BICSI Installer 2 Fiber key terms
BICSI Installer 2 Fiber ยท Get comfortable with the vocabulary.
- Attenuation
- Related: Insertion Loss, Link Loss Budget, Optical Loss Test Set (OLTS)
The decrease in optical power as light travels through fiber, connectors, or splices, expressed in decibels. It is caused mainly by absorption and scattering and limits how far a signal can travel.
- Insertion Loss
- Related: Attenuation, Link Loss Budget
The optical power lost when a component such as a connector, splice, or cable section is inserted into a link, measured in decibels as the difference between power in and power out.
- Modal Dispersion
- Related: Chromatic Dispersion, Bandwidth-Distance Product, Numerical Aperture
Pulse spreading in multimode fiber caused by light rays traveling paths of different lengths at different speeds, so they arrive at the receiver at slightly different times and smear the signal.
- Chromatic Dispersion
- Related: Modal Dispersion, Operating Wavelength Window
Pulse spreading caused by different wavelengths from a source traveling at slightly different speeds through the glass. It dominates in single-mode systems and worsens with distance and with wider source spectra.
- Numerical Aperture
- Related: Modal Dispersion
A number describing the range of angles over which a fiber accepts incoming light. Higher values mean a wider acceptance cone, typically more guided modes, and higher loss in multimode fiber.
- Rayleigh Backscatter
- Related: Optical Time-Domain Reflectometer (OTDR), Event Dead Zone
Small amounts of light scattered backward along a fiber by microscopic density variations in the glass. An OTDR uses this returned light to measure loss and locate faults.
- Operating Wavelength Window
- Related: Attenuation, Optical Loss Test Set (OLTS)
A wavelength band where fiber loss is relatively low and equipment is standardized, such as 850, 1300, 1310, and 1550 nanometers. Components and test sets must match the window in use.
- Bandwidth-Distance Product
- Related: Modal Dispersion
A multimode fiber rating, given in megahertz-kilometers, showing the bandwidth available over one kilometer. Dividing the rating by the actual link length gives the usable bandwidth at that distance.
- Tight-Buffered Cable
- Related: Loose-Tube Cable, Fan-Out Kit
A cable design in which each fiber is coated with a protective plastic layer directly against the glass, making it flexible and easy to connectorize for indoor and short-run use.
- Loose-Tube Cable
- Related: Tight-Buffered Cable, Fan-Out Kit, Splice Closure
A cable design in which fibers sit loosely inside a gel-filled plastic tube, isolating them from stress and moisture. It is common in outdoor and long-haul installations with high fiber counts.
- Armored Fiber Cable
- Related: Loose-Tube Cable, Bend Radius
Cable built with a metal or dielectric armor layer around the fiber core to resist rodent damage, crushing, and moisture. It is used outdoors, in industrial areas, or where physical protection is needed.
- Plenum-Rated Cable (OFNP)
- Related: Riser-Rated Cable (OFNR), NFPA 262
Cable tested and listed for installation in air-handling spaces. It has low flame spread and low smoke production and is usually the most costly jacket option available.
- Riser-Rated Cable (OFNR)
- Related: Plenum-Rated Cable (OFNP), NEC Article 770
Cable listed for vertical runs between floors, such as in riser shafts. It resists flame travel upward but is not approved for installation in air-handling plenums.
- Splice Closure
- Related: Fusion Splicing, Service Loop
A protective enclosure that houses and seals splices, shielding them from moisture, dust, and physical damage. It is used at aerial, buried, and underground splice points.
- Fiber Distribution Panel
- Related: Pigtail, Service Loop
A rack- or wall-mounted enclosure holding adapter panels and splice trays, providing an organized place to terminate cables and cross-connect patch cords within a fiber system.
- Fan-Out Kit
- Related: Loose-Tube Cable, Tight-Buffered Cable
A breakout assembly that splits a multi-fiber cable or ribbon into individually jacketed fibers with standard connectors, giving each fiber mechanical protection and a usable interface.
- Pulling Tension
- Related: Bend Radius, Cable Lubricant
The longitudinal force applied to a cable during installation. Exceeding the manufacturer's limit stretches or breaks fibers, so tension is monitored with a gauge and kept within specification.
- Bend Radius
- Related: Pulling Tension, J-Hook, Service Loop
The smallest curve a cable or fiber can tolerate without added loss or permanent damage. It is usually stated as a multiple of cable diameter and enforced during pulling, routing, and coiling.
- Innerduct
- Related: Pulling Tension, Cable Lubricant
A flexible or rigid subduct placed inside a conduit or trench to create separate pathways for cables. It eases future pulls and helps separate fiber from power conductors.
- J-Hook
- Related: Bend Radius
A hook-shaped support with a wide, smooth saddle used to hold cables overhead without kinking or over-bending them. Spacing must follow manufacturer and standard requirements.
- Cable Lubricant
- Related: Pulling Tension, Innerduct
A compatible compound applied to cable or duct to reduce friction during a pull. Lubricants must be approved for the jacket material and must not leave harmful residue on the fiber.
- Service Loop
- Related: Bend Radius, Fiber Distribution Panel
Extra cable coiled and stored at an enclosure or termination point. It supplies slack for future retermination, splicing, or equipment relocation without pulling new cable.
- Fusion Splicing
- Related: Cleaving, Mechanical Splice, Splice Closure
Joining two fibers by melting their ends together with an electric arc. It gives the lowest-loss, most reliable splice and requires properly cleaved ends, good alignment, and a splice protector.
- Mechanical Splice
- Related: Fusion Splicing, Cleaving
A splice made by aligning and locking two cleaved fibers inside a small assembly, often using index-matching gel. It is fast and needs no power but usually has higher loss than fusion splicing.
- Cleaving
- Related: Fusion Splicing, Ferrule
Scoring and breaking a fiber to produce a flat, square endface perpendicular to the core. A good cleave is required for low-loss splicing and for successful connector termination.
- Ferrule
- Related: Cleaving, Reflectance
A small precision cylindrical tube, usually ceramic, that holds and centers a fiber inside a connector so that it aligns accurately with the mating connector's fiber.
- Epoxy-and-Polish Connector
- Related: Ferrule, Cleaving, Reflectance
A field-installable connector where epoxy is injected and cured, then the endface is polished. It is durable and low loss but slower, and it requires polishing supplies and technique.
- Pigtail
- Related: Fusion Splicing, Fiber Distribution Panel
A short length of fiber with a factory-installed connector on one end and bare fiber on the other, spliced onto a cable to provide a finished termination point.
- Optical Loss Test Set (OLTS)
- Related: Reference Test Method, Link Loss Budget, Attenuation
A matched light source and power meter used to measure end-to-end loss of a link at a chosen wavelength. It is the standard instrument for Tier 1 link certification.
- Optical Time-Domain Reflectometer (OTDR)
- Related: Rayleigh Backscatter, Launch Cable, Event Dead Zone
An instrument that sends light pulses into a fiber and analyzes returning backscatter and reflections to measure loss, length, and the location of faults along the link.
- Launch Cable
- Related: Optical Time-Domain Reflectometer (OTDR), Event Dead Zone
A known-length reference fiber connected between the OTDR and the link under test, allowing the instrument to measure the first connector and stabilize its receiver before the link's events.
- Reference Test Method
- Related: Optical Loss Test Set (OLTS), Link Loss Budget
A defined way of connecting source and meter during loss testing, such as the one-jumper or two-jumper method, which determines whether end connectors are included in the measured loss.
- Link Loss Budget
- Related: Insertion Loss, Optical Loss Test Set (OLTS), Attenuation
The maximum loss a link can tolerate and still operate, calculated from transmitter output, receiver sensitivity, and allowances for repairs and aging. Test results must fall inside this budget.
- Event Dead Zone
- Related: Launch Cable, Optical Time-Domain Reflectometer (OTDR)
The distance following a reflective event, such as a connector, during which an OTDR cannot resolve a second event. Shorter pulses shrink dead zones but reduce measurement range.
- Reflectance
- Related: Ferrule, Epoxy-and-Polish Connector, Optical Time-Domain Reflectometer (OTDR)
The portion of light reflected back from a connector, splice, or break, expressed in decibels. High reflectance can disturb transmitters and points to a poor endface or an air gap.
- NEC Article 770
- Related: Riser-Rated Cable (OFNR), Plenum-Rated Cable (OFNP), NFPA 262
The section of the National Electrical Code covering installation of optical fiber cables and raceways, including which cable types are permitted in plenum, riser, and general-purpose locations.
- NFPA 262
- Related: Plenum-Rated Cable (OFNP), NEC Article 770
The standard Steiner tunnel test that measures flame spread and smoke density of cables intended for air-handling spaces; passing it is what qualifies a cable as plenum rated.
- Laser Safety Class
- Related: Safety Data Sheet (SDS)
A rating system, such as Class 1 or Class 1M, that describes the hazard level of an optical source and the precautions required. Intact fiber systems are typically Class 1.
- Safety Data Sheet (SDS)
- Related: Laser Safety Class, Cable Lubricant
A document supplied with chemicals such as solvents, adhesives, and lubricants that lists hazards, safe handling, first aid, and disposal requirements for the product.
- As-Built Documentation
- Related: Link Loss Budget, Service Loop
Updated drawings and records showing the fiber plant as actually installed, including cable routes, splice locations, and test results, used for maintenance and future additions.