AM2 / AM2S study materials
AM2 / AM2S study resources

AM2 / AM2S key terms

AM2 / AM2S · Get comfortable with the vocabulary.

Risk assessment

A careful look at the work before it starts to identify what could cause harm, how likely and how serious that harm is, and what controls will reduce it to an acceptable level.

Related: Method statement, Permit to work
Method statement

A written description of how a particular job will be carried out safely, setting out the sequence of work, who is responsible and the control measures applied at each stage.

Related: Risk assessment, Safe isolation procedure
Permit to work

A formal written authorisation allowing defined work on or near a system for a limited period, recording the isolations and precautions taken and confirming when the system is handed back.

Related: Safe isolation procedure, Lock-off device
Personal protective equipment (PPE)

Items worn or held by the worker, such as safety footwear, gloves, eye protection and a hard hat, that reduce exposure to a hazard and are used alongside other controls, never instead of them.

Related: Risk assessment
Composite installation

The practical task in the assessment where containment, cables, accessories and protective devices must be installed to a given specification, safely and within a set time, to a professional standard.

Related: Consumer unit, Circuit protective conductor (CPC)
Consumer unit

The enclosure at the origin of a domestic installation that holds the main switch, circuit breakers and often RCDs, and from which the final circuits of the premises are supplied.

Related: Miniature circuit breaker (MCB), Residual current device (RCD)
Miniature circuit breaker (MCB)

A small automatic switch that opens on overload or short-circuit current to protect the circuit it supplies, and can be reset by hand once the fault has been dealt with.

Related: RCBO, Consumer unit
Residual current device (RCD)

A device that continuously compares the current leaving in the line conductor with the current returning in the neutral and trips when the imbalance, caused by earth leakage, reaches its rated value.

Related: RCBO, Nuisance tripping
RCBO

A single device that gives a circuit both overcurrent protection and residual current protection, so that an earth fault on that circuit trips only that circuit's own device.

Related: Residual current device (RCD), Miniature circuit breaker (MCB)
Circuit protective conductor (CPC)

The conductor that connects the exposed conductive parts of a circuit, and any associated extraneous conductive parts, back to the main earthing terminal to provide a path for earth fault current.

Related: Main protective bonding conductor, Earth fault loop impedance (Zs)
Main protective bonding conductor

A conductor that links incoming metal services such as water, gas and oil to the main earthing terminal so those services sit at substantially the same potential as the earthing system.

Related: Circuit protective conductor (CPC), Earthing arrangement (TN-S, TN-C-S, TT)
Steel wire armour (SWA) cable

A cable in which a layer of steel wires surrounds the insulated cores to give mechanical protection; when the gland is correctly made off, the armour can also serve as the circuit protective conductor.

Related: Circuit protective conductor (CPC), Fire performance cable
Fire performance cable

A cable designed to keep working, carrying current and maintaining circuit integrity, for a stated time while exposed to fire, used for alarms, emergency lighting and other life safety circuits.

Related: Steel wire armour (SWA) cable
Thermal insulation derating

The reduction applied to a cable's tabulated current rating when the cable is enclosed in thermal insulation, because trapped heat makes the conductor run hotter for the same load.

Related: Composite installation
IP rating

A two-digit code marked on an enclosure stating the degree of protection it gives against entry of solid objects and of water, for example IP44 or IP65.

Related: Consumer unit
Insulation resistance test

A test made with the supply isolated and loads disconnected, applying a steady DC voltage between conductors and earth to measure, in megohms, how well the insulation resists leakage.

Related: Continuity test, Electrical Installation Certificate (EIC)
Continuity test

A low-resistance measurement taken with the supply safely isolated to prove that a conductor, such as a protective or bonding conductor, runs unbroken from one end to the other.

Related: Ring final circuit continuity test, Circuit protective conductor (CPC)
R1 + R2 test

A measurement of the line conductor resistance plus the circuit protective conductor resistance for a radial circuit, taken end to end to prove continuity and to predict the earth fault loop impedance.

Related: Continuity test, Earth fault loop impedance (Zs)
Ring final circuit continuity test

Three linked resistance readings taken at the consumer unit that prove the line, neutral and protective conductors of a ring final circuit are continuous, correctly connected and form one unbroken loop.

Related: Continuity test, R1 + R2 test
Polarity test

A check confirming that line conductors are connected to the line terminals of accessories and that switches are fitted in the line conductor, so single-pole devices isolate safely.

Related: Continuity test
Earth fault loop impedance (Zs)

The total impedance of the earth fault loop, from the origin through the line conductor, the fault and the protective conductor back to the source, used to check disconnection times are met.

Related: External earth fault loop impedance (Ze), R1 + R2 test
External earth fault loop impedance (Ze)

The impedance of the supply and the installation's means of earthing, measured at the origin with the main switch open and all final circuits disconnected.

Related: Earth fault loop impedance (Zs), Earthing arrangement (TN-S, TN-C-S, TT)
RCD trip time test

A test with a dedicated instrument that measures how quickly an RCD operates at its rated residual current and at half that value, compared with the permitted maximum times.

Related: Residual current device (RCD), Nuisance tripping
Electrical Installation Certificate (EIC)

The certificate issued for a new installation or for an alteration, declaring that the design, construction, inspection and testing comply with BS 7671 and supported by schedules of inspection and test results.

Related: Minor Electrical Installation Works Certificate, Insulation resistance test
Minor Electrical Installation Works Certificate

The shorter certificate used for small additions or alterations that do not include a new circuit, recording the work done and the inspection and test results for that work.

Related: Electrical Installation Certificate (EIC)
Electrical Installation Condition Report (EICR)

A report produced after inspecting and testing an existing installation, describing its condition, listing departures from BS 7671 and giving each observation a classification code.

Related: Electrical Installation Certificate (EIC)
Safe isolation procedure

The formal sequence for making equipment dead and keeping it dead: identify the supply, isolate, lock off and sign, prove the tester, prove dead at the point of work, then prove the tester again.

Related: Prove dead, Lock-off device, Proving unit
Prove dead

Using an approved voltage indicator to show that no dangerous voltage exists between every combination of live conductors and between each live conductor and earth at the exact point of work.

Related: Voltage indicator, Proving unit
Voltage indicator

A two-pole test lamp or meter built to the recognised guidance for test leads, with fused leads, finger guards and short exposed probe tips, used to check for the presence of voltage.

Related: Proving unit, Prove dead
Proving unit

A known source of test voltage used immediately before and after the prove-dead step to show that the voltage indicator is working and would actually detect a live supply.

Related: Voltage indicator, Prove dead
Lock-off device

A padlock, lock or locking attachment fitted to an isolator or protective device that physically prevents it being switched back on, usually with a warning notice naming the person working.

Related: Safe isolation procedure, Permit to work
Half-split fault finding

A logical method of testing at the middle of a suspect circuit and using the result to decide which half still contains the fault, repeating until the faulty section is narrowed down.

Related: High-resistance joint
Borrowed neutral

A wiring fault where a circuit's neutral is taken from, or shared with, a different circuit, so that isolating one circuit can leave a neutral live and RCDs may trip unexpectedly.

Related: Nuisance tripping, Safe isolation procedure
High-resistance joint

A loose, corroded or poorly made connection that adds resistance to a conductor, causing local heating, voltage drop and unreliable test readings at that point.

Related: Half-split fault finding
Nuisance tripping

Unwanted operation of an RCD or RCBO when there is no genuine earth fault, often caused by accumulated leakage currents, damp, incorrect wiring or a faulty appliance.

Related: Borrowed neutral, Residual current device (RCD)
Automatic disconnection of supply (ADS)

A protective measure in which a fault is cleared by a protective device opening within a specified time, relying on a suitable earth path and the disconnection time set for the circuit voltage.

Related: Earth fault loop impedance (Zs), Earthing arrangement (TN-S, TN-C-S, TT)
Earthing arrangement (TN-S, TN-C-S, TT)

The way an installation is connected to earth, described as TN-S, TN-C-S or TT according to whether the earth path is a separate supply conductor, a combined neutral and earth, or a local electrode.

Related: Main protective bonding conductor, External earth fault loop impedance (Ze)
Discrimination

Coordination between protective devices so that the device nearest the fault opens first and the rest of the installation stays supplied.

Related: Miniature circuit breaker (MCB), RCBO
SELV

A protective measure in which the circuit is supplied at a safe extra-low voltage from a source such as a safety isolating transformer and is isolated from earth and from other circuits.

Related: IP rating
Part P

The part of the Building Regulations applying in England and Wales that covers electrical safety in dwellings and requires certain notifiable work to be carried out and certified by a competent person.

Related: Minor Electrical Installation Works Certificate