Plumbing, Draining and Gasfitting

  • Minimum sanitary drainage grade is 1:60 (1.7%) for DN100 and smaller, and 1:100 (1%) for DN150 and larger unless the design specifies otherwise.

  • A water seal trap must hold between 25 mm and 55 mm of seal depth; fixture traps must be self-cleaning and accessible for clearing.

  • Vent stack sizing follows fixture discharge units: a DN50 vent serves up to 20 fixture units, DN65 up to 60, DN80 up to 140 in typical AS/NZS 3500.2 arrangements.

  • Every discharge pipe must be tested: water test to 3 m head above the highest point, or air test at 35 kPa for at least 5 minutes with no drop.

  • Backflow prevention device selection depends on hazard rating: individual (low), zone (medium), or containment (high) protection at the boundary.

  • Gas pipe sizing uses the longest-run method: total equivalent length (measured length plus allowances for each fitting) sets the pipe diameter from the sizing table.

  • Gas pressure test: 7 kPa for 10 minutes minimum on natural gas installations, or 1.5 times working pressure for LP Gas, whichever governs.

  • Combustion air for an indoor gas appliance requires two permanent openings, each sized at 1/1000 of the appliance input in MJ/h for a direct-to-outside duct.

Quick reference

Roof Plumbing

  • Roof catchment area (m2) equals plan length multiplied by plan width; for pitched roofs use the horizontal plan projection, not the sloping surface.

  • Rainfall intensity for design is taken from AS/NZS 3500.3 tables by location and storm duration (typically 5-minute and 100-year ARI values).

  • Box gutter depth must not exceed 1/3 of its width; minimum width 200 mm and minimum depth 75 mm for a standard high-front box gutter with overflow.

  • Minimum roof slope for corrugated metal sheet is 5 degrees; for lapped metal sheet 3 degrees; for metal tray 1 degree with continuous support.

  • Downpipe capacity in a charged system is limited by head: a DN90 downpipe carries roughly 380 L/min at 1.5 m head; verify against the manufacturer's chart.

  • Overflow provisions: an overflow weir or rainhead must be sized to pass the design flow when the primary outlet blocks, at the same design rainfall intensity.

  • Flashing laps must be 150 mm minimum over the roof covering, 100 mm minimum for side laps, and fixings must not penetrate the flashing within 75 mm of a lap edge.

  • Sarking and insulation: roof plumber must ensure condensation control layer is continuous and laid with laps facing the direction of water flow.

Quick reference

Medical Gas and Mechanical Services

  • Medical gas pipeline identification uses colour codes: oxygen white, nitrous oxide blue, medical air black/white, nitrogen black, carbon dioxide grey, vacuum yellow.

  • A medical gas system must be pressure tested with oil-free dry nitrogen at 1.5 times the design working pressure for a minimum of 24 hours with no pressure loss.

  • Purity test for medical oxygen: minimum 99.5% oxygen by volume; dew point must be below -46 degrees C for medical air.

  • Terminal unit flow rates: oxygen and medical air outlets deliver 60-80 L/min at 400 kPa; vacuum outlets deliver 40-80 L/min at 40 kPa below atmospheric.

  • Mechanical services: air change rates for operating theatres are 20-25 air changes per hour with a positive pressure differential of at least 15 Pa.

  • Duct pressure testing classifies leakage: Class A (low), Class B (medium), Class C (high); test pressure is 1.25 times design working pressure.

  • Medical gas alarm systems must be located at the source, at the area alarm panel, and at the master alarm in a continuously staffed location.

  • Cross-connection test: after any alteration, the pipeline must be purged and tested for identity at each outlet before commissioning.

Quick reference

Disconnection and Reconnection of Fixed Electrical Equipment

  • Only a licensed electrician may perform fixed electrical work; a plumber may disconnect and reconnect fixed electrical equipment only where permitted by the relevant state/territory regulation and within the scope of their licence.

  • A plumber may disconnect and reconnect a fixed appliance (such as a hot water system or pump) only where the connection is via a plug and socket, or where a restricted electrical licence authorises the work.

  • Before reconnection, verify polarity and earth continuity; insulation resistance must be at least 1 megohm at 500 V DC test voltage.

  • Isolation procedure: isolate at the main switch or circuit breaker, lock and tag, prove dead with an approved voltage tester, then proceed.

  • Circuit protection: a residual current device (RCD) with 30 mA sensitivity protects all socket outlets and lighting circuits in domestic installations.

  • Cable sizing must account for derating factors: ambient temperature, grouping, and installation method; the protective device rating must not exceed the cable current-carrying capacity.

  • Earthing: the main earthing conductor minimum size is 6 mm2 copper for a domestic installation with a 100 A consumer mains; verify against AS/NZS 3000 Table 5.1.

  • After reconnection, test and tag portable appliances; fixed equipment requires a certificate of electrical safety where the work is notifiable.