F-Gas Category I · Keep the key ideas within reach.

Quick reference

F-Gas and ODS Regulations - Legal Duties and Environmental Obligations

  • F-Gas Regulation (EU) 2024/573 replaced Regulation 517/2014; it controls placing on market, use, leak checks, recovery and training for fluorinated greenhouse gases.

  • ODS Regulation (EC) 1005/2009 governs ozone-depleting substances including HCFCs and CFCs; virgin HCFC supply for maintenance is banned and reclaimed HCFC use is time-limited.

  • Operators must hold F-gas certificates and use certified personnel for installation, servicing, leak checking, recovery and decommissioning of equipment above defined charge thresholds.

  • Leak-check frequency scales with CO2e charge: no statutory check below 5 t CO2e (hermetically sealed 10 t), then every 12 months, 6 months and 3 months as thresholds rise; leak-detection systems allow intervals to be halved in frequency.

  • Records of refrigerant charge, leak checks, repairs and recovery must be kept for at least 5 years and made available to the competent authority on request.

  • Deliberate venting of F-gases to atmosphere is prohibited; refrigerant must be recovered by certified persons before disposal or dismantling of equipment.

  • Placing on market bans apply to certain HFCs and to new equipment using high-GWP gases; the phase-down is measured in CO2e tonnes, not kilograms.

  • Labelling and product/equipment information requirements apply to F-gas containers and equipment, and leakage of 1 kg or more (or 0.1% of charge for hermetically sealed) must be reported where required.

Quick reference

Refrigerant Identification, Properties and Environmental Impact

  • Refrigerants are identified by ASHRAE number (R-134a, R-410A, R-32) and by chemical family: CFC, HCFC, HFC, HFO, and natural refrigerants (ammonia R-717, CO2 R-744, hydrocarbons).

  • GWP expresses the climate impact of 1 kg of a gas relative to CO2 over 100 years; ODP expresses ozone-depletion potential relative to CFC-11 (ODP = 1.0).

  • CO2e charge = refrigerant mass (kg) × GWP; this value determines leak-check frequency and phase-down obligations.

  • R-410A is a near-azeotropic HFC blend (R-32/R-125, roughly 50/50) with GWP around 2088; R-32 is a single-component HFC with GWP around 675.

  • R-134a has GWP around 1430; R-404A around 3922; R-407C around 1774; these values drive compliance thresholds.

  • Blends must be charged as liquid to avoid fractionation; leaking blends change composition, so the remaining charge may not match the original specification.

  • Flammability classes per ASHRAE 34: A1 no flame propagation, A2L lower flammability, A3 higher flammability; toxicity class B denotes higher toxicity.

  • R-717 (ammonia) has GWP near 0 and ODP 0 but is toxic and flammable at certain concentrations; R-744 (CO2) has GWP 1 and operates at high pressures.

Quick reference

Installation, Commissioning and Record Keeping

  • Before commissioning, pressure-test and leak-test the system with dry nitrogen or OFN; never use refrigerant or oxygen for pressure testing.

  • Evacuate to a vacuum (typically below 500 microns or the manufacturer's specification) and hold to confirm no moisture or in-leakage before charging.

  • Record the as-built refrigerant charge in kilograms, the refrigerant type, GWP, CO2e tonnes, and the date of commissioning in the equipment log.

  • Commissioning records must include pressure-test results, evacuation results, leak-test method and result, and personnel certification numbers.

  • Equipment containing F-gases must carry a label stating refrigerant type, charge and CO2e where required by regulation.

  • Charge must be verified by weighing (weighing scale) rather than by pressure or sight glass alone; record the cylinder mass before and after charging.

  • Handover documentation to the operator must include the refrigerant log, leak-check schedule and the CO2e threshold that determines check frequency.

  • Any change of refrigerant type or charge during retrofit must be recorded and the label updated; reclaimed refrigerant must be documented with its source.

Quick reference

Service, Maintenance and Leak Detection

  • Leak detection methods include electronic detectors, UV dye, soap-bubble testing, and pressure/vacuum testing; each has limits and must be appropriate to the refrigerant.

  • Electronic leak detectors must be calibrated for the specific refrigerant; sensitivity and cross-sensitivity to other gases affect reliability.

  • A leak check must cover all joints, valves, flanges, Schrader ports, brazed connections and the compressor seals; inaccessible joints must still be checked where practicable.

  • After a leak is repaired, a follow-up leak check must be performed within one month of the repair to confirm the fix.

  • If a leak cannot be repaired, the remaining refrigerant must be recovered and the system decommissioned or the charge reduced within the regulatory timeframe.

  • Leak-detection systems, where fitted, must be checked at least every 12 months and their alarms logged; failure of the system reverts to standard leak-check intervals.

  • Refrigerant top-up during service counts toward the total charge and must be recorded; repeated top-ups without finding the leak indicate an unrepaired leak.

  • Non-hermetic systems with a CO2e charge of 5 tonnes or more require periodic leak checks; hermetically sealed systems have a higher starting threshold (10 t CO2e).

Quick reference

Recovery, Recycling, Reclaim and Disposal of Refrigerant

  • Recovery = removing refrigerant from a system into a container; recycling = basic cleaning (oil/particulate removal) for reuse; reclaim = reprocessing to new-product specification, usually by a certified facility.

  • Reclaimed refrigerant must meet AHRI 700 specification and be accompanied by a certificate of analysis; it can be used to meet virgin-gas obligations where permitted.

  • Recovery cylinders must be dedicated to a single refrigerant type, clearly labelled, and never overfilled; fill limit is typically 80% of water capacity by mass.

  • Never mix refrigerants in a recovery cylinder; mixed refrigerant is treated as waste and must be destroyed or reclaimed by an approved facility.

  • Recovery equipment must be capable of evacuating the system to the required vacuum (often 500 microns or per manufacturer) before dismantling.

  • Refrigerant removed from equipment being disposed of must be recovered before the equipment is scrapped; documentation of recovery must be retained.

  • Ozone-depleting substances must be destroyed or reclaimed by approved processes; venting ODS is prohibited.

  • Cylinders must be weighed before and after recovery to document the mass recovered and to avoid overfilling.

Quick reference

Safety, Handling and Cylinder Management

  • Refrigerant cylinders must be stored upright, secured, away from heat and ignition sources, and below the maximum permitted temperature; never expose to direct flame.

  • Cylinders must be hydrostatically tested periodically and marked with the test date; do not use cylinders past their test date or with damaged valves.

  • Liquid refrigerant can cause cold burns (frostbite); wear gloves, eye protection and face shield when handling liquid lines or charging.

  • Refrigerants are heavier than air in confined spaces and can displace oxygen; use gas detection and ventilation in plant rooms and basements.

  • Some refrigerants (A2L, A3) are flammable; observe ignition-source control, no-smoking rules and appropriate electrical classification in the work area.

  • Recovery and charging cylinders must never be filled above 80% liquid volume; overfilling risks hydraulic rupture on warming.

  • When brazing or welding near refrigerant lines, purge with nitrogen and ensure no refrigerant remains; decomposition products (e.g., hydrogen fluoride) are toxic.

  • Transport of refrigerant cylinders is subject to dangerous-goods rules; cylinders must be secured, valves closed and caps fitted during transport.