ACI Tilt-Up Supervisor study materials
ACI Tilt-Up Supervisor study resources

ACI Tilt-Up Supervisor flashcards

ACI Tilt-Up Supervisor · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Casting bed flatness tolerance
A common requirement is 1/4 in. deviation in 10 ft measured with a straightedge. Beds outside this tolerance produce panel bow and misalignment at erection.
Bond breaker purpose
A coating applied to the casting surface that prevents concrete from bonding to the bed. It is applied at the manufacturer's coverage rate, often in two perpendicular coats.
Panel thickness tolerance
Typically plus or minus 1/4 in. from the specified thickness. It is verified at multiple perimeter points before and after concrete placement.
Panel plumb tolerance
Commonly 1/4 in. in 10 ft of panel height. Final plumb is checked after all braces are installed and snugged.
Lifting insert design factor
Lifting hardware is commonly designed with a 2:1 factor on the static panel load to account for dynamic effects during the pick.
Panel weight calculation
Panel weight equals volume times concrete unit weight, typically 150 lb per cubic foot. Embeds, insulation, and finishes are added to the total.
Center of gravity balance
Lifting points are placed symmetrically about the panel centroid so the panel hangs level. An unbalanced pick causes rotation and loss of control.
Spreader beam use
A rigging member that keeps slings vertical or at a favorable angle, reducing compression and bending induced in the panel during lifting.
Brace angle efficiency
Braces are most efficient near 45 degrees from horizontal. Angles steeper than 60 degrees reduce the brace's resistance to lateral load.
Two-brace minimum
At least two braces per panel are common, with three for tall or narrow panels. Braces are snugged before the crane releases the load.
Crane load chart use
Capacity is read at the actual lifting radius, not the maximum radius. The load includes panel weight plus rigging and hardware weight.
Outrigger ground pressure
Crane outrigger loads are distributed through mats or cribbing. Ground bearing pressure must not exceed the verified soil capacity.
Tag line control
A rope used to control panel rotation during the lift. Personnel handling tag lines stay clear of the panel's swing path and the exclusion zone.
Job hazard analysis
A document listing tasks, hazards, controls, and responsible persons. It is reviewed with the crew before work begins each shift.
Lift strength verification
Panels are lifted only after field-cured cylinders or maturity testing confirm the concrete meets the lift design strength, often 75 percent of design.
Vapor retarder laps
A 10-15 mil sheet under slabs with sealed laps. Punctures are repaired before concrete placement to preserve the moisture barrier.
Edge form bracing
Edge forms are braced to resist concrete pressure and must not deflect more than about 1/8 in. under placement loads.
Chamfer strip location
A chamfer strip is set on the exposed face side of the edge form, typically 3/4 in., to produce the specified edge detail.
Reveal strip placement
Reveal and rustication strips are attached to the casting surface, not the edge form, so the profile appears on the exposed face.
Embed location tolerance
Commonly plus or minus 1/2 in. in plan unless the connection design requires tighter. Embeds are verified against templates before placement.
Brace anchor embed height
Brace anchor embeds are set at the heights shown on the bracing plan. Location error changes the brace angle and the load it carries.
Exposed face cover
Reinforcement cover on the exposed face depends on exposure class, typically 3/4 in. to 1-1/2 in. for tilt-up panels.
Concrete slump range
Tilt-up panels commonly use 4-6 in. slump unless a plasticizer is approved. Slump is checked against the approved mix design.
Evaporation rate threshold
An evaporation rate above 0.2 lb per square foot per hour indicates a need for hot-weather placement and curing precautions.
Cold-weather concrete limit
Protection is required when ambient temperature falls below 40 F unless the specification states otherwise. Panels are not lifted until strength is verified.
Casting bed layout rule
Panels are placed so all lift points fall within the crane's rated radius at both minimum and maximum reach used in the lift plan.
Erection sequence principle
Panels cast farthest from the building footprint are typically erected first when the crane must reach over them to access nearer panels.
Panel identification marks
Marks are placed on the non-exposed face and must match erection drawings. Orientation arrows ensure the correct face is set outward.
Anchor bolt tolerance
Cast-in anchor bolts are set from survey control, commonly within 1/4 in. horizontal unless structural drawings specify tighter.
Brace removal condition
Temporary braces are removed only after the permanent structural connection is completed and approved by the engineer of record.
Exclusion zone rule
No personnel stand or walk under a suspended panel. The zone is marked and enforced for the duration of the lift.
Nonconforming panel disposition
A panel outside tolerance is documented and dispositioned by the engineer of record. Repair procedures are approved before any repair work begins.