × 100; accuracy class defines the maximum error as a percentage of full-scale (or reading) deflection.

  • A current transformer secondary must never be open-circuited while primary current flows; the collapsing core flux induces dangerous voltage, so short the secondary before removing burden.

  • Skin and proximity effects raise the effective AC resistance of conductors above the DC value at higher frequency, larger cross-section, and closer spacing.

Quick reference

Rotating Machines and Electromagnetic Devices

  • Synchronous speed: n_s = 120 f / P rpm; a 60 Hz, 4-pole machine runs at 1800 rpm, and an induction rotor always turns slower than n_s in motoring.

  • Slip: s = (n_s − n_r)/n_s; rotor frequency f_r = s · f; rotor-induced EMF and reactance scale directly with slip.

  • Induction motor developed torque is approximately proportional to the square of applied terminal voltage, so reduced-voltage starting sharply lowers starting torque while lowering inrush current.

  • Round-rotor synchronous machine per phase: E_f = V_t + j X_s I_a; real power P ≈ (E_f V_t / X_s) sin δ, maximum at δ = 90° (steady-state stability limit).

  • DC machine: E_a = K Φ ω (generated EMF proportional to flux and speed); electromagnetic torque T = K Φ I_a; separately excited and shunt fields behave differently under load.

  • Transformer: turns ratio a = N1/N2 = V1/V2; impedance referred to the primary = a² × (secondary impedance); current ratio is inverse to the voltage ratio.

  • Transformer losses: core (hysteresis + eddy current) loss is essentially constant at rated voltage and frequency; copper loss varies as I² and is found from the short-circuit test; core loss from the open-circuit test.

  • Machine efficiency η = P_out / P_in; losses appear as heat, and temperature rise at a given load depends on the cooling method (self, forced, or totally enclosed).

Quick reference

Transmission and Distribution

  • Surge (characteristic) impedance of a lossless line Z_c = √(L/C), roughly 400 Ω for overhead lines in air; underground cables have far lower values because of high capacitance.

  • Voltage regulation = (|V_no-load| − |V_full-load|)/|V_full-load| × 100, evaluated at the receiving end for a specified load power factor.

  • Ferranti effect: on a long, lightly loaded or open line the receiving-end voltage exceeds the sending-end voltage because charging current through the series inductance adds voltage.

  • Bundled conductors (two, three, or four subconductors per phase) reduce series inductive reactance, reduce corona and audible noise, and raise the effective GMR of the phase.

  • Corona inception depends on conductor surface voltage gradient, diameter, and spacing; larger conductors, bundled phases, and higher humidity/altitude effects change the critical voltage.

  • Lossless line power transfer: P ≈ (V_s V_r / X) sin δ; the angle δ limits transfer, and series compensation reduces X to raise the steady-state limit.

  • Transposition of phase conductors at regular intervals balances the mutual inductances so that the three phases see approximately equal impedance over the line length.

  • Distribution grounding practice determines step and touch potentials; a ground grid is designed so that mesh and step voltages stay below tolerable body-current limits during a fault.

Quick reference

Power System Analysis

  • Symmetrical components: an unbalanced three-phase set resolves into positive, negative, and zero sequences; operator a = 1∠120°, with 1 + a + a² = 0.

  • Zero-sequence current requires a grounded return path; it circulates in grounded-wye windings and grounded networks but cannot pass an ungrounded delta or an ungrounded neutral.

  • Per-unit base change: Z_pu,new = Z_pu,old × (V_base,old / V_base,new)² × (S_base,new / S_base,old).

  • Single line-to-ground fault: I_a1 = V_f / (Z1 + Z2 + Z0 + 3Z_n), and the three sequence networks are connected in series for this fault type.

  • Swing equation: (2H/ω_s) d²δ/dt² = P_m − P_e (per unit); accelerating power produces rotor angle excursion, and H (inertia constant) sets the response speed.

  • Equal-area criterion: transient stability holds when the available decelerating area equals or exceeds the accelerating area; critical clearing time is when the two areas just balance.

  • Load flow: Newton–Raphson converges quadratically but needs a Jacobian each iteration; Gauss–Seidel is simple and slow; both solve the Y_bus power balance equations.

  • Three-phase fault at a bus: I_f = V_th / (√3 |Z_th|) using per-phase Thevenin impedance, with prefault voltage typically assumed 1.0 pu.

Quick reference

Protection

  • Distance relay zone 1 reaches approximately 80–85% of the protected line with no intentional delay so that it underreaches the remote bus; zone 2 reaches roughly 120–150% with a coordinating time delay.

  • Differential protection compares currents entering and leaving the protected zone; balanced through-fault current produces no operating signal, while an internal fault produces a differential current.

  • Overcurrent coordination: the device closest to the fault clears first; time-current curves, pickup multiples, and the coordination time interval set the grading margin between upstream and downstream relays.

  • Generator protection functions include 87G (differential), 51V (voltage-restrained overcurrent), 40 (loss of field), 32 (reverse power), 46 (negative sequence), and 59/27 (over/under voltage).

  • Directional overcurrent elements need a polarizing quantity (voltage, current, or memory) to establish a reference so that they respond only to faults in the intended direction.

  • Current transformer saturation distorts secondary current, delays relay pickup, and can cause overreach or miscoordination; DC offset in the primary current worsens saturation.

  • Transformer differential protection must compensate for the phase shift and ratio of wye-delta windings, and use harmonic restraint (often second harmonic) to avoid tripping on magnetizing inrush.

  • Breaker failure protection trips all surrounding breakers after a short timer if current through the faulted breaker persists after a trip command.

Quick reference

Power Electronics

  • Single-phase full-controlled rectifier: V_dc = (2 V_m / π) cos α for continuous conduction; output becomes negative for α > 90°, permitting inversion.

  • Three-phase full bridge (six-pulse) rectifier: V_dc = (3√3 V_m / π) cos α ≈ 1.35 V_LL cos α, with V_m the peak phase voltage.

  • Buck chopper: V_o = D · V_in; boost chopper: V_o = V_in / (1 − D); both relations assume continuous inductor conduction and ideal switches.

  • Line-commutated converter: V_d = V_d0 cos α − (3/π) X_c I_d, where the second term is the commutation (reactance) voltage drop.

  • Twelve-pulse operation uses two six-pulse bridges fed by delta and wye secondaries; the 30° shift cancels the 5th and 7th harmonic currents on the AC side.

  • PWM inverters control both magnitude and frequency; the modulation index sets fundamental output, and higher switching frequency pushes harmonics to higher orders for easier filtering.

  • Thyristors turn off only at natural current zero (line commutation), while IGBTs and GTOs allow forced commutation; snubbers limit dv/dt and di/dt and dissipate switching energy.

  • Rectifier input power factor degrades as firing angle increases; displacement factor ≈ cos α, and total power factor also includes current harmonic distortion.