The Arizona Registrar of Contractors (AZ ROC) issues contractor licenses by classification, and the R-11 Electrical classification is the electrical trade credential within that system. AZ ROC - established in 1931 - licenses and regulates residential and commercial contractors, and licensing is tied to qualifying through examinations plus experience requirements. The AZ ROC R-11 Electrical study guide has 6 sections and about 2,179 words.

01

Electrical Systems and General Electrical Knowledge

Questions in this domain test fundamentals more than memorized tables. Be fluent with Ohm's law (E = I x R), the power formulas (P = I x E for resistive loads; P = 1.732 x E x I x PF for three-phase), and the distinction between kW (real power) and kVA (apparent power).

357 words, about 2 min
02

Wiring Methods, Materials, and Installations

Chapter 3 governs how raceways and cables are installed. Know the common methods by article number and application: NM cable (334), AC (320), MC (330), FMC (348), LFMC (350), EMT (358), IMC (342), RMC (344), PVC (352).

379 words, about 2 min
03

Overcurrent Protection, Grounding, and Bonding

Know the standard ratings in 240.6 and the small-conductor rules in 240.4(D): 14 AWG to 15 A, 12 AWG to 20 A, 10 AWG to 30 A, unless a specific article permits otherwise (motor circuits under 240.4(G) are the classic exception). The next-size-up rule in 240.4(B) allows rounding up only where the device does not exceed 800 A and the load does not exceed the conductor ampacity.

381 words, about 2 min
04

Electrical Equipment, Motors, and Controls

The governing principle is that motor conductors and protection are sized from table values, not nameplate current. Use Tables 430.247 through 430.250 for full-load current (FLC), then apply: branch-circuit conductors at 125 percent of FLC (430.22); overload protection sized to the motor nameplate and service factor (430.32); short-circuit and ground-fault protection per 430.52, typically up to 250 percent of FLC for an inverse-time breaker, 175 percent for a dual-element fuse, and 300 percent for a non-time-delay fuse.

355 words, about 2 min
05

National Electrical Code and Arizona Electrical Rules/Statutes

NFPA 70 is organized into Chapters 1 through 4 (general requirements that apply everywhere), Chapter 5 (special occupancies), Chapter 6 (special equipment), Chapter 7 (special conditions), Chapter 8 (communications), and Chapter 9 (tables). Annexes A through I are informational only and are not enforceable.

365 words, about 2 min
06

Estimating, Safety, and Project Management

The estimate is built from a quantity takeoff against the plans: device counts, fixture counts, linear footage of raceway and cable, panel and gear counts, and equipment. Apply labor units (hours per item or per hundred feet), then multiply by a fully burdened labor rate that includes payroll taxes, insurance, and benefits, typically 25 to 40 percent on top of base wage.