TX HVAC Contractor study materials
TX HVAC Contractor study resources

TX HVAC Contractor flashcards

TX HVAC Contractor · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Sensible heat ratio
The ratio of sensible cooling capacity to total cooling capacity; total capacity is the sum of sensible and latent capacity.
One ton of cooling
A cooling rate of 12,000 Btu per hour, approximately the heat needed to melt one ton of ice in 24 hours.
Evaporator superheat
The number of degrees the suction vapor is above its saturation temperature at the evaporator outlet; measured with a gauge and thermometer.
Subcooling
The number of degrees the liquid refrigerant is below its saturation temperature at the condenser outlet; used to verify charge in TXV systems.
Evaporator delta T
The dry-bulb temperature difference between return air entering and supply air leaving the evaporator; typically 16 to 22 degrees Fahrenheit.
Apparatus dew point
The effective coil surface temperature at the air leaving condition; dehumidification occurs when this is below the entering air dew point.
Furnace temperature rise
The supply-air temperature minus return-air temperature across a furnace; calculated as output Btu/h divided by 1.08 times cfm.
AFUE
Annual Fuel Utilization Efficiency; the ratio of annual heat output to annual fuel energy input, expressed as a percentage for heating equipment.
Heat pump balance point
The outdoor temperature at which heat pump heating capacity equals the building heat loss; below this point supplemental heat is needed.
Combustion air requirement
Roughly 50 cubic feet of free space per 1,000 Btu/h of gas input for unconfined spaces; confined spaces need dedicated openings.
Manifold pressure
The gas pressure measured at the burner manifold; typically about 3.5 inches water column for natural gas and 10 to 11 for propane.
Saturation temperature
The temperature at which a refrigerant boils or condenses at a given pressure; superheat and subcooling are measured relative to it.
Compression ratio
Absolute discharge pressure divided by absolute suction pressure; high ratios raise discharge temperature and reduce compressor capacity.
TXV function
A thermostatic expansion valve modulates refrigerant flow to maintain a nearly constant evaporator superheat as load and pressure change.
Recovery cylinder limit
A refrigerant recovery cylinder must not be filled above 80 percent of its capacity to allow for liquid expansion and prevent hydrostatic rupture.
Deep vacuum level
A vacuum of about 500 microns is commonly used for dehydration; it removes moisture and noncondensables before charging.
Ohm’s law
The relationship E equals I times R; voltage equals current times resistance, and power equals voltage times current in a resistive circuit.
R terminal
The 24-volt hot terminal on a low-voltage thermostat; it supplies control power to cooling, heating, and fan circuits.
Run capacitor
A microfarad-rated capacitor that stays in the motor circuit to improve running torque and power factor; failure causes high current and poor performance.
Contactor
An electromechanical switch that uses a low-voltage coil to close line-voltage contacts, starting compressors, fans, or electric heaters.
Locked rotor amps
The current a motor draws at startup when the rotor is stationary; used with nameplate data for branch-circuit and overload sizing.
Disconnect within sight
An electrical disconnecting means installed within sight of and within 50 feet of equipment, capable of being locked in the open position.
Manual J
ACCA’s residential load calculation method that estimates room-by-room heating and cooling loads from envelope, orientation, infiltration, and internal gains.
Manual D
ACCA’s duct design method; it uses room airflow, equivalent length, and friction rate to size ducts and select fittings.
Friction rate
The pressure loss per 100 feet of equivalent duct length; residential duct designs commonly use about 0.1 inch water column per 100 feet.
Equivalent length
The total duct length plus the pressure-loss equivalent of fittings; elbows and transitions add substantial resistance to airflow.
Duct area formula
Cross-sectional duct area in square feet equals airflow in cfm divided by duct velocity in feet per minute.
Texas Occupations Code 1302
The Texas statute governing air conditioning and refrigeration contracting, including licensing, technician registration, enforcement, and penalties administered by TDLR.
16 TAC Chapter 75
The Texas Administrative Code chapter containing TDLR rules for air conditioning and refrigeration contractors, technicians, licensing, and enforcement.
EPA Section 608
Federal rule requiring certification for technicians who service, repair, or dispose of appliances containing ozone-depleting or substitute refrigerants.
Fall protection threshold
OSHA generally requires fall protection for construction work at heights of 6 feet or more above a lower level.
Lockout tagout
An energy-control procedure that isolates electrical, gas, or mechanical energy before service and verifies the equipment cannot restart unexpectedly.