Quick reference

Fire Detection and Alarm Systems

  • Detector spacing is governed by the listed coverage area, ceiling height, beam pockets, and ventilation; a single area-per-detector rule cannot be applied across all detector types.

  • Keep point detectors at least 0.5 m from walls and clear of air diffusers; the manufacturer's installation instructions set the final clearance.

  • Alarm audibility: at least 65 dBA at occupied locations or 5 dBA above ambient, whichever is higher; sleeping areas commonly require 75 dBA at the pillow.

  • Secondary battery capacity: C = I_standby × t_standby + I_alarm × t_alarm, with t_standby typically 24 h and t_alarm 5 min; apply battery derating and ageing factors.

  • Supervised detection circuits must annunciate open-circuit and short-circuit faults; end-of-line devices or addressed loop isolation provide fault discrimination.

  • Smoke detectors are generally unsuitable in dusty, steam-laden, or cooking environments; use heat or alternative detection matched to the expected fire signature.

  • A sprinkler flow switch or pressure switch used as a fire alarm input must be monitored and assigned an alarm zone that identifies the water flow location.

  • Cross-zoning requires two independent detector alarms before a suppression release or a high-level alarm, reducing false discharges.

Quick reference

Automatic Fire Sprinkler Systems

  • Design density formula: Q = ρ × A, where Q is minimum sprinkler flow in L/min, ρ is density in mm/min or L/min/m², and A is the design area of operation in m².

  • Sprinkler discharge formula: Q = K√P, where Q is flow in L/min, K is the listed K-factor, and P is pressure in bar for metric K-factors.

  • Select the sprinkler temperature rating above the maximum ambient temperature; ordinary-rated 68°C heads are common for occupied spaces with moderate ceilings.

  • A wet-pipe alarm valve flow switch should actuate on a single sprinkler flow; the inspector's test valve simulates the hydraulically most remote sprinkler.

  • Calculate pump head as elevation pressure plus pipe friction loss plus residual pressure at the most remote sprinkler; include backflow and valve losses.

  • Use Hazen-Williams for water pipe friction: h = 10.67 L Q^1.85 / (C^1.85 d^4.87), with consistent SI units.

  • A sprinkler system must have a main drain, alarm test valve, and pressure gauge to verify supply and alarm operation.

  • Do not reduce pipe size below the minimum listed for the sprinkler and occupancy; hydraulic calculations, not pipe-size rules, govern.

Quick reference

Fire Hydrant and Hose Reel Systems

  • Hydrant design must satisfy simultaneous flow at the design number of hydrants, with residual pressure at the most remote hydrant not below the local code minimum.

  • Pump head equals static elevation plus friction loss plus residual pressure; include hose and hydrant valve losses.

  • Hazen-Williams friction formula h = 10.67 L Q^1.85 / (C^1.85 d^4.87) applies to hydrant mains and hose reel pipework.

  • Hose reels are typically 30 m long with 19 mm or 25 mm hose; the reel must reach all parts of the protected area without passing through fire doors.

  • Each hydrant should have a valve, non-return arrangement where required, drain, and a compatible fire brigade coupling.

  • Booster connections must be accessible to fire brigades and marked with the system type and pressure rating.

  • Hydrant ring mains require sectional valves so isolation does not remove more than the permitted number of hydrants.

  • Flow testing records should include static pressure, residual pressure, flow rate, and pump status.

Quick reference

Gaseous and Special Hazard Fire Suppression Systems

  • Total-flooding agent mass: m = (V/S) × C/(100−C), where V is enclosure volume, S is specific volume, and C is design concentration in percent.

  • Design concentration equals extinguishing concentration multiplied by a safety factor; clean-agent Class B designs commonly use a 1.2 safety factor.

  • For occupied spaces, the design concentration should not exceed the agent's NOAEL; if it does, provide pre-discharge warning and timed egress.

  • Clean-agent total-flooding discharge is typically 10 s; inert-gas systems often use 60–120 s to limit pressure and noise.

  • Enclosure integrity testing with a door fan verifies that the room can hold the design concentration for the required hold time.

  • CO2 total-flooding systems must not be used in normally occupied spaces because of asphyxiation risk.

  • Cross-zoned detection and a pre-discharge delay allow investigation and evacuation before agent release.

  • Pressure relief vents must be sized to prevent enclosure overpressure during agent discharge.

Quick reference

Portable and Mobile Fire Extinguishing Equipment

  • Extinguisher rating codes such as 2A:10B:C indicate Class A water-equivalent rating, Class B test-fire size, and electrical non-conductivity.

  • Water extinguishers are unsuitable for live electrical equipment and cooking-oil fires; Class F wet chemical agents saponify hot oils.

  • CO2 extinguishers are effective on electrical fires but have limited cooling; in confined spaces, discharge can reduce oxygen.

  • Dry-powder extinguishers leave residue that can damage electronics; clean-agent extinguishers are preferred for sensitive equipment.

  • Mount portable extinguishers with the carrying handle not more than 1.5 m above the floor and the label visible.

  • Class D metal fires require specially formulated dry powders; water, foam, and CO2 are generally ineffective or dangerous.

  • Travel distance to an extinguisher depends on occupancy hazard and extinguisher class; check the applicable code for the maximum distance.

  • An extinguisher is only suitable for a fire class shown on its label; never use a lower-rated extinguisher than the hazard requires.