BICSI Installer 2 Fiber study materials
BICSI Installer 2 Fiber study resources

BICSI Installer 2 Fiber cheat sheet

BICSI Installer 2 Fiber · Keep the key ideas within reach.

Quick reference

Fiber Optic Theory and Transmission Principles

  • Attenuation (dB) = 10 × log10(Pin/Pout); link loss (dB) = Pin(dBm) − Pout(dBm).

  • Power conversion: dBm = 10 × log10(P/1 mW); 0 dBm = 1 mW, −3 dBm ≈ 0.5 mW, +10 dBm = 10 mW.

  • Single-mode fiber: 8–10 µm core; 1310 nm and 1550 nm windows; 1550 nm has lower attenuation, 1310 nm has minimum chromatic dispersion.

  • Multimode fiber: 50 µm or 62.5 µm core; 850 nm and 1300 nm windows; modal dispersion limits reach and bandwidth.

  • Loss budget = transmitter output (dBm) − receiver sensitivity (dBm) − margin; total link loss must be ≤ budget.

  • Numerical aperture: NA = sin θ; larger NA accepts more light and generally increases multimode modal dispersion.

  • Macrobending loss rises with tighter bend radius and longer wavelength; microbending loss comes from stress or roughness.

  • Fresnel reflection at an uncoated glass-air interface is about 4%; index-matching gel reduces reflection loss.

  • Dispersion types: modal dispersion dominates multimode; chromatic and polarization-mode dispersion affect single-mode at high rates.

Quick reference

Fiber Optic Cables, Components, and Hardware

  • Fiber grades: OS1/OS2 single-mode; OM1 62.5/125; OM2 50/125; OM3, OM4, OM5 laser-optimized 50/125 multimode.

  • Loose-tube cable is common outside plant; tight-buffered cable is common indoors and for patch cords.

  • Strength members: aramid yarn provides tensile strength; central or peripheral strength members control load.

  • Jacket ratings: OFNP/OFCP plenum, OFNR/OFCR riser, OFN/OFNG general purpose; LSZH is a low-smoke zero-halogen material, not a plenum rating.

  • Ferrule sizes: SC, ST, FC = 2.5 mm; LC = 1.25 mm.

  • Polish types: PC and UPC are flat or domed; APC has an 8° angled end face and higher return loss.

  • Return loss: APC typically ≥60 dB; UPC typically ≥50 dB; mating APC to UPC causes high loss and reflection.

  • Bend radius rule of thumb: 10× cable outside diameter installed and 20× during pulling, unless manufacturer specifies otherwise.

  • Duplex polarity: A-to-B and B-to-A crossover at patch cords; array systems use Method A, B, or C per TIA-568.

Quick reference

Cable Installation Practices (Pulling, Routing, and Support)

  • Maximum pulling tension for premises fiber is commonly 25 lbf (110 N); the manufacturer's cable specification governs.

  • Bend radius during pull: typically 20× cable OD; installed: typically 10× cable OD.

  • Pull using the strength member and a pulling eye or grip; a breakaway swivel limits tension and prevents twist.

  • Conduit fill: 40% for three or more cables, 53% for one cable, 31% for two cables.

  • Support horizontal fiber cable at intervals specified by code and manufacturer; vertical cable is supported at each floor.

  • Sidewall pressure must not exceed the cable limit; use a compatible pulling lubricant and avoid sharp raceway bends.

  • Separate fiber from power circuits as required by NEC Article 770 and the applicable electrical code.

  • Seal rated wall and floor penetrations with a listed firestop system tested to ASTM E814/UL 1479.

  • Leave slack loops at handholes, cabinets, and termination points as specified; record slack and route.

Quick reference

Splicing, Termination, and Connectorization

  • Fusion splice loss is typically ≤0.1 dB; mechanical splice loss is typically ≤0.3 dB; connector loss is typically ≤0.3–0.5 dB.

  • Cleave angle for fusion splicing is typically ≤1°; end face must be free of hackle, mist, and chips.

  • Use a splice protection sleeve; cure or shrink per manufacturer and place it in the splice tray within bend radius.

  • Connector termination methods: epoxy-and-polish, pre-polished field-installable, and fusion splice-on connector.

  • Inspect connector end faces at 200× or 400×; zones A (core) and B (cladding) are most critical.

  • APC and UPC connectors are not mated; the 8° angle and flat end face do not contact correctly.

  • Connectors and adapters are cleaned before every mating with lint-free wipes and approved cleaning tools.

  • For duplex polarity, follow TIA-568 A-B crossover; confirm transmit-to-receive orientation end to end.

  • OTDR splice loss: average bidirectional readings to remove gainer error from backscatter differences.

Quick reference

Testing, Measurement, and Troubleshooting

  • Tier 1 test: optical loss test set (OLTS) measures insertion loss and length; Tier 2 adds OTDR.

  • Test wavelengths: multimode 850/1300 nm; single-mode 1310/1550 nm.

  • Reference method: 1-jumper, 2-jumper, or 3-jumper; set the reference per the chosen method and standard.

  • Encircled flux is the required launch condition for multimode loss testing; a mandrel wrap or mode conditioner can provide it.

  • OTDR event dead zone separates reflective events; attenuation dead zone separates loss events; shorter pulses improve resolution but reduce range.

  • OTDR distance depends on group index of refraction; incorrect IOR setting produces length error.

  • A gainer is an apparent negative splice loss caused by backscatter differences; bidirectional averaging gives true loss.

  • High loss causes: dirty connector, damaged end face, bad splice, tight bend, crack, or break.

  • A visual fault locator (VFL) shows breaks and tight bends near the tester by visible red light leakage.

Quick reference

Safety, Codes, Standards, and Job Documentation

  • NEC Article 770 covers optical fiber cable installation; Article 800 covers communications circuits; Article 300 covers wiring methods.

  • Plenum cable rating is verified by NFPA 262; riser cable by UL 1666; general-purpose cable by UL 1581.

  • TIA-568 covers cabling performance and topology; TIA-606 covers administration and labeling; TIA-607 covers grounding and bonding.

  • Laser safety: never look into a fiber or connector; infrared light is invisible; verify the source is off before inspection.

  • Fiber scraps and cleaved ends go into a closed sharps container, not trash, because they can penetrate skin and eyes.

  • Safety Data Sheets (SDS) are required for chemicals such as solvents, adhesives, and index-matching gel under OSHA Hazard Communication.

  • Test documentation includes link ID, date, tester model and calibration, reference method, wavelengths, loss, length, and pass/fail.

  • As-built records include cable routes, splice schematics, port assignments, slack locations, and labeling.

  • Metallic strength members and conductive cables require grounding and bonding per NEC and TIA-607.