Air Conditioning Systems

  • Nominal capacity: 1 ton = 12,000 Btu/h; nominal airflow is about 400 cfm per ton (design range roughly 350–450 cfm/ton).

  • Total capacity = sensible + latent; sensible heat ratio (SHR) = sensible capacity ÷ total capacity.

  • Air-side total capacity (Btu/h) ≈ 4.5 × cfm × Δh, where Δh is the enthalpy difference across the coil in Btu/lb dry air.

  • Sensible capacity (Btu/h) ≈ 1.08 × cfm × ΔT at standard air conditions.

  • Evaporator superheat is measured at the suction line outlet; typical target for fixed-orifice systems is 8–12°F, while TXV systems are charged by subcooling.

  • Typical evaporator air temperature drop is 16–22°F; low ΔT suggests low load, high airflow, or dirty coil; high ΔT suggests low airflow.

  • R-410A is a near-azeotropic HFC blend with small glide and requires POE oil; operating pressures are roughly 1.5–2 times R-22 at the same saturation temperature.

  • Dehumidification requires the coil surface temperature to be below the entering air dew point; apparatus dew point is the coil surface condition at the air leaving condition.

  • Compressor short cycling can result from oversizing, low refrigerant charge, faulty thermostat, or a tripped safety control.

Quick reference

Heating Systems

  • Electric resistance heat: 1 kW = 3,413 Btu/h; capacity (Btu/h) = kW × 3,413.

  • Furnace temperature rise (°F) = output Btu/h ÷ (1.08 × cfm); typical natural-gas furnace rise is 35–65°F.

  • Natural gas heating value is about 1,000 Btu/ft³; LP gas about 2,500 Btu/ft³.

  • Standard combustion air rule: 50 ft³ of space per 1,000 Btu/h input for unconfined spaces; grilles sized for free area.

  • Natural gas manifold pressure is typically 3.5 in. w.c.; LP manifold pressure is typically 10–11 in. w.c.

  • AFUE measures annual fuel utilization efficiency; condensing furnaces (90%+) recover latent heat and produce acidic condensate.

  • A cracked heat exchanger can introduce carbon monoxide; inspect with combustion analysis and visual/leak testing.

  • Heat pump balance point is the outdoor temperature where heat pump capacity equals building heat loss; auxiliary heat covers below it.

  • Limit switches and rollout switches are safety devices that open the gas valve on excess temperature or flame rollout.

Quick reference

Refrigeration Systems

  • Saturation temperature is the temperature at which a refrigerant changes phase at a given pressure; superheat is vapor temperature above saturation.

  • Subcooling is liquid temperature below saturation; TXV charging targets subcooling, while fixed orifice targets superheat.

  • Compression ratio = absolute discharge pressure ÷ absolute suction pressure; high ratios increase discharge temperature and reduce capacity.

  • A TXV modulates refrigerant flow to maintain a constant evaporator superheat as load changes.

  • Refrigerant recovery cylinders must not be filled above 80% of capacity by weight/volume.

  • Deep vacuum for dehydration is typically 500 microns; triple evacuation with nitrogen sweeps removes moisture and noncondensables.

  • HFC refrigerants such as R-410A and R-134a require POE lubricant; mineral oil is used with CFC/HCFC refrigerants.

  • Noncondensables raise discharge pressure and reduce capacity; they are removed by proper evacuation, not by adding refrigerant.

  • Refrigerant leaks are located with electronic detectors, soap bubbles, or UV dye; EPA Section 608 certification is required to handle refrigerant.

Quick reference

Electrical, Controls, and Components

  • Ohm’s law: E = I × R; power in a resistive circuit: P = E × I = I²R.

  • Single-phase power (W) = volts × amps × power factor; three-phase power = √3 × volts × amps × power factor.

  • A 24V control circuit is Class 2 low voltage; R is 24V hot, C is common, Y calls cooling, W calls heat, G calls fan.

  • Start capacitors increase starting torque and are removed by a potential relay or centrifugal switch after startup.

  • Run capacitors are rated in microfarads (µF); a bulged or failed run capacitor causes high current and poor motor performance.

  • Contactors switch line voltage; overloads protect motors from sustained overcurrent, not short circuits.

  • NEC requires a disconnecting means within sight of and within 50 ft of the equipment; it must be lockable.

  • Continuous loads are sized at 125% of the load for conductor and overcurrent sizing.

  • Motor service factor above 1.0 allows limited overload; nameplate RLA/LRA values are used for branch-circuit and breaker sizing.

Quick reference

Load Calculations, Duct Design, and Installation Practices

  • ACCA Manual J calculates room-by-room heating and cooling loads; Manual S selects equipment; Manual D designs ducts; Manual T selects outlets.

  • Heat loss through an assembly: Q = U × A × ΔT, where U is the overall heat-transfer coefficient.

  • Sensible infiltration/ventilation load: Q ≈ 1.08 × cfm × ΔT; latent load uses the enthalpy or moisture difference.

  • Typical residential duct design friction rate is about 0.1 in. w.c. per 100 ft of equivalent length.

  • Duct cross-sectional area (ft²) = cfm ÷ velocity (ft/min); round duct area = π × radius².

  • Equivalent length adds straight duct plus fitting losses; elbows and transitions can dominate total pressure drop.

  • A typical fan static-pressure budget is about 0.5 in. w.c. total, split between supply and return; flex duct adds more resistance if compressed.

  • Flex duct must be fully extended, supported, and kept with gradual bends; sharp bends and sagging reduce airflow.

  • Condensate drains require a trap sized to the fan static pressure and a secondary drain or float switch for overflow protection.

Quick reference

Texas Statutes, Administrative Rules, Safety, and Business Practices

  • Texas Occupations Code Chapter 1302 governs air conditioning and refrigeration contracting; the Texas Department of Licensing and Regulation (TDLR) administers the license.

  • 16 Texas Administrative Code Chapter 75 contains the ACR licensing, technician registration, and enforcement rules.

  • A licensed A/C contractor is responsible for the work performed under the license; technicians work under contractor supervision as required by rule.

  • Local permits and inspections are separate from the state license; state licensure does not replace municipal code requirements.

  • EPA Section 608 certification is required for technicians who service, repair, or dispose of refrigerant-containing equipment.

  • OSHA requires fall protection for work at 6 ft or more in construction; ladders and roof work require documented safety procedures.

  • Lockout/tagout isolates electrical and gas energy before service; verify with a meter and bleed stored pressure.

  • Carbon monoxide is produced by incomplete combustion; install CO alarms and perform combustion analysis on fuel-burning equipment.

  • Texas Deceptive Trade Practices Act and licensing rules prohibit false advertising and require accurate representations of services and credentials.