C&G 2922-34 Solar PV flashcards
C&G 2922-34 Solar PV · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- PV DC live when illuminated
- PV modules produce dangerous DC voltage whenever light falls on them; the DC side remains live even when the AC isolator is open.
- G98 notification threshold
- G98 applies to grid-connected generation up to 16 A per phase, equivalent to 3.68 kW single-phase; install and notify the DNO within 28 days.
- G99 application process
- G99 applies to generation above 16 A per phase; a connection application must be made to the DNO and approval received before commissioning.
- DC isolator rating
- A DC isolator must be rated for the system maximum Voc and Isc and be DC-rated; AC isolators must not be used on PV DC circuits.
- Part P scope
- In England and Wales, electrical work in dwellings is notifiable under Part P; PV installations must comply with BS 7671 and be certified by a competent person.
- Working at height hierarchy
- Avoid work at height where possible; prevent falls using edge protection or scaffolds; mitigate residual risk with harnesses and fall-arrest systems.
- String maximum voltage
- Calculate string Voc at the lowest expected cell temperature using the Voc temperature coefficient; it must not exceed inverter or module maximum system voltage.
- MPPT minimum string voltage
- The string Vmp at the highest expected cell temperature must stay above the inverter MPPT minimum or the inverter will not track maximum power.
- Ideal UK roof pitch
- A south-facing roof at 30–40° tilt gives near-optimal annual yield in the UK; east/west or flatter arrays reduce output and alter the yield profile.
- Roof structural load
- PV arrays typically add 10–20 kg/m²; the roof structure and fixings must be checked for dead, wind and snow loads before installation.
- DC voltage drop target
- Keep DC cable voltage drop typically below 1% to minimise energy loss and avoid inverter input voltage issues; AC drop is usually below 3–5%.
- Inverter DC:AC ratio
- The array peak DC power divided by inverter AC rating; typical ratios are 1.1–1.3 in the UK, balancing clipping losses against yield.
- Shading survey tool
- Use a solar pathfinder, Solmetric SunEye or similar to quantify shade across the year; avoid shading or use optimisers or module-level electronics.
- Module clamp zones
- Mounting clamps must be positioned within the manufacturer's specified clamp zones, commonly 1/4 and 3/4 along the module frame, and torqued correctly.
- Rafter fixing requirement
- Roof hooks and brackets should be fixed into structural rafters or trusses, not just tile battens, using stainless steel fixings sized for wind uplift.
- DC cable rating
- PV DC cable should be double-insulated, UV-resistant and rated at least 1000 V DC, often 1500 V DC, with correct current rating for Isc.
- MC4 connector rule
- Only mate connectors from the same manufacturer and type; use the correct crimp tool and test pull-out; mixed-brand MC4 connectors can overheat.
- Series vs parallel
- Connecting modules in series adds voltages while current stays constant; parallel connection adds currents while voltage stays constant.
- Roof penetration sealing
- Every roof fixing must be sealed with a flashing or sealant compatible with the roof covering to prevent water ingress and long-term decay.
- Inverter AC isolator
- A lockable AC isolator must be installed adjacent to the inverter so the unit can be safely isolated for maintenance and clearly labelled.
- RCD type for inverters
- Some inverters require Type A or Type B RCDs depending on DC residual current characteristics; follow the inverter manufacturer's instructions and BS 7671.
- Anti-islanding requirement
- The inverter must disconnect from the grid when supply is lost, preventing islanding that could endanger utility workers and damage equipment.
- Consumer unit dedicated way
- The PV inverter should be connected via a dedicated MCB or RCBO in the consumer unit, sized to the inverter maximum AC output current.
- Export limitation CT
- A current transformer clamp on the incoming supply measures export; the inverter or export limiter reduces output to stay within the DNO-approved limit.
- Dual supply label
- A warning label at the consumer unit and meter position must state that the installation has a dual supply, including the PV system.
- DC insulation resistance
- Measure insulation resistance of DC strings to earth before connection; a value below 1 MΩ indicates a fault and requires investigation.
- Voc string test
- Measure open-circuit voltage of each string and compare with expected Voc corrected for cell temperature and irradiance; a missing string shows zero or low voltage.
- I-V curve tracing
- An I-V curve tracer compares actual array performance with the expected curve, revealing shading, soiling, mismatch or failed bypass diodes.
- Thermal imaging use
- Thermal cameras detect hot spots, faulty bypass diodes, loose connections and cell damage during commissioning and maintenance inspections.
- RCD trip test
- Test the RCD protecting the inverter AC circuit with a suitable tester; verify trip time and current meet BS 7671 requirements.
- Annual maintenance checks
- Annual checks include visual inspection, connector torque, DC insulation resistance, inverter error logs, cleaning and verification of labels and documentation.
- Ground fault diagnosis
- An earth fault on a PV array is located by isolating strings and testing insulation resistance to earth; the faulty string shows low resistance.