Quick reference

Industrial Refrigeration I

  • The mechanical refrigeration cycle has four steps: compression, condensation, expansion, evaporation; heat is absorbed in the evaporator and rejected in the condenser.

  • Saturation temperature is the temperature at which a refrigerant boils or condenses at a given pressure; it rises as pressure rises and falls as pressure falls.

  • Superheat = actual vapor temperature minus saturation temperature at the same pressure. Subcooling = saturation temperature minus actual liquid temperature at the same pressure.

  • Compression ratio = absolute discharge pressure divided by absolute suction pressure; absolute pressure = gauge pressure plus atmospheric pressure.

  • Refrigerating effect = enthalpy of vapor leaving the evaporator minus enthalpy of liquid entering the evaporator.

  • Work of compression = discharge enthalpy minus suction enthalpy; COP = refrigerating effect divided by work of compression.

  • 1 ton of refrigeration = 12,000 Btu/h = 200 Btu/min = 3.517 kW.

  • Ammonia has a much higher latent heat of vaporization than halocarbon refrigerants, so a given capacity needs a lower refrigerant mass flow.

  • Ammonia is not miscible with mineral oil, so oil is removed by separators, drains, and oil pots rather than returning with the refrigerant.

Quick reference

Industrial Refrigeration II (Systems)

  • Low side: evaporator, suction line, accumulator, and low-pressure receiver up to the compressor suction. High side: discharge line, condenser, receiver, and liquid line.

  • Single-stage compressors become inefficient and run hot at high compression ratios; low-temperature duty generally uses two-stage or compound systems.

  • Screw compressors control capacity with a slide valve; reciprocating compressors use cylinder unloading or variable speed.

  • Pumped liquid recirculation systems use a low-pressure receiver and pump; typical overfeed rates are 2:1 to 4:1.

  • Thermosyphon oil cooling circulates liquid refrigerant by density difference; liquid injection and water-cooled oil coolers are the alternatives.

  • Evaporative condensers reject heat by evaporating water in an air stream and require water treatment plus bleed to control scale and biological growth.

  • Noncondensable gases collect in the condenser and raise head pressure; they are removed by a purger from the highest point of the high side.

  • Hot gas defrost routes discharge vapor through the evaporator to melt frost and must be followed by a drain-down period before refrigeration resumes.

  • EPR valves hold minimum evaporator pressure, CPR valves limit compressor suction pressure, and hot gas bypass holds a minimum load on the compressor.

Quick reference

Industrial Refrigeration IV (Plant Operation and Safety)

  • OSHA permissible exposure limit for ammonia is 50 ppm as an 8-hour TWA; NIOSH IDLH is 300 ppm; the odor threshold is well below both values.

  • Ammonia burns in air at roughly 15 to 28 percent by volume; it is toxic, lighter than air, and rises when released.

  • Ammonia attacks copper and copper alloys, so ammonia service uses steel, stainless steel, and compatible elastomers, not brass or bronze.

  • OSHA Process Safety Management applies to ammonia systems containing 10,000 lb or more and requires hazard analysis, written procedures, training, and mechanical integrity.

  • Before opening any component: pump down or isolate, lock out energy sources, bleed pressure to zero, and verify zero pressure on a gauge.

  • Never cap, plug, or block a relief valve; relief discharge must be piped to a safe, unrestricted location.

  • Ammonia emergency PPE: SCBA or supplied-air respirator, full face shield, chemical goggles, impermeable gloves, and protective suit.

  • Emergency sequence: sound the alarm, evacuate unprotected personnel upwind, isolate or shut down the source, ventilate, and re-enter only with PPE and a buddy.

  • Hot work on or near refrigeration equipment requires a permit, gas testing before and during the job, and a fire watch.

Quick reference

Basic Electricity I

  • Ohm's law: V = I × R. Power: P = V × I, also written I²R or V²/R for resistive loads.

  • Series: total resistance is the sum of the resistances, current is common to all loads, and voltage divides across them.

  • Parallel: voltage is common to all branches, current divides, and 1/R_total = 1/R1 + 1/R2 + … so total resistance is below the smallest branch.

  • Peak and RMS: V_peak = 1.414 × V_rms and V_rms = 0.707 × V_peak; a 480 V RMS line has a peak of about 679 V.

  • Balanced three-phase power: P = √3 × V_line × I_line × power factor.

  • Synchronous speed N = 120 × f ÷ poles; slip = (N_synchronous − N_actual) ÷ N_synchronous.

  • A voltmeter is connected in parallel with the load; an ammeter or clamp meter is connected in series with the conductor.

  • Overload protection guards the motor against sustained overcurrent; fuses and breakers protect conductors against short-circuit and ground-fault current.

  • Single-phasing a three-phase motor makes the remaining windings draw high current and overheat; phase-loss protection is required.

  • Power factor = kW ÷ kVA; capacitors supply reactive current and raise power factor.

Quick reference

Basic Electricity II (Ladder Diagrams)

  • Ladder rungs are read left (power rail) to right (neutral rail); a coil energizes only when a complete path exists through the rung.

  • Contacts are named and drawn in the de-energized state: a normally open contact closes when actuated, a normally closed contact opens when actuated.

  • Start pushbuttons are wired in parallel, stop pushbuttons in series, with the contactor coil in the rung.

  • A seal-in (holding) contact is wired in parallel with the start pushbutton to keep the coil energized after the button is released.

  • Safety devices - high-pressure cutout, low-oil switch, overload contact - are wired in series so any one opens the control circuit and stops the machine.

  • Standard symbols: contactor coil, normally open and normally closed contacts, overload heater, time-delay contacts, and pressure, float, and thermostat switches.

  • Wire numbers and device designations let you trace a circuit between sheets; the same number identifies the same conductor.