Quick reference

Fundamentals, Terminology, and Core Concepts

  • Ohm's law: V = I × R. Power: P = V × I = I² × R.

  • Series circuits: RT = R1 + R2 + … and the same current flows through every element. Parallel circuits: 1/RT = 1/R1 + 1/R2 + … and the same voltage appears across every branch.

  • A normally closed (NC) zone trips on an open circuit; a normally open (NO) zone trips on a closed circuit. Supervised alarm zones use the NC configuration with an end-of-line resistor.

  • The EOL resistor value must equal the zone value programmed in the panel (common values are 1 kΩ, 2.2 kΩ and 4.7 kΩ); a mismatch produces a permanent trouble or a false alarm.

  • Class 2 and Class 3 circuits are power-limited and covered by NEC Article 725; fire alarm circuits by Article 760; communications circuits by Article 800.

  • Fail-safe (powered-to-lock) hardware unlocks when power is lost; fail-secure (powered-to-unlock) hardware stays locked when power is lost and is used where egress is released by a request-to-exit device.

  • A 4–20 mA analog loop uses 4 mA as 0 % (live zero) and 20 mA as 100 %; a reading below 4 mA indicates an open loop or a failed transmitter.

  • Sound pressure adds logarithmically: a 6 dB increase is roughly double the acoustic pressure, and a 10 dB increase is roughly double perceived loudness.

Quick reference

Installation, Setup, and Configuration

  • Cat5e/Cat6 horizontal channel is limited to 100 m (328 ft) including all patch and equipment cords; the permanent link is limited to 90 m.

  • RS-485: up to about 1200 m (4000 ft) of twisted pair, daisy-chain topology, no star branches, and 120 Ω termination at both physical ends of the bus.

  • RS-232: approximately 15 m (50 ft) maximum at 9600 bps.

  • T568B pin order, pins 1–8: white-orange, orange, white-green, blue, white-blue, green, white-brown, brown.

  • PoE budgets: 802.3af provides 15.4 W at the PSE and 12.95 W at the PD; 802.3at (PoE+) provides 30 W at the PSE and 25.5 W at the PD.

  • Standby battery capacity: Ah = (standby current × standby hours + alarm current × alarm hours) × 1.25 aging/derating factor.

  • Maintain at least 2 in. (50 mm) of separation between low-voltage/communications cable and power conductors; where separation is impossible, cross at 90°.

  • Voltage drop on a two-wire run: Vd = I × (2 × L × R), where R is conductor resistance per unit length and L is the one-way length.

Quick reference

Operation, Monitoring, and Maintenance

  • Video storage per camera: GB/day ≈ bitrate in Mbps × 10.8; total storage = per-camera value × camera count × retention days.

  • Sealed lead-acid standby batteries typically serve 3–5 years; a load-test capacity below 80 % of rating indicates replacement is due.

  • A dynamic (under-load) battery test is required because a float-voltage reading alone will not reveal a failed cell.

  • Cross-zoning (alarm verification) requires two detectors in the same area to trip within a defined window before an alarm is transmitted, reducing false dispatches.

  • NTP synchronization keeps panel, recorder and access-control logs on a common time base; clock drift breaks incident correlation.

  • The daily automatic test signal confirms the communication path (dial-capture, IP or cellular); a missing test signal is reported as a communication trouble.

  • Camera image faults map to specific controls: blur to back focus, washout to exposure/WDR, banding to the anti-flicker 50/60 Hz setting, smearing to bitrate or I-frame interval.

  • Maintenance entries must record device ID, test method, result, technician and date to remain traceable.

Quick reference

Testing, Inspection, and Troubleshooting

  • Measure voltage with the circuit energized and the meter in parallel; measure resistance only with power removed and the component isolated.

  • Zone diagnostics: near 0 Ω indicates a short, an infinite reading indicates an open, and a reading offset by the EOL value places the fault on the panel side of the resistor.

  • Half-split method: divide the circuit at its midpoint, determine which half contains the fault, and repeat - a fault is located in log₂(n) tests.

  • A time domain reflectometer reports the distance to an open, short or impedance mismatch, so cable damage can be located without destructive access.

  • Cat6 certification covers wire map, length, insertion loss, NEXT and return loss; a pass requires every parameter to be within the standard's limits.

  • A ground fault on a supervised loop is found by measuring resistance from each conductor to earth; the low reading identifies the compromised leg.

  • Smoke detectors are functionally tested with calibrated aerosol or test gas and must annunciate at the panel; heat detectors are tested with a heat source or manufacturer magnet test.

  • IP device no-response order: verify power and link LEDs, ping the address, check for IP conflict or VLAN error, then substitute a known-good device.

Quick reference

Codes, Regulations, and Safety Practices

  • NFPA 72 governs fire detection and alarm system installation, testing and inspection; NFPA 731 governs premises security system installation.

  • NEC Article 760 covers fire alarm cable (FPL, FPLR, NPLF); Article 725 covers Class 1/2/3 remote-control and signal circuits; Article 800 covers communications cabling.

  • Cable installed in air-handling (plenum) spaces must be listed CMP; riser cable is CMR; general-purpose is CM/CMG.

  • OSHA 1910.147 requires lockout/tagout of all hazardous energy before servicing, verified by an attempted start; NFPA 70E sets arc-flash PPE and approach boundaries.

  • Fall protection is required in general industry at 4 ft (1.2 m) and in construction at 6 ft (1.8 m).

  • Ladder setup follows the 4:1 rule - 1 ft of base setback for every 4 ft of working height - with the ladder extending 3 ft above the landing.

  • Every penetration of a rated wall or floor must be firestopped with a listed system that restores the assembly's fire resistance rating.

  • NFPA 101 requires egress doors to release on fire alarm signal; fail-safe locks must be tied to the fire alarm system and to a manual release.

Quick reference

Documentation, Reporting, and Customer Handoff

  • The Record of Completion (NFPA 72) documents the installed system, device list and test results, signed by the installing contractor and the owner's representative.

  • As-built drawings must reflect field conditions: device addresses, zone schedules, cable identifiers, IP address tables and panel locations.

  • The battery calculation sheet, voltage-drop calculations and device test records are retained in the job file.

  • A punch list records every open deficiency with an assigned owner, a due date and a closure signature; the job is not complete until all items are closed.

  • Handoff training is documented with date, topics covered, attendee names and signatures.

  • Default installer and user passwords are changed at handoff and the new credentials are recorded in the secured handover document.

  • Warranty terms, service contact information and the preventive-maintenance schedule are delivered in writing as part of the closeout package.