- Cross-connection
- Any actual or potential connection between a potable water system and a source of contamination or pollution that could allow backflow into the potable supply.
- Backsiphonage
- Backflow caused by negative or sub-atmospheric pressure in the supply piping, which draws nonpotable water into the potable system through a cross-connection.
- Backpressure
- Backflow caused by downstream pressure exceeding the supply pressure, often from pumps, boilers, elevation differences, or compressed gas systems connected to the potable line.
- Pollution versus contamination
- Pollution degrades water quality without creating a health hazard; contamination creates an actual health hazard and requires a higher degree of protection such as an air gap or RPZ.
- Premises isolation
- Containment protection installed at the service connection to protect the public main; it does not protect occupants inside the building from internal cross-connections.
- Air gap
- A physical separation between the supply pipe and the flood level rim of the receiving fixture, at least twice the effective opening diameter and never less than one inch.
- Atmospheric vacuum breaker
- A non-testable device with a check and an air inlet, installed at least six inches above the highest downstream outlet, with no downstream shutoff valve permitted.
- Pressure vacuum breaker
- A testable assembly with a loaded check and an air inlet, installed at least twelve inches above the highest downstream outlet, and it may have downstream shutoff valves.
- Double check valve assembly
- A testable assembly with two independent check valves, approved for non-health hazards such as low-hazard commercial or irrigation service connections.
- Reduced pressure principle assembly
- A testable assembly with two check valves and a hydraulically loaded relief valve; it is the only mechanical assembly approved for health hazards and must not be installed in a pit.
- Spill-resistant vacuum breaker
- A testable vacuum breaker with a check that limits discharge at the air inlet, used where a standard pressure vacuum breaker would discharge during normal operation.
- Assembly versus device
- An assembly is testable and has two or more shutoff valves and test cocks; a device is not testable and does not meet assembly requirements.
- Differential pressure gauge
- The field instrument used to test backflow assemblies; it must be calibrated, with calibration records retained, and accuracy verified before each test.
- RPZ test sequence
- Record supply pressure, test check one, test check two, then test the relief valve differential and verify it opens at the required threshold, typically two psi or greater.
- DCVA test sequence
- Test check one for tightness, then test check two, using the gauge connected through the test cocks and observing whether each check holds pressure.
- PVB test
- Verify the check valve holds tight and confirm the air inlet opens at the required vacuum, using the gauge to create and observe the pressure conditions.
- Backsiphonage test
- A test in which the gauge is used to create negative pressure by bleeding water through the high side, then observing whether the check valve holds.
- Test report content
- Assembly make, model, size, serial number, location, test date, tester name and certification number, gauge serial and calibration date, recorded values, and pass or fail.
- RPZ continuous relief discharge
- Usually caused by a fouled or damaged first check, debris on the relief seat, or a failed relief diaphragm; inspect check one before replacing the relief valve.
- Check valve leakage causes
- Debris on the seat, a torn seat disc, a broken spring, or a distorted clapper; manufacturer-approved repair kits restore original performance.
- PVB air inlet leak
- May indicate a fouled air inlet seat, a failed check, or water reaching the air inlet because a downstream shutoff was installed below the required height.
- Approved repair parts
- Only manufacturer-approved parts may be used; field modifications, mismatched parts, and altered springs void approval and can change the assembly's rated protection.
- Post-repair retest
- After any repair, the assembly must be retested and the results reported, recording the repair, parts used, tester, and date for traceability.
- RPZ installation limits
- Installed horizontally unless the manufacturer lists vertical approval, with clearance for testing and repair, and never in a pit, vault, or flood-prone location.
- RPZ relief discharge piping
- Relief valve discharge must be piped to a drain through an air gap and must not be connected directly to a drainage system; the discharge must remain visible.
- PVB and AVB heights
- A pressure vacuum breaker is installed at least twelve inches above the highest downstream outlet; an atmospheric vacuum breaker requires six inches and no downstream shutoff.
- Site survey steps
- Identify all water uses and auxiliary supplies, trace the distribution system, list cross-connections, assign degree of hazard, and specify protection for each.
- Auxiliary supply protection
- Wells, reclaimed water, boilers, and chemical injection systems require an air gap or RPZ at the point of connection; a double check is not acceptable for a health hazard.
- Record retention
- Test and repair reports are retained per jurisdiction, commonly at least three to five years and sometimes for the life of the assembly.
- Tester certification
- Certification must be current and issued by a recognized program; testing performed with an expired certification is generally not accepted by the water purveyor.
- Confined space safety
- Never enter a permit-required confined space such as a vault or pit without training, an attendant, and atmospheric testing; use proper retrieval and ventilation equipment.
- Pressure safety during testing
- Depressurize and bleed test cocks slowly, wear eye protection, and never loosen fittings on a pressurized assembly to avoid injury from released pressure.