- Arizona Registrar of Contractors
- State agency that licenses and regulates Arizona contractors, investigates complaints against licensees, and can suspend or revoke a license or order restitution to a harmed homeowner.
- R-39 Classification
- Arizona residential license limited to air conditioning and refrigeration work on residential structures; the commercial counterpart is C-39 and the dual license is L-39.
- $1,000 Licensing Threshold
- In Arizona a contractor's license is required for any project of $1,000 or more in labor and materials; unlicensed contracting carries criminal penalties.
- Eight-Year Statute of Repose
- A.R.S. § 12-552 generally bars construction defect lawsuits more than eight years after substantial completion, even when the defect was hidden for years.
- Superheat
- The number of degrees a refrigerant vapor is above its saturation temperature at the same pressure; measured at the evaporator outlet to verify metering-device performance and charge.
- Subcooling
- The number of degrees a liquid refrigerant is below its saturation temperature at the same pressure; measured at the condenser outlet and used to verify charge on TXV systems.
- Thermostatic Expansion Valve
- Metering device that modulates refrigerant flow to hold a constant superheat at the evaporator outlet as the load and outdoor conditions change.
- One Ton of Refrigeration
- A heat absorption rate equal to 12,000 Btu per hour, or 200 Btu per minute, roughly the heat needed to melt one ton of ice in 24 hours.
- AFUE
- Annual Fuel Utilization Efficiency: the percentage of fuel energy delivered to the space over a heating season, about 80% for standard furnaces and 90% or more for condensing furnaces.
- Balance Point
- The outdoor temperature at which heat pump capacity exactly equals the building heat loss; below that temperature supplemental electric resistance or gas heat must operate.
- Condensing Furnace
- Furnace with a secondary heat exchanger that condenses water vapor in the flue gas, reaching 90%+ AFUE, vented in PVC and draining acidic condensate through a trap.
- Manifold Pressure
- Gas pressure measured at the burner manifold with a manometer, typically 3.5 in. w.c. for natural gas and 10 to 11 in. w.c. for propane.
- Ohm's Law
- Voltage equals current multiplied by resistance, V = I × R; combined with P = V × I it lets a technician solve for any circuit value from two known quantities.
- Motor Branch 125% Rule
- Branch-circuit conductors, disconnects, and controllers must be sized at not less than 125% of the motor's nameplate full-load current, per the National Electrical Code.
- PSC Motor
- Permanent split capacitor motor: a run capacitor in series with the start winding produces moderate starting torque with no centrifugal switch and no start capacitor.
- Equipment Disconnect
- A means to disconnect power that must be installed within sight of the HVAC equipment and generally within 50 feet of it.
- External Static Pressure
- The sum of supply and return static pressures the air handler must overcome, measured with a manometer; residential units are typically rated at 0.5 in. w.c.
- Equal Friction Method
- Duct sizing method that holds pressure drop constant, commonly 0.1 in. w.c. per 100 feet of effective length, beginning at the longest run.
- Return Grille Velocity
- Return grilles are commonly sized for 300 to 500 feet per minute face velocity so that noise and pressure drop stay acceptable.
- Nitrogen Purge
- A low flow of dry nitrogen through the tubing while brazing displaces oxygen, preventing internal copper oxide scale that would later contaminate valves and the compressor.
- 500 Micron Vacuum
- Evacuation standard for a new system; the micron gauge is isolated from the pump and the vacuum must hold without rising, confirming no leaks or moisture remain.
- 15% Silver Solder
- Higher-silver brazing filler used on high-vibration joints and copper-to-steel connections; copper-to-copper joints normally use 5% silver-phosphorus without flux.
- Manual J
- ACCA method for room-by-room heating and cooling load calculation using envelope construction, window data, infiltration, and internal heat gains.
- Sensible Heat Equation
- Q in Btu/h = 1.08 × CFM × temperature difference between entering and leaving air; the constant assumes sea-level standard air density.
- Total Heat Equation
- Q in Btu/h = 4.5 × CFM × enthalpy difference, used to determine total coil capacity when entering and leaving air enthalpies are known.
- Sensible Heat Ratio
- Sensible load divided by total load; the selected equipment's sensible heat ratio must match the calculated value or the space will run humid.
- Recovery Cylinder Fill
- A refrigerant recovery cylinder may never be filled above 80% of its water capacity, controlled by weight on a scale to leave room for liquid expansion.
- OSHA Fall Protection
- Fall protection is required at six feet in construction and four feet in general industry, provided by guardrails, personal fall arrest systems, or nets.
- Section 608 Certification
- Federal EPA credential required for technicians who service, repair, or dispose of refrigerant-containing appliances; categories are Type I, II, III, and Universal.
- Gross Margin
- Margin percent equals price minus cost, divided by price, times 100; a 25% gross margin corresponds to a 33.3% markup on cost.
- Preliminary 20-Day Notice
- Arizona notice given by a subcontractor or supplier within 20 days of first furnishing labor or materials, preserving mechanics' lien rights on the project.
- Change Order
- A written, signed modification to the contract scope, price, or schedule; work performed without a signed change order is often uncompensated.