ITI Solar Technician Electrical (AITT Theory): Solar PV System Components: Batteries, Charge Controllers and Inverters

ITI Solar Technician Electrical (AITT Theory) · Work through your exam, one topic at a time.

All guide sections

Solar PV System Components: Batteries, Charge Controllers and Inverters

Solar PV System Components: Batteries, Charge Controllers and Inverters

This domain tests battery capacity and care, charge-controller choice, and inverter sizing and output quality.

Core rules

  • Battery capacity in Ah depends on the discharge rate; C10 means capacity at a 10-hour discharge. Depth of discharge (DoD) is the usable fraction.
  • Lead-acid specific gravity falls as the battery discharges; a fully charged cell is about 1.265 at 25°C. Equalisation charging helps balance cells.
  • PWM controllers are simple and suit small systems where array Vmp is close to battery voltage; MPPT controllers track the array's maximum power point and suit higher-voltage arrays.
  • Inverter must supply continuous load plus surge; output may be square, modified sine or pure sine. Grid-tie inverters must synchronise and have anti-islanding.

Worked example

A 12 V, 100 Ah battery is used to 50% DoD, giving 50 Ah × 12 V = 600 Wh. An inverter with 90% efficiency delivers 540 Wh. A 60 W fan can run for 540/60 = 9 hours, ignoring battery ageing and temperature derating.

Traps that cost marks

Treating Ah as usable energy without voltage; discharging lead-acid below 50% regularly; choosing an inverter by VA only and ignoring surge; connecting a grid-tie inverter without anti-islanding; using a PWM controller with a high-voltage array.