Ohm's law
Voltage equals current times resistance (E = I × R); power equals voltage times current, so P = I²R = E²/R for resistive loads.
Three-phase power formula
For a balanced three-phase load, real power equals the square root of three times line voltage times line current times power factor.
Continuous load sizing
A continuous load is expected to operate at maximum current for three hours or more; branch-circuit conductors and overcurrent devices are sized at 125 percent of that load.
Box fill volume
National Electrical Code box fill counts each 14 AWG conductor as 2.00 cubic inches, each 12 AWG as 2.25 cubic inches, and each 10 AWG as 2.50 cubic inches.
Wye neutral current
In a balanced three-phase wye circuit with linear loads, the neutral current is zero; the neutral carries only the unbalanced current when loads differ.
NM cable support
Nonmetallic-sheathed cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet along the run.
EMT support spacing
Electrical metallic tubing must be supported within 3 feet of each box and at intervals not exceeding 10 feet, unless a listed exception applies.
Conduit fill percentages
For conduit fill, one conductor may fill 53 percent, two conductors 31 percent, and three or more conductors 40 percent of the conduit interior area.
Raceway conductor derating
When 4 to 6 current-carrying conductors share a raceway, ampacity is reduced to 80 percent; 7 to 9 conductors to 70 percent; 10 to 20 to 50 percent.
Expansion joint fitting
A listed expansion fitting is required where a raceway crosses a building expansion joint so the conduit can move without buckling or pulling apart.
Standard breaker sizes
Common standard overcurrent device ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 amperes.
Ground rod length
A grounding rod must be at least 8 feet long and driven to full length; multiple rods must be spaced at least 6 feet apart.
Water pipe supplement
When a metal underground water pipe is used as a grounding electrode, it must be supplemented by an additional electrode such as a ground rod.
Equipment grounding conductor
The equipment grounding conductor provides a low-impedance fault path and is sized from National Electrical Code Table 250.122 based on the overcurrent device rating.
GFCI trip threshold
A ground-fault circuit interrupter for personnel protection trips at approximately 5 milliamperes of ground-fault current to reduce electric shock risk.
Motor conductor sizing
Motor branch-circuit conductors are sized at 125 percent of the motor full-load current from the National Electrical Code tables, not the nameplate current.
Motor overload protection
Motor overload protection is typically sized at 115 to 125 percent of the motor nameplate full-load current and protects the motor from sustained overload.
Motor disconnect location
A motor disconnecting means must be within sight of the motor and controller, or capable of being locked open, unless the code permits otherwise.
NEMA 3R enclosure
A NEMA 3R enclosure is weather-resistant and rainproof for outdoor use; it protects against falling rain and is not watertight.
Motor short-circuit protection
Motor branch short-circuit and ground-fault protection is selected from National Electrical Code Table 430.52; an inverse-time breaker generally may not exceed 250 percent of full-load current.
Arizona R-11 license
The Arizona Registrar of Contractors R-11 classification is an electrical contractor license; it authorizes the licensee to contract for electrical work within the scope of that classification.
A.R.S. Title 32 Chapter 10
Arizona Revised Statutes Title 32, Chapter 10 governs contractor licensing and regulation by the Arizona Registrar of Contractors, including electrical contractors.
Unlicensed contracting prohibition
Arizona law generally prohibits a person from offering or performing contractor work without a valid license; violations can lead to citations, cease-and-desist orders, and civil penalties.
Statewide journeyman license
Arizona does not issue a statewide journeyman electrician license; individual cities or towns may require their own electrician registration or license.
NEC local amendments
The National Electrical Code is a model code; in Arizona the edition in force and any amendments are set by the adopting jurisdiction and enforced by its authority having jurisdiction.
Arizona Blue Stake
Arizona 811, formerly Arizona Blue Stake, must be contacted before excavation so underground utilities can be marked; digging before marks is unsafe and may violate law.
Markup versus margin
Markup equals price minus cost divided by cost; margin equals price minus cost divided by price. A 25 percent markup is only a 20 percent margin.
Labor unit estimating
Labor cost equals quantity times the labor unit in hours per unit times the loaded hourly rate, including wages, taxes, insurance, and benefits.
Change order requirement
A change order documents added or deleted work and should be written and signed by the owner or authorized representative before the changed work proceeds.
Lockout tagout
Lockout/tagout isolates hazardous energy with a lock and tag before servicing equipment; only the person who applied the lock should remove it.
Assured grounding program
An assured equipment grounding conductor program tests temporary cords, receptacles, and tools for continuity and records the tests at required intervals.
Critical path method
The critical path is the longest sequence of dependent project activities; any delay on that path delays the entire project completion date.