F-Gas Category I flashcards
F-Gas Category I · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- F-Gas Regulation 2024/573
- The EU regulation controlling fluorinated greenhouse gases; it sets leak-check frequencies, phase-down of HFCs, certification requirements, recovery obligations and labelling rules for equipment and containers.
- ODS Regulation 1005/2009
- The EU regulation on ozone-depleting substances; it bans production and use of CFCs and restricts HCFCs, requiring recovery and destruction of ODS at end of life.
- CO2e charge calculation
- Multiply the refrigerant mass in kilograms by its GWP to give tonnes of CO2 equivalent; this value sets the leak-check frequency and phase-down obligations.
- Leak-check frequency thresholds
- For non-hermetic systems: no statutory check below 5 t CO2e, then every 12 months from 5 t, every 6 months from 50 t, and every 3 months from 500 t CO2e.
- Record retention period
- Operators must keep refrigerant records - charge, leak checks, repairs and recovery - for at least five years and produce them to the competent authority on request.
- Venting prohibition
- Deliberate release of F-gases or ODS to atmosphere is prohibited; refrigerant must be recovered by certified personnel before servicing, dismantling or disposal of equipment.
- GWP definition
- Global Warming Potential is the climate impact of one kilogram of a gas relative to carbon dioxide over a 100-year horizon; CO2 has a GWP of 1.
- ODP definition
- Ozone Depletion Potential is the ability of a substance to destroy stratospheric ozone relative to CFC-11, which is assigned an ODP of 1.0.
- R-410A composition
- A near-azeotropic HFC blend of R-32 and R-125 at roughly 50/50 by mass, with a GWP near 2088; it must be charged as liquid.
- R-32 properties
- A single-component HFC with GWP around 675, classified A2L (lower flammability), used in split systems; it is not a blend so fractionation does not apply.
- R-134a GWP
- A single-component HFC with GWP around 1430, ODP zero, classified A1; commonly used in chillers and mobile air conditioning.
- R-717 ammonia
- A natural refrigerant with GWP near zero and ODP zero, but toxic and flammable at certain concentrations; requires specific safety and materials compatibility measures.
- R-744 carbon dioxide
- A natural refrigerant with GWP of 1 and ODP zero; it operates at high pressures and requires transcritical system design and high-pressure safety controls.
- Blend fractionation
- When a zeotropic blend leaks, components escape at different rates, changing composition; blends must therefore be charged as liquid and recharged fully after significant loss.
- Pressure testing gas
- Dry nitrogen or oxygen-free nitrogen is used for pressure and leak testing; oxygen and refrigerant must never be used for pressure testing due to fire or environmental risk.
- Evacuation target
- Evacuate the system to below about 500 microns (or manufacturer specification) and hold to confirm no moisture or air in-leakage before charging refrigerant.
- Commissioning record contents
- As-built charge in kilograms, refrigerant type, GWP, CO2e tonnes, pressure and evacuation results, leak-test method, and certifying technician's details.
- Weighing charge method
- Charge is verified by weighing the cylinder before and after charging; pressure gauges and sight glasses alone do not confirm the correct mass.
- Equipment label requirement
- Equipment containing F-gases must carry a label stating refrigerant type, charge mass and CO2e tonnes where required, updated after any retrofit or charge change.
- Electronic leak detector
- A handheld instrument that senses refrigerant concentration; it must be calibrated for the specific refrigerant because sensitivity and cross-sensitivity vary between gases.
- Post-repair leak check
- After repairing a leak, a follow-up leak check must be carried out within one month to confirm the repair is effective and the system is leak-free.
- Leak-detection system check
- Fixed leak-detection systems must be verified at least every 12 months and alarms logged; a failed system reverts the site to standard leak-check intervals.
- Unrepaired leak action
- If a leak cannot be repaired, the remaining refrigerant must be recovered and the system decommissioned or charge reduced within the regulatory timeframe.
- Recovery definition
- The removal of refrigerant from a system into a container for reuse, recycling, reclaim or destruction; it must be done by certified personnel.
- Recycling definition
- Basic cleaning of recovered refrigerant to remove oil and particulates so it can be reused in the same or similar equipment; it does not restore full specification.
- Reclaim definition
- Reprocessing recovered refrigerant to new-product specification, typically by a certified facility, with a certificate of analysis meeting AHRI 700.
- Recovery cylinder fill limit
- Recovery cylinders must not be filled above 80% of water capacity by mass; overfilling risks hydraulic rupture when the cylinder warms.
- Mixed refrigerant rule
- Never mix different refrigerants in one recovery cylinder; mixed refrigerant is treated as waste and must be destroyed or reclaimed by an approved facility.
- Cylinder storage rules
- Store cylinders upright, secured, away from heat and ignition, below maximum permitted temperature, and never use cylinders past their hydrostatic test date.
- Cold burn hazard
- Liquid refrigerant boils at very low temperature and can cause frostbite; wear gloves, eye protection and a face shield when handling liquid lines or charging.
- Asphyxiation risk
- Refrigerant vapour is heavier than air and can displace oxygen in basements and plant rooms; use gas detection and ventilation before entering confined spaces.
- Brazing decomposition hazard
- Heating refrigerant or its decomposition products can release toxic hydrogen fluoride; purge lines with nitrogen and ensure no refrigerant remains before brazing.