ASSE 5130 · Keep the key ideas within reach.

Quick reference

Cross-Connection Control Fundamentals and Regulations

  • Cross-connection: any actual or potential connection between a potable water system and a source of contamination or pollution; backflow is the unwanted reversal of flow into potable supply.

  • Backsiphonage is caused by negative or sub-atmospheric pressure in the supply; backpressure is caused by downstream pressure exceeding supply pressure (pumps, boilers, elevation, compressed gas).

  • Pollution is a substance that degrades water quality but does not create a health hazard; contamination creates an actual health hazard, so contaminant protection requires a higher degree of protection.

  • Degree of hazard drives the required protection: health hazard (toxic or biological) requires an air gap or reduced pressure principle assembly; non-health hazard permits a double check or atmospheric vacuum breaker depending on application.

  • Authority hierarchy: federal Safe Drinking Water Act sets the floor; state primacy agencies adopt rules; local water purveyors enforce containment through ordinance, plumbing code, and cross-connection control programs.

  • Typical program elements: enabling ordinance, hazard survey, containment versus isolation protection, assembly approval lists, tester certification, and annual testing with records retained per jurisdiction.

  • Premises isolation (containment) protects the public main at the service; internal isolation protects fixtures and processes; a complete program generally uses both, since containment alone does not protect occupants.

  • Cross-connections are controlled by elimination, by an approved air gap, or by a mechanical backflow preventer; no assembly may be substituted for an air gap where an air gap is specifically required.

  • Definitions that appear on exams: cross-connection, backflow, backsiphonage, backpressure, pollution, contamination, air gap, backflow preventer, containment, and auxiliary supply.

Quick reference

Backflow Prevention Assembly Types and Applications

  • Air gap: physical separation of at least twice the effective opening diameter, never less than 1 inch; highest protection, appropriate for health hazards and high-hazard connections.

  • Atmospheric vacuum breaker (AVB): non-testable, no downstream shutoff valve, must be installed at least 6 inches above the highest downstream outlet; used on hose bibbs and irrigation zones.

  • Pressure vacuum breaker (PVB): testable, with a loaded check and an air inlet; must be installed 12 inches above the highest downstream outlet and may have downstream shutoff valves.

  • Double check valve assembly (DCVA): two check valves, testable, for non-health hazards such as low-hazard commercial and irrigation service lines.

  • Reduced pressure principle assembly (RPZ): two check valves plus a hydraulically loaded relief valve; the only mechanical assembly approved for health hazards, and it must not be installed in a pit or submerged location.

  • Spill-resistant vacuum breaker (SVB): a PVB variant with a check that limits discharge at the air inlet; used where a PVB would discharge in normal operation, and it is testable.

  • Specialty devices: dual check (non-testable, residential service), hose connection vacuum breaker, and barometric loop (not a mechanical device, limited to backsiphonage only).

  • Selection rules: health hazard requires an air gap or RPZ; continuous pressure requires a testable device with loaded checks; non-health hazard permits DCVA or PVB depending on backsiphonage risk.

  • Assembly versus device: an assembly is testable and has two or more shutoff valves and test cocks; a device is not testable and does not meet assembly requirements.

Quick reference

Testing Procedures and Equipment

  • Test equipment: differential pressure gauge, test kit hoses, and test cock adapters; gauge must be calibrated and its accuracy verified before use, with calibration records retained.

  • Gauge accuracy is commonly required within plus or minus 2 percent of full scale or a stated psi tolerance; a gauge out of tolerance invalidates the field test.

  • Test sequence for an RPZ: record supply pressure, test check valve 1 (RPZ), test check valve 2, then test the relief valve differential, then verify the relief opens at the required threshold.

  • RPZ relief valve opening point is typically required to open at 2 psi or greater differential; a relief valve that opens below the threshold indicates a failed check or relief valve.

  • Test sequence for a DCVA: test check 1 for tightness, then check 2, using the gauge in series with the test cocks and observing pressure drop or hold.

  • PVB test: verify check valve tightness and verify the air inlet opens at the required vacuum; AVB is not field tested but is inspected for installation height and absence of downstream shutoff.

  • Backsiphonage test: the gauge is used to create a negative pressure by bleeding water through the high side, then observing whether the check holds.

  • Test report content: assembly make, model, size, serial number, location, test date, tester name and certification number, gauge serial number and calibration date, and pass or fail with values recorded.

  • A failed test requires notification to the water purveyor, repair or replacement, and retest; the assembly is not returned to service until it passes.

Quick reference

Troubleshooting, Repair, and Maintenance

  • Continuous relief discharge on an RPZ usually means a fouled or damaged first check, debris on the relief seat, or a failed relief diaphragm; inspect check 1 before replacing the relief valve.

  • RPZ relief valve opens at too low a differential when check 1 is leaking, the relief spring is weak, or the relief seat is damaged.

  • Chatter or noise in a check valve indicates a worn spring, damaged seat, or debris; disassemble and inspect rather than adjusting the relief setting.

  • Water passing a check valve can be caused by debris on the seat, a torn seat disc, a broken spring, or a distorted clapper; repair kits restore original performance.

  • Air inlet on a PVB that leaks continuously can indicate a fouled air inlet seat, a failed check, or water pressure reaching the air inlet due to a downstream shutoff installed too low.

  • Repair parts must be manufacturer-approved; field modifications, mismatched parts, and altered springs void approval and can change the assembly's rated protection.

  • Maintenance intervals: annual testing is the minimum in most programs; high-use or dirty-water installations may require more frequent inspection, and strainers should be cleaned at service.

  • After any repair, the assembly must be retested and the results reported; record the repair, parts used, tester, and date for traceability.

  • Freeze damage, water hammer, and debris are the most common causes of failure; protection includes draining, proper orientation, and strainer maintenance.

Quick reference

Installation Requirements and Site Surveys

  • RPZ installation: must be installed horizontally unless the manufacturer lists vertical approval, with adequate clearance for testing and repair, and must not be in a pit, vault, or location subject to flooding or backpressure.

  • RPZ discharge: relief valve discharge must be piped to a drain with an air gap and must not be connected directly to a drainage system; the discharge must be visible.

  • PVB and AVB installation height: PVB at least 12 inches above the highest downstream outlet; AVB at least 6 inches above the highest downstream outlet and no downstream shutoff.

  • Air gap: minimum separation of twice the effective opening diameter and never less than 1 inch, measured from the supply pipe to the flood level rim of the receiving fixture.

  • Site survey steps: identify all water uses and auxiliary supplies, trace the distribution system, list cross-connections, assign degree of hazard, and specify protection for each.

  • Containment survey: locate the service connection, meter, and any bypass; verify no unprotected bypass, no fire line connection without protection, and no unauthorized auxiliary supply.

  • Auxiliary supplies such as wells, reclaimed water, boilers, and chemical injection systems require an air gap or RPZ at the point of connection; a DCVA is not acceptable for a health hazard.

  • Installation records: as-built drawings, device location, orientation, size, and manufacturer approval documentation should be retained for the assembly's service life.

Quick reference

Recordkeeping, Reporting, and Safety

  • Retain test and repair reports per jurisdiction; many programs require records for at least 3 to 5 years, and some require the life of the assembly.

  • Required report fields: assembly identification, location, size, make, model, serial number, test values, pass or fail, tester certification, gauge calibration, and date.

  • Tester certification: certification must be current and issued by a recognized program; testing performed with an expired certification is generally not accepted.

  • Gauge calibration records must be traceable and available at the time of test; a gauge without current calibration invalidates the reported results.

  • Safety hazards in the field: confined spaces (vaults, pits), electrical hazards, slips and falls, and pressure release; never enter a permit-required confined space without training, attendant, and atmospheric testing.

  • Pressure safety: depressurize and bleed test cocks slowly, wear eye protection, and never loosen fittings on a pressurized assembly.

  • Contamination control: use dedicated hoses and disinfect test connections; do not allow test water to contact the potable supply, and flush the assembly after testing.

  • Notification requirements: report failed assemblies to the purveyor and owner promptly, and document the corrective action taken and the retest result.

  • Record retention supports audits, liability defense, and program compliance; electronic records must be secure, backed up, and retrievable.