AZ HVAC: Ductwork, Air Distribution, and Ventilation

AZ HVAC · Work through your exam, one topic at a time.

All guide sections

Ductwork, Air Distribution, and Ventilation

Static pressure is the language of air

Air moves because of pressure difference, and the fan must overcome the total external static pressure of the system. A typical residential budget is about 0.5 in. w.c., split between the filter, coils, registers, grilles, and duct run. Field-measure static pressure with a manometer: high return-side static points to restrictive filter or undersized return, high supply-side static points to undersized or crushed duct. Excess static reduces airflow, which reduces capacity and can freeze coils.

Sizing and layout

Manual D governs duct sizing using an available static pressure and a total effective length that includes fitting equivalent lengths, then derives a friction rate in inches of water column per 100 feet. A common design target near 0.1 in. w.c. per 100 feet is a starting reference, not a rule that overrides the calculation. Return air must be sized as generously as supply; a starved return is one of the most common Arizona field defects, especially with attic ducts and flex runs that are compressed or sharply bent. Seal all joints with mastic or listed tape; duct leakage in a hot attic is a direct capacity loss.

Ventilation and indoor air quality

Mechanical ventilation requirements address whole-house ventilation, local exhaust for baths and kitchens, and filtration rated by MERV. Filtration adds static pressure, so a high-MERV filter on an undersized return is a capacity problem. Insulate ducts and plenums in unconditioned space, and support flex duct so it stays fully round.

Worked example

Available static is 0.50 in. w.c.; known device and coil losses total 0.25 in. w.c.; total effective length is 150 feet. Remaining static is 0.25, so friction rate = (0.25 / 150) x 100 = about 0.167 in. w.c. per 100 feet to size the duct run.