C&G 2079-11 F-Gas Category I flashcards
C&G 2079-11 F-Gas Category I ยท Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- CO2e formula
- Tonnes CO2e equals charge in kilograms multiplied by GWP, then divided by 1,000; this sets leak-check and record thresholds.
- GWP definition
- Global warming potential compares the climate impact of one kilogram of a gas with one kilogram of carbon dioxide over a stated horizon.
- ODP definition
- Ozone depletion potential compares a substance's ozone-destroying effect with CFC-11, which is assigned a reference value of one.
- R-22 status
- R-22 is an HCFC controlled as an ozone-depleting substance; virgin supplies are phased out and recovered material faces separate restrictions.
- Operator responsibility
- The operator must prevent leaks, arrange certified leak checks and recovery, keep records for five years, and ensure only certified competent persons work on the equipment.
- Environmental impact
- F-gas releases increase global warming; ODS releases also deplete ozone; leakage reduces efficiency and raises energy-related indirect emissions.
- Record retention period
- F-gas records, including charge, leak checks, recovery and servicing, must be kept for at least five years and made available to inspectors.
- Deliberate venting ban
- Deliberate release of F-gases or ODS to atmosphere is prohibited; refrigerant must be recovered, recycled, reclaimed or destroyed through authorised routes.
- A2L refrigerant
- A2L refrigerants have lower flammability than A3 but still require ignition control, ventilation, leak detection and flammable-refrigerant procedures.
- A3 refrigerant
- A3 refrigerants are highly flammable and require strict ignition-source exclusion, ventilation, and equipment designed and labelled for flammable refrigerant use.
- Asphyxiation hazard
- Refrigerant vapour is denser than air and can displace oxygen in pits, basements or plant rooms, causing dizziness, unconsciousness or death.
- Thermal decomposition
- Heated refrigerant or refrigerant exposed to flame can form hydrogen fluoride and other toxic, corrosive products, requiring evacuation and respiratory protection.
- Liquid refrigerant frostbite
- Liquid refrigerant contacting skin causes rapid frostbite; impermeable cold-protective gloves and eye protection are required, and liquid must not be trapped against skin.
- Recovery cylinder fill limit
- Recovery cylinders must not be filled above their maximum permitted weight, commonly 80% of water capacity, leaving vapour space for expansion.
- Cylinder valve protection
- Valve caps or guards remain fitted during transport, cylinders are secured upright, and cylinders are never lifted by the valve.
- Risk assessment hierarchy
- Controls are applied in order: eliminate exposure, substitute safer options, use engineering controls, adopt safe systems of work, then PPE.
- PPE for refrigerant work
- Typical PPE includes safety glasses or goggles, chemical-resistant gloves and safety footwear; risk assessment may add flame-retardant clothing and respiratory protection.
- Cylinder heat exposure
- Cylinders must be kept away from flames, heaters and direct sun because heat raises pressure and can cause relief-valve release, rupture or fire.
- Leak check threshold
- Periodic leak checks apply from 5 tonnes CO2e; charge in kilograms multiplied by GWP and divided by 1,000 determines the threshold.
- Leak detection system effect
- A verified automatic leak detection system halves the required leak-check frequency in the 50โ500 and 500-plus tonnes CO2e bands.
- Leak record content
- Leak records identify equipment, refrigerant, charge, CO2e, check date, findings, repairs, technician and leak-detection system verification.
- Leak repair verification
- After a leak repair, the repaired area is rechecked and the result recorded; repeated leaks may trigger additional containment or replacement duties.
- Containment measures
- Containment includes minimising joints, protecting pipework from corrosion and vibration, using correct materials and avoiding unnecessary refrigerant charge.
- Nitrogen pressure test
- Oxygen-free nitrogen with a pressure regulator is used for strength testing; oxygen or compressed air with refrigerant oil can cause fire or explosion.
- Triple evacuation
- Triple evacuation breaks vacuum with nitrogen between stages to remove moisture and non-condensables, followed by a standing vacuum test.
- Vacuum gauge placement
- Vacuum is measured at the system with a calibrated electronic gauge, not at the pump, and the pump is isolated before the standing test.
- Commissioning charge record
- Commissioning records include actual charge by weight, refrigerant type, CO2e, date, equipment identity and adjustments to superheat or subcooling.
- Pressure test safety
- The test area is barricaded, pressure is increased in stages, and a pressurised system is never left unattended during testing.
- Recovery versus recycling
- Recovery removes refrigerant from a system; recycling cleans it on site; reclamation reprocesses it to a specification and requires laboratory analysis.
- Decommissioning recovery
- Before dismantling, all refrigerant is recovered, the quantity recorded, the system labelled, and refrigerant and components disposed of through authorised routes.
- Reclaimed refrigerant analysis
- Reclaimed refrigerant must meet a published specification and be supported by laboratory analysis before it is returned to equipment.
- Recovery cylinder labelling
- Recovery cylinders are labelled with refrigerant identity, owner, date, gross weight and tare weight; mixtures are clearly identified as mixtures.