FPAS Fire Systems Design (FSD) flashcards
FPAS Fire Systems Design (FSD) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Alarm zone
- A defined area of a fire detection system that is separately annunciated at the control panel so responders can locate the alarm source.
- Smoke detector spacing
- Smoke detector coverage is limited by listed spacing, ceiling height, beams, and airflow; manufacturers specify maximum area and distance between detectors.
- Alarm audibility requirement
- Fire alarm sounders must produce at least 65 dBA at occupied locations or 5 dBA above ambient, and commonly 75 dBA at sleeping-area bedheads.
- Battery standby calculation
- Secondary battery capacity equals standby current times standby hours plus alarm current times alarm hours, typically 24 hours standby and 5 minutes alarm, with derating.
- End-of-line resistor
- A supervised detection circuit uses an end-of-line resistor so the panel can detect open circuits, short circuits, and device removal as distinct fault conditions.
- Cross-zoning
- A logic arrangement requiring alarms from two independent detectors or zones before a suppression release or high-level alarm, reducing false activation.
- Heat detector suitability
- Heat detectors suit dusty, smoky, or cooking environments where smoke detectors would false-alarm, but they respond more slowly to smouldering fires.
- Design density formula
- Minimum sprinkler flow equals design density multiplied by the design area of operation, with density in mm/min and area in square metres giving litres per minute.
- Sprinkler K-factor formula
- For metric K-factors, sprinkler flow in litres per minute equals the K-factor multiplied by the square root of pressure in bar.
- Ordinary sprinkler rating
- A 68°C rated sprinkler is common for ordinary occupied spaces; the rating must exceed the maximum ambient temperature and suit the ceiling environment.
- Inspector's test valve
- A test connection at the hydraulically most remote point that simulates one sprinkler flowing, verifying alarm valve and flow-switch operation.
- Hazen-Williams formula
- Friction loss in water pipes is calculated as h = 10.67 L Q^1.85 / (C^1.85 d^4.87), using consistent SI units.
- Main drain test
- A main drain test records static and residual pressure to indicate supply valve status and detect deterioration in the water supply.
- Wet-pipe alarm valve
- A wet-pipe alarm valve controls water flow into a sprinkler system and initiates an alarm when a sprinkler operates and creates sustained flow.
- Hydrant residual pressure
- The pressure remaining at a flowing hydrant after elevation and friction losses; it must meet the code minimum at the most remote design hydrant.
- Fire brigade booster
- A connection allowing fire service pumpers to supplement the hydrant or sprinkler supply; it must be accessible, marked, and compatible with brigade couplings.
- Hose reel coverage
- A hose reel must reach all parts of its protected area with a 30 m hose, allowing for hose route, obstructions, and doorways without passing through fire doors.
- Hydrant ring main
- A looped water main supplying hydrants from more than one direction, improving reliability and reducing pressure loss compared with a dead-end main.
- Sectional isolating valve
- A valve that isolates part of a hydrant ring main for maintenance while keeping the remaining hydrants in service; placement limits the number isolated.
- Hydrant flow test
- A test recording static pressure, residual pressure, and flow rate at a hydrant to verify that the supply meets the design demand.
- Total-flooding agent mass
- Agent mass equals enclosure volume divided by specific volume, multiplied by design concentration divided by 100 minus concentration.
- NOAEL
- No-observed-adverse-effect level; the highest agent concentration at which no adverse health effect is expected, used to set limits for occupied spaces.
- Enclosure integrity test
- A door-fan test that measures room leakage and predicts whether the enclosure will hold the design agent concentration for the required hold time.
- Clean-agent discharge time
- Total-flooding clean-agent systems typically discharge within 10 seconds, while inert-gas systems often use 60 to 120 seconds to control pressure and noise.
- CO2 occupancy hazard
- Carbon dioxide total-flooding systems are not permitted in normally occupied spaces because discharge can cause rapid asphyxiation; they suit unoccupied hazards.
- Pre-discharge delay
- A timed interval after alarm confirmation before agent release, allowing occupants to evacuate and responders to investigate or abort the discharge.
- Extinguisher rating code
- A label such as 2A:10B:C shows the Class A water-equivalent rating, Class B test-fire size, and Class C electrical non-conductivity.
- Class F wet chemical
- Wet chemical extinguishers saponify hot cooking oils, forming a soap-like layer that cools and seals the surface, making them suitable for Class F fires.
- CO2 extinguisher limitation
- CO2 extinguishers are effective on electrical fires but provide little cooling and can displace oxygen in confined spaces, creating an asphyxiation risk.
- Class D metal fire
- Class D fires involve combustible metals such as magnesium or sodium; special dry powders are required because water, foam, and CO2 can react violently.
- Extinguisher mounting height
- Portable extinguishers are mounted so the carrying handle is not more than 1.5 m above the floor, with the label visible and the unit accessible.
- Dry powder residue
- Dry-powder extinguishers leave corrosive or insulating residue that can damage electronics and machinery; clean-agent extinguishers are preferred for sensitive equipment.