Saturation temperature
The temperature at which a refrigerant boils or condenses at a given pressure, with liquid and vapor present together. Raising the pressure raises the saturation temperature.
Superheat
The difference between the actual temperature of vapor and the saturation temperature at the same pressure. Measured at the evaporator outlet, it confirms the coil is fully fed with liquid.
Subcooling
The difference between saturation temperature and the actual liquid temperature at the same pressure. It proves the liquid line is solid and increases the refrigerating effect per kilogram.
Compression ratio
Absolute discharge pressure divided by absolute suction pressure. A high ratio raises discharge temperature, reduces volumetric efficiency, and pushes the system toward two-stage compression.
One ton of refrigeration
A capacity of 12,000 Btu per hour, 200 Btu per minute, or 3.517 kilowatts of heat removal. It is the standard basis for rating refrigeration equipment.
Latent heat of vaporization
The heat absorbed when a liquid changes to vapor at constant saturation temperature. Ammonia's high latent heat means a smaller mass flow is needed for a given capacity.
Coefficient of performance
Refrigerating effect divided by work of compression in the same units. A higher value means more cooling is produced per unit of energy input to the compressor.
Low side
The portion of the system at evaporating pressure: evaporator, suction line, accumulator, and low-pressure receiver, extending up to the compressor suction connection.
Flooded evaporator
An evaporator kept completely full of liquid refrigerant, with vapor separated in a low-pressure receiver and liquid recirculated by gravity or by a pump.
Overfeed rate
The mass of liquid refrigerant supplied to an evaporator divided by the mass evaporated there. Pumped recirculation systems commonly run between two and four to one.
Evaporative condenser
A condenser in which water sprayed over the coil evaporates into an air stream, rejecting heat. It needs water treatment and bleed to control scale and biological growth.
Thermosyphon oil cooling
Liquid refrigerant from the receiver circulates to the oil cooler because of density difference and returns as vapor to the condenser, cooling compressor oil without a pump.
Hot gas defrost
Discharge vapor from the compressor is routed through an evaporator to melt frost from the coil. A drain-down period follows before the coil returns to refrigeration.
EPR valve
Evaporator pressure regulator. It maintains a minimum evaporating pressure in a coil, keeping the coil temperature from dropping too low for the product or the room.
Ammonia IDLH
The immediately dangerous to life or health concentration for ammonia is 300 parts per million. Entry at or above this level requires supplied-air respiratory protection.
Ammonia PEL
The OSHA permissible exposure limit for ammonia is 50 parts per million as an eight-hour time-weighted average. Gas detectors are usually set to alarm well below that.
Ammonia flammability range
Ammonia will burn in air at roughly 15 to 28 percent by volume. A high-energy ignition source is needed, and the odor is detectable long before that range.
PSM threshold, ammonia
OSHA Process Safety Management applies to ammonia systems containing 10,000 pounds or more, requiring process hazard analysis, written operating procedures, training, and mechanical integrity programs.
Pump-down procedure
Refrigerant is removed from the section to be serviced and stored in a receiver or another part of the system, then the isolated section is bled to zero pressure and verified.
Lockout/tagout
Isolating every energy source, applying locks and tags, and trying the equipment to confirm it will not start before maintenance begins on the machine.
Ohm's law
Voltage equals current multiplied by resistance, written V = I × R. It applies to DC circuits and to AC circuits that are purely resistive.
Electrical power formula
Power in watts equals voltage times current, P = V × I. It can also be written as I²R or V²/R for resistive loads.
Series circuit
A circuit with only one current path. Current is the same through every component, total resistance is the sum, and the source voltage divides across the loads.
Parallel circuit
A circuit with more than one current path. Voltage is the same across every branch, current divides, and total resistance is lower than the smallest branch resistance.
Three-phase power
For a balanced three-phase load, power equals the square root of three times line voltage times line current times power factor.
Motor synchronous speed
Calculated as 120 times frequency divided by the number of poles. At 60 hertz a four-pole motor has a synchronous speed of 1800 rpm and runs slightly slower when loaded.
Ladder diagram
A control schematic drawn with two vertical power rails. Each rung is read left to right, and a coil energizes only when a complete path exists through the rung.
Normally open contact
A contact drawn open when its operating device is de-energized. It closes to complete the circuit when the coil, switch, or operator is actuated.
Seal-in circuit
A holding contact wired in parallel with a momentary start pushbutton. After the button is released, the contact keeps the coil energized until a stop device opens.
Stop button wiring
Stop pushbuttons and safety switches are wired in series with the coil, so opening any one of them breaks the path and de-energizes the circuit.
Interlock
A contact taken from one device and wired into another device's circuit so the two cannot run together or operate out of the required sequence.
Overload heater
A thermal element in a motor starter that bends or melts when sustained current exceeds the motor rating, opening the control circuit through the overload contact.