AZ ROC R-11 Electrical study materials
AZ ROC R-11 Electrical study resources

AZ ROC R-11 Electrical cheat sheet

AZ ROC R-11 Electrical · Keep the key ideas within reach.

Quick reference

Electrical Systems and General Electrical Knowledge

  • Ohm's law: E = I × R. Power: P = E × I = I²R = E²/R for resistive loads.

  • Single-phase power: P = V × I × power factor. Balanced three-phase power: P = √3 × line voltage × line current × power factor.

  • Approximate voltage drop: single-phase VD = 2 × K × I × L / circular mils; three-phase VD = √3 × K × I × L / circular mils.

  • A continuous load is expected to operate at maximum current for 3 hours or more; conductors and overcurrent devices are sized at 125% of the continuous load plus 100% of noncontinuous load.

  • In a balanced wye system, line voltage = √3 × phase voltage and line current = phase current. In a balanced delta system, line current = √3 × phase current.

  • Common systems include 120/240 V single-phase, 120/208 V three-phase wye, 277/480 V three-phase wye, and 240/480 V three-phase delta.

  • Conductor ampacity is limited by termination temperature ratings: 60°C, 75°C, or 90°C. The lowest-rated component in the circuit sets the final ampacity unless listed otherwise.

  • Box fill: each 14 AWG conductor counts as 2.00 cubic inches, 12 AWG as 2.25, 10 AWG as 2.50, 8 AWG as 3.00, and 6 AWG as 5.00.

  • In a three-phase wye circuit with linear loads, the neutral carries only unbalanced current; neutral current is zero when the load is balanced.

Quick reference

Wiring Methods, Materials, and Installations

  • Nonmetallic-sheathed cable is permitted in many dry indoor locations but is not permitted in wet locations or where subject to physical damage.

  • EMT must be supported within 3 ft of each box and at intervals not exceeding 10 ft. Rigid metal conduit uses the same 10 ft support interval.

  • Conduit fill limits: 1 conductor = 53% of interior area, 2 conductors = 31%, and 3 or more conductors = 40%.

  • Ampacity derating for current-carrying conductors in a raceway: 4 to 6 conductors = 80%, 7 to 9 = 70%, and 10 to 20 = 50%.

  • NM cable must be secured within 12 in of each box and at intervals not exceeding 4.5 ft.

  • All junction boxes, outlet boxes, and switch boxes must remain accessible; boxes cannot be permanently covered by building finishes.

  • A listed expansion fitting is required where a raceway crosses a building expansion joint.

  • NEC Table 300.5 sets minimum burial cover; PVC raceways for 120/240 V circuits generally require at least 18 in of cover.

  • The grounded conductor and equipment grounding conductor must be separated downstream of the service disconnect; a subpanel neutral bar is not bonded to the enclosure.

Quick reference

Overcurrent Protection, Grounding, and Bonding

  • Standard overcurrent device ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 A, continuing in standard steps above 100 A.

  • The next-higher-standard overcurrent device may be used only under NEC 240.4(B) conditions, generally when the device does not exceed 800 A and the conductor ampacity is adequate for the load.

  • A ground rod must be at least 8 ft long and driven to full length; multiple rods must be spaced at least 6 ft apart.

  • A metal underground water pipe grounding electrode must be supplemented by an additional electrode such as a ground rod.

  • Equipment grounding conductors are sized from NEC Table 250.122 based on the rating of the overcurrent device protecting the circuit.

  • GFCI personnel protection trips at approximately 5 mA of ground-fault current.

  • The grounded neutral conductor is not normally fused or switched; overcurrent protection is placed in the ungrounded conductors.

  • Ground-fault protection of equipment is required for certain 480Y/277 V services rated 1000 A or more under NEC 230.95.

  • Series-rated overcurrent combinations must be listed as a series-rated system; a breaker cannot be substituted unless the listing permits it.

Quick reference

Electrical Equipment, Motors, and Controls

  • Motor branch-circuit conductors are sized at 125% of the motor full-load current from NEC tables, not from the motor nameplate current.

  • Motor overload protection is generally sized at 115% to 125% of the motor nameplate full-load current.

  • Motor branch short-circuit and ground-fault protection is selected from NEC Table 430.52; an inverse-time breaker generally may not exceed 250% of full-load current.

  • A motor disconnecting means must be within sight of the motor and controller or capable of being locked open, unless the Code permits otherwise.

  • Motor overload protection protects the motor from sustained overload; branch-circuit short-circuit protection protects the circuit from fault current.

  • NEC motor full-load current tables are used for conductor and branch short-circuit sizing; nameplate current is used for overload sizing.

  • NEMA 1 enclosures are for indoor use; NEMA 3R is rainproof and weather-resistant; NEMA 4 is watertight; NEMA 12 is dusttight.

  • A motor controller may be remote if the disconnecting means is capable of being locked open and the installation complies with NEC 430.102.

  • Multi-speed motors require branch-circuit conductors and protection based on the highest rated winding current unless the Code specifies otherwise.

Quick reference

National Electrical Code and Arizona Electrical Rules/Statutes

  • The National Electrical Code is a model code; the edition in force and any local amendments are established by the adopting jurisdiction and enforced by its authority having jurisdiction.

  • Arizona Revised Statutes Title 32, Chapter 10 governs contractor licensing and regulation by the Arizona Registrar of Contractors.

  • The Arizona Registrar of Contractors R-11 classification is an electrical contractor license covering electrical contracting within that classification's scope.

  • Arizona law generally prohibits offering or performing contractor work without a valid license; violations can lead to citations, cease-and-desist orders, and civil penalties.

  • Arizona does not issue a statewide journeyman electrician license; individual cities or towns may require their own electrician registration or license.

  • Arizona ROC rules require a written contract for residential work that states the scope, price, and payment schedule.

  • Arizona licensed contractors must include their ROC license number in advertising.

  • Local building departments issue permits and perform inspections; electrical work must pass the required inspections before being concealed or energized.

  • Arizona's preliminary 20-day notice is used by subcontractors and suppliers without a direct contract with the owner to preserve mechanics' lien rights.

Quick reference

Estimating, Safety, and Project Management

  • Markup = (price − cost) / cost. Margin = (price − cost) / price. A 25% markup produces only a 20% margin.

  • Labor cost = quantity × labor unit hours per unit × loaded hourly rate, where the loaded rate includes wages, taxes, insurance, and benefits.

  • Material takeoffs add a waste factor; a common allowance for wire and small materials is 5% to 10%.

  • A change order documents added or deleted work and should be written and signed by the owner or authorized representative before the work proceeds.

  • Lockout/tagout isolates hazardous energy with a lock and tag before servicing equipment; only the person who applied the lock should remove it.

  • An assured equipment grounding conductor program tests temporary cords, receptacles, and tools for grounding continuity and records the tests at required intervals.

  • Arizona 811, formerly Arizona Blue Stake, must be contacted before excavation so underground utilities can be marked.

  • The critical path is the longest sequence of dependent project activities; any delay on that path delays project completion.

  • OSHA electrical construction safety requirements are in 29 CFR 1926 Subpart K, including minimum approach distances and temporary power rules.