- Decibel loss formula
- Loss in decibels equals 10 times the base-10 logarithm of input power divided by output power; a 10 dB loss means one-tenth of the power remains.
- dBm reference
- Power in dBm equals 10 times the base-10 logarithm of power in milliwatts divided by one milliwatt; 0 dBm is 1 mW and -3 dBm is about 0.5 mW.
- Single-mode core size
- Single-mode fiber typically has an 8 to 10 micrometer core and carries 1310 and 1550 nanometer wavelengths, supporting long-reach and high-bandwidth transmission.
- Multimode core sizes
- Multimode fiber uses 50 or 62.5 micrometer cores and commonly operates at 850 and 1300 nanometers; modal dispersion limits distance compared with single-mode.
- Numerical aperture
- Numerical aperture equals the sine of the acceptance angle; a higher NA accepts more light but usually increases modal dispersion in multimode fiber.
- Link loss budget
- The loss budget is transmitter output power minus receiver sensitivity minus a safety margin; total cable, connector, and splice losses must not exceed it.
- OM3 and OM4
- OM3 and OM4 are laser-optimized 50-micrometer multimode fibers; OM4 has higher bandwidth and supports longer 10-gigabit and 40-gigabit distances.
- Loose-tube cable
- Loose-tube fiber cable places fibers in gel-filled tubes around a central strength member; it is suited to outside-plant and long outdoor runs.
- Tight-buffered cable
- Tight-buffered cable has a protective buffer directly on each fiber, making it flexible and suitable for indoor jumper and horizontal cabling.
- APC connector angle
- An APC connector has an 8-degree angled ferrule end face; it provides high return loss and must not be mated with a flat UPC connector.
- Plenum cable rating
- Plenum-rated fiber cable, marked OFNP or OFCP, has low smoke and flame spread for use in air-handling spaces such as return-air ceilings.
- Connector ferrule sizes
- SC, FC, and ST connectors use 2.5-millimeter ferrules, while LC connectors use 1.25-millimeter ferrules; ferrule size does not determine polish.
- Pull tension limit
- Premises fiber cable is commonly limited to about 25 pounds-force pulling tension, but the manufacturer's published limit always governs the installation.
- Pull bend radius
- During pulling, fiber cable typically needs a bend radius of at least 20 times its outside diameter; installed radius is often 10 times diameter.
- Conduit fill rule
- For three or more cables, conduit fill should not exceed 40 percent; one cable may use 53 percent and two cables 31 percent.
- Strength member pulling
- Pull on the cable strength member with a pulling eye or grip rather than the jacket, and use a swivel to prevent twisting.
- Firestop penetration
- Cable penetrations through rated walls or floors must be sealed with a listed firestop system tested to ASTM E814 or UL 1479.
- Fusion splice loss
- A properly made fusion splice typically adds 0.1 decibel or less; mechanical splices and connectors commonly add up to about 0.3 decibel.
- Cleave angle limit
- A fiber cleave for fusion splicing should be within about one degree of perpendicular and free of mist or hackle to produce a low-loss splice.
- APC to UPC mating
- Mating an angled APC connector to a flat UPC connector causes high loss and reflection because the end faces do not physically contact correctly.
- Connector inspection zones
- End-face inspection divides the ferrule into zones A through D; defects in the central core zone A are most critical for loss.
- Splice loss OTDR gainer
- An apparent negative splice loss, called a gainer, can result from backscatter differences; bidirectional OTDR averaging gives the true splice loss.
- Tier 1 fiber test
- Tier 1 testing uses an optical loss test set to measure insertion loss and length; Tier 2 adds an OTDR trace for troubleshooting and splice analysis.
- Encircled flux launch
- Encircled flux is a controlled multimode launch condition required for accurate loss testing; a mandrel wrap or mode conditioner helps achieve it.
- OTDR dead zone
- The OTDR event dead zone is the minimum spacing for resolving two reflective events; the attenuation dead zone is longer for resolving loss events.
- OTDR distance measurement
- An OTDR calculates distance from light round-trip time and the fiber's group index of refraction, so an incorrect index setting skews length.
- Visual fault locator
- A visual fault locator injects visible red light to reveal breaks, tight bends, and bad connectors near the tester through a glowing leak.
- NEC Article 770
- National Electrical Code Article 770 covers installation requirements for optical fiber cables and their associated boxes, raceways, and grounding.
- TIA-606 labeling
- TIA-606 provides administration standards for labeling and documenting telecommunications spaces, cables, and pathways so links can be traced.
- Fiber scrap disposal
- Fiber scraps and cleaved ends must go into a closed container, not trash or clothing, because they can penetrate skin and eyes.
- Laser safety rule
- Never look into a fiber end or connector unless the source is off and verified; infrared laser light is invisible and can damage the retina.
- Test record contents
- A fiber test record should include link identifier, date, tester and calibration, reference method, wavelengths, loss results, and pass-fail status.