- Per-unit impedance base
- Z_base equals base voltage squared divided by base voltampere. Divide actual ohms by Z_base to get per-unit, which is unchanged across an ideal transformer regardless of side.
- Balanced three-phase power
- Total apparent power equals square root of three times line-to-line voltage times line current. Real power multiplies that product by the cosine of the power factor angle.
- Series resonance
- A series RLC circuit resonates when inductive and capacitive reactances are equal. Impedance becomes purely resistive, current is limited only by resistance, and reactive voltages can exceed the source.
- Two-wattmeter method
- On a balanced three-phase load, the two wattmeter readings add to give total real power, and root three times their difference gives total reactive power.
- Current transformer open secondary
- Opening a current transformer secondary while primary current flows removes the counter-flux, producing very high secondary voltage. Short the secondary before changing connected burdens.
- Synchronous speed
- The rotating field speed in revolutions per minute equals one hundred twenty times frequency divided by pole count. A sixty-hertz four-pole machine therefore runs at eighteen hundred rpm.
- Slip
- Slip is the difference between synchronous speed and rotor speed divided by synchronous speed. Rotor frequency equals slip times stator frequency, and rotor reactance falls with low slip.
- Induction motor torque
- Developed torque varies approximately with the square of terminal voltage. A ten percent voltage reduction therefore cuts torque about nineteen percent while lengthening acceleration and raising rotor heating.
- Power angle equation
- For a round-rotor synchronous machine, real power approximately equals internal voltage times terminal voltage divided by synchronous reactance, all multiplied by sine of the power angle.
- Transformer impedance referral
- Impedance on the secondary referred to the primary is multiplied by the square of the turns ratio. The per-unit impedance value is identical on both sides of the transformer.
- Surge impedance
- The characteristic impedance of a lossless overhead line is the square root of inductance divided by capacitance, typically a few hundred ohms. Cables have much lower surge impedance.
- Ferranti effect
- On a long, lightly loaded or open transmission line, receiving-end voltage exceeds sending-end voltage because charging current through series inductance adds voltage along the line.
- Voltage regulation
- Voltage regulation is the no-load receiving voltage minus full-load receiving voltage, divided by full-load receiving voltage, expressed as a percentage at a stated load power factor.
- Bundle conductors
- Two or more subconductors per phase reduce series inductive reactance and corona loss, and increase the effective geometric radius compared with a single conductor of the same total area.
- Corona
- Ionization of air at conductor surfaces above a threshold voltage gradient causes power loss, audible noise, and radio interference. Larger conductors and bundled phases raise the inception voltage.
- Symmetrical components
- Any unbalanced three-phase set separates into positive, negative, and zero sequence sets. The operator a is one at one hundred twenty degrees, and a squared is at two hundred forty degrees.
- Zero-sequence path
- Zero-sequence current needs a grounded return path. It flows through grounded-wye windings and grounded neutrals but cannot pass through an ungrounded delta or ungrounded neutral.
- Per-unit base change
- Converting per-unit impedance to a new base multiplies the old value by the old-to-new base voltage ratio squared and by the new-to-old base power ratio.
- Swing equation
- Rotor angle accelerates in proportion to the difference between mechanical and electrical power. The inertia constant and synchronous speed determine how rapidly the angle changes.
- Equal-area criterion
- Transient stability is assessed by comparing the accelerating area with the available decelerating area. Stability holds when decelerating area equals or exceeds the accelerating area.
- Line-to-ground fault current
- Single line-to-ground fault current equals three times the prefault positive-sequence voltage divided by the sum of positive, negative, and zero sequence impedances plus three times ground impedance.
- Distance zone one reach
- Zone one typically reaches eighty to eighty-five percent of the protected line with no intentional time delay, deliberately underreaching so it never operates for faults beyond the remote terminal.
- Differential protection
- Differential relaying compares currents entering and leaving the protected zone. Equal through-fault currents balance and produce no operation, while an internal fault creates a differential current.
- Overcurrent coordination
- Protective devices are graded so the device nearest a fault trips first. Time-current curves, pickup multiples, and the coordination time interval establish the margin between successive devices.
- Loss-of-field relay
- This element detects an under-excited or open-field generator condition, usually through impedance or admittance measurement, and trips to prevent machine overheating and system voltage collapse.
- Reverse power relay
- Applied to generators to detect motoring, when real power flows from the system into the machine. It typically operates after loss of the prime mover or turbine trip.
- CT saturation effect
- When a current transformer saturates, its secondary no longer reproduces the primary current, delaying relay pickup and potentially causing overreach or miscoordination between protective zones.
- Controlled rectifier output
- A single-phase full converter with firing angle alpha delivers an average direct voltage of twice the peak input voltage divided by pi, multiplied by cosine of alpha.
- Buck converter duty ratio
- An ideal buck converter produces an output voltage equal to duty ratio times input voltage. The switch conducts for fraction D of each switching period in continuous conduction.
- Boost converter
- An ideal boost converter steps voltage up by a factor of one divided by one minus the duty ratio, assuming continuous inductor current and ideal lossless components.
- Twelve-pulse rectifier
- Two six-pulse bridges fed from delta and wye transformer secondaries produce twelve-pulse operation, cancelling the fifth and seventh harmonic currents on the alternating-current side.
- HVDC converter voltage
- The direct voltage of a line-commutated converter equals its ideal no-load value times cosine of the firing angle, minus the drop caused by commutation reactance.