Calibration

The comparison of an instrument's output to a known reference standard across a range of inputs, followed by adjustment if needed, so the instrument reports values within an acceptable tolerance.

Related: As-found / as-left data, Traceability, Test standard
Zero adjustment

A calibration step that sets the instrument's output to its lowest defined value, often 4 mA or 0%, when the applied input is at the bottom of its range.

Related: Span adjustment, Calibration
Span adjustment

A calibration step that sets the instrument's output to its highest defined value, often 20 mA or 100%, when the applied input is at the top of its range.

Related: Zero adjustment, Calibration
Accuracy

How close a measured or output value is to the true value, usually expressed as a percentage of span or a fixed unit over the instrument's range.

Related: Tolerance, Repeatability
Repeatability

The closeness of agreement among repeated measurements of the same input under identical conditions, taken in the same direction, showing how consistently an instrument responds.

Related: Hysteresis, Accuracy
Hysteresis

The difference in instrument output at the same input value when that input is approached from increasing versus decreasing directions, caused by mechanical or magnetic lag.

Related: Repeatability, Deadband
Linearity

How closely an instrument's output follows a straight-line relationship to its input over its calibrated range, often measured as maximum deviation from a best-fit line.

Related: Hysteresis, Accuracy
Deadband

The range of input change that produces no measurable change in output; a small deadband can cause control offset, while a large one indicates friction or linkage issues.

Related: Hysteresis, Stiction
Tolerance

The allowable plus-or-minus deviation from a specified value; a calibration passes when the instrument's error remains inside this limit throughout the checked range.

Related: Accuracy, Test standard
Traceability

A documented chain of comparisons linking an instrument's calibration reference to a national or international standard, showing that the reference's accuracy is known and valid.

Related: Test standard, Calibration
As-found / as-left data

Recorded calibration results taken before any adjustment (as-found) and after adjustment (as-left), used to show instrument condition, drift, and whether repair was needed.

Related: Calibration, Drift
Test standard

A reference instrument or device with known accuracy and valid traceability, used as the comparison source during calibration; its tolerance must be tighter than the instrument being calibrated.

Related: Traceability, Loop calibrator
Loop calibrator

A portable source and meter that can generate or measure 4โ€“20 mA, simulate a transmitter, and read loop current, used for field calibration and loop troubleshooting.

Related: Test standard, Loop check
Preventive maintenance

Scheduled inspection, cleaning, lubrication, testing, and adjustment performed on instruments to prevent failures and keep them within performance limits before problems occur.

Related: Corrective maintenance, Work order
Corrective maintenance

Repair work performed after a fault is found, aimed at restoring an instrument or loop to normal operation; often triggered by a work order or troubleshooting finding.

Related: Preventive maintenance, Work order
Work order

A written or electronic authorization describing the maintenance task, asset tag, scope, safety requirements, parts, and completion record for a specific job.

Related: Corrective maintenance, Preventive maintenance
Lockout/tagout (LOTO)

A safety procedure that isolates energy sources and applies locks and tags so equipment cannot be started or energized while maintenance or calibration work is performed.

Related: Work order
Impulse line

The small-bore tubing that connects a process tap to a pressure transmitter; it must be filled properly, free of leaks and blockages, and sloped for venting or draining.

Related: Three-valve manifold, Drift
Three-valve manifold

A valve block mounted on a pressure transmitter with two block valves and one equalizing valve, used to vent, isolate, and equalize pressure safely during maintenance or calibration.

Related: Impulse line, Calibration
P&ID

A drawing that shows process piping, equipment, instruments, and control loops using standard symbols and tag numbers; used to locate instruments and understand loop function.

Related: Instrument index, Loop folder
Stiction

Friction that makes a valve or moving instrument part resist starting to move, then jump or slip suddenly; it causes erratic control and is often visible as a sticky valve stroke.

Related: Valve stroke test, Deadband
Ground fault

An unintended electrical connection between a signal circuit and earth ground that can cause noise, offset readings, blown fuses, or a loop that reads incorrectly or not at all.

Related: Electrical noise, Open circuit
Open circuit

A break in an electrical path, such as a cut wire, loose terminal, or failed component, that stops current flow and typically causes a zero or failed-loop indication.

Related: Ground fault, Loop check
HART communicator

A handheld or PC-based tool that communicates with HART-enabled instruments over the 4โ€“20 mA loop to read process variables, change configuration, and perform calibration or diagnostics.

Related: Loop calibrator, Calibration
Fail-safe

A design condition in which an instrument or system moves to a predefined safe state, often de-energized, when power, air, or signal is lost, to protect people and equipment.

Related: Cause and effect matrix, Valve stroke test
Electrical noise

Unwanted voltage or current induced into signal wiring by nearby power cables, motors, radio transmitters, or grounding problems; it can cause erratic readings and calibration errors.

Related: Ground fault, Drift
Drift

A gradual change in an instrument's output or zero point over time with the same input, often caused by temperature, aging, contamination, or mechanical wear, requiring recalibration.

Related: Calibration, As-found / as-left data
Punch list

A documented list of incomplete or defective items found during walkdowns or testing that must be corrected before a project or system is accepted and turned over.

Related: Mechanical completion, Pre-commissioning
Mechanical completion

The stage when construction and installation are finished and the system is ready for pre-commissioning checks, but before full functional testing and start-up.

Related: Pre-commissioning, Punch list
Pre-commissioning

Checks performed after installation and before commissioning, including inspection, cleaning, flushing, continuity checks, and basic instrument verification to confirm the system is ready for testing.

Related: Commissioning, Mechanical completion
Instrument index

A master list of all instruments in a project, including tag numbers, service, type, range, location, and drawing references, used for planning, calibration, and loop checks.

Related: P&ID, Loop folder
Project start-up

The transition from construction and commissioning to running the plant or system, including initial energization, first process feed, operator checks, and stabilization of controls.

Related: Commissioning, Pre-commissioning
Commissioning

The process of testing and verifying installed systems and equipment under controlled conditions to confirm they work as designed before handover to operations.

Related: Pre-commissioning, Site acceptance test (SAT)
Factory acceptance test (FAT)

A test performed at the vendor's shop before shipment to verify that a system or panel meets specifications, including I/O checks, functionality, and documentation, before site installation.

Related: Site acceptance test (SAT), Commissioning
Site acceptance test (SAT)

Testing performed at the final installation site to confirm that equipment and systems work correctly with actual field wiring, process connections, and site conditions.

Related: Factory acceptance test (FAT), Commissioning
Cause and effect matrix

A table that defines how each trip or interlock cause should affect final elements and alarms, used to test and document safety and control responses during commissioning.

Related: Fail-safe, Commissioning
Loop check

A field verification that each instrument in a control loop is correctly wired, tagged, calibrated, and communicating with the control system from sensor to final element.

Related: Point-to-point check, Loop folder
Point-to-point check

A test confirming that each field device is connected to the correct control-system input or output channel and that the signal arrives at the expected terminal.

Related: Loop check, Instrument index
Valve stroke test

A check that moves a control valve through its full travel, either manually or by signal, to confirm wiring, positioner action, travel limits, and feedback are correct.

Related: Loop check, Stiction
Loop folder

A collection of documents for one loop-drawings, calibration records, test sheets, and sign-offs-used to plan, perform, and record commissioning and loop-check activities.

Related: Loop check, Instrument index