NSW Plumbing Licence flashcards
NSW Plumbing Licence · Build recall with a focused review session.
31 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Minimum drainage grade
- Sanitary drainage pipes must fall at least 1:60 for DN100 and smaller, and 1:100 for DN150 and larger, to maintain self-cleansing velocity of about 0.6 m/s.
- Water seal depth
- A trap must retain a water seal between 25 mm and 55 mm deep; deeper seals are hard to clear and shallower seals evaporate or siphon away.
- Drainage air test
- A completed drainage system is air tested at 35 kPa for at least 5 minutes with no measurable drop, after all joints are sealed and the test plug installed.
- Backflow hazard rating
- Backflow risk is classed individual (low, single dwelling), zone (medium, multiple premises), or containment (high, boundary protection), and the device type must match the class.
- Gas pipe longest-run sizing
- Pipe diameter is chosen by adding the measured pipe length to an allowance for each fitting, then reading the total equivalent length against the appliance load in MJ/h.
- Natural gas pressure test
- A new natural gas installation is tested at 7 kPa for at least 10 minutes; any drop indicates a leak and the test must be repeated after repair.
- Combustion air openings
- Indoor gas appliances need two permanent openings sized at 1/1000 of the appliance input in MJ/h when ducted directly to outside air.
- Roof catchment area
- Catchment area in square metres equals the horizontal plan projection of the roof, obtained by multiplying plan length by plan width, not the sloping surface area.
- Box gutter proportions
- A high-front box gutter must have depth no greater than one third of its width, with a minimum width of 200 mm and minimum depth of 75 mm.
- Minimum metal roof slopes
- Corrugated metal sheet needs a minimum 5 degree slope; lapped sheet 3 degrees; metal tray 1 degree with continuous support beneath every pan.
- Design rainfall intensity
- Rainfall intensity for roof drainage design is taken from AS/NZS 3500.3 tables for the site, using the 5-minute, 100-year average recurrence interval value.
- Overflow weir sizing
- The overflow weir or rainhead must pass the full design flow at design rainfall intensity when the primary outlet is blocked, preventing ponding above the gutter.
- Flashing lap minimums
- Flashing must lap the roof covering by at least 150 mm, side laps at least 100 mm, and fixings must stay at least 75 mm from any lap edge.
- Downpipe flow capacity
- A charged DN90 downpipe carries roughly 380 L/min at 1.5 m head; always confirm capacity from the manufacturer's flow chart for the specific system.
- Medical gas colour codes
- Oxygen is white, nitrous oxide blue, medical air black and white, nitrogen black, carbon dioxide grey, and vacuum yellow for pipeline identification.
- Medical gas pressure test
- Medical gas pipelines are tested with oil-free dry nitrogen at 1.5 times design working pressure for at least 24 hours with no pressure loss recorded.
- Oxygen purity limit
- Medical oxygen must be at least 99.5 percent pure by volume, and medical air must have a dew point below minus 46 degrees Celsius.
- Theatre air change rate
- Operating theatres require 20 to 25 air changes per hour with a positive pressure differential of at least 15 Pa relative to adjacent spaces.
- Duct leakage classes
- Ductwork is pressure tested at 1.25 times design working pressure and classed A (low), B (medium), or C (high) according to measured leakage rate.
- Medical gas alarm locations
- Alarms must be fitted at the gas source, at the area alarm panel serving the clinical area, and at the master alarm in a continuously staffed location.
- Terminal unit flow rates
- Oxygen and medical air outlets deliver 60 to 80 L/min at 400 kPa, while vacuum outlets deliver 40 to 80 L/min at 40 kPa below atmospheric.
- Pipeline identity test
- After any alteration, each medical gas outlet is purged and tested for correct gas identity before the system is commissioned for clinical use.
- Electrical licence boundary
- Fixed electrical work requires an electrician's licence; a plumber may only disconnect and reconnect equipment within the scope permitted by their licence and state regulation.
- Plug and socket reconnection
- A plumber may disconnect and reconnect a fixed appliance where it connects by plug and socket; hard-wired connection needs a restricted electrical licence or an electrician.
- Insulation resistance minimum
- Before reconnection, insulation resistance must be at least 1 megohm when tested at 500 volts DC between active, neutral, and earth conductors.
- Isolation and prove dead
- Isolate at the main switch or breaker, lock and tag, then prove dead with an approved voltage tester before touching any conductor or terminal.
- RCD sensitivity
- A residual current device with 30 mA sensitivity must protect socket outlets and lighting circuits in domestic installations to reduce electric shock risk.
- Cable derating factors
- Cable current capacity is reduced for ambient temperature, grouping with other cables, and installation method; the protective device rating must not exceed the derated capacity.
- Main earthing conductor
- For a domestic installation with 100 A consumer mains, the main earthing conductor is at least 6 mm2 copper, checked against the AS/NZS 3000 table.
- Test and tag requirement
- After reconnection, portable appliances are tested and tagged, and notifiable fixed electrical work requires a certificate of electrical safety.
- Earth continuity check
- Before reconnection, confirm earth continuity from the appliance frame to the earthing terminal and verify active and neutral polarity at the connection point.