Question 1Calibration

Calibration of an industrial instrument is best defined as:

  1. Adjusting its display until it reads correctly
  2. Comparing its output with a reference standard Correct answer.
  3. Repairing it until it matches the process
  4. Replacing the sensor with a new sensor

Explanation

Calibration establishes the relationship between the indicated value and the true value by comparison with a standard of known accuracy, and it records the result. Adjustment or repair is only one possible outcome of that comparison, not the definition of calibration itself.

Question 2Calibration

Measurement traceability means that an instrument's calibration is:

  1. Recorded on a signed calibration certificate
  2. Repeated at least once every twelve months
  3. Linked to national standards by an unbroken chain Correct answer.
  4. Performed only by the original manufacturer

Explanation

Traceability is an unbroken chain of comparisons, each with stated uncertainty, linking the instrument's calibration to national or international standards. Frequency and paperwork do not by themselves create traceability.

Question 3Calibration

Accuracy of a measurement refers to:

  1. How close the measured value is to the true value Correct answer.
  2. The spread of repeated readings about their mean
  3. How quickly the instrument responds to a step input
  4. The smallest input change that gives a detectable output

Explanation

Accuracy expresses the closeness of agreement between the measured value and the true value. It is distinct from precision, resolution and speed of response.

Question 4Calibration

A five-point calibration check of a 0-100 psig transmitter normally applies inputs at:

  1. 10, 20, 30, 40 and 50 psig
  2. 0, 25, 50, 75 and 100 psig Correct answer.
  3. 100, 75, 50, 25 and 0 psig in that order only
  4. 0, 50 and 100 psig only

Explanation

Five-point checks use 0, 25, 50, 75 and 100 percent of span so that linearity and endpoint performance are covered. Readings are usually taken both upscale and downscale so hysteresis can also be seen.

Question 5Calibration

A deadweight tester is used as a calibration standard for:

  1. Flow rate
  2. Pressure Correct answer.
  3. Level
  4. Temperature

Explanation

A deadweight tester balances pressure against known weights on a calibrated piston, producing a calculable reference pressure. It is a primary-style pressure standard and does not measure the other variables listed.

Question 6Calibration

An ice-point bath is used during temperature calibration because it provides a reference at:

  1. 100 °C at sea level
  2. 32 °C at equilibrium
  3. 0 °C at equilibrium Correct answer.
  4. −40 °C, where scales cross

Explanation

A properly prepared ice bath of melting ice and water at equilibrium provides a stable 0 °C reference. It is widely used as a check point for thermometers, RTDs and thermocouples.

Question 7Calibration

The span of an instrument ranged 50 to 250 °F is:

  1. 200 °F Correct answer.
  2. 250 °F
  3. 50 °F
  4. 300 °F

Explanation

Span is the algebraic difference between the upper and lower range values. Here 250 °F minus 50 °F equals 200 °F.

Question 8Calibration

A transmitter with a 4-20 mA output is ranged 0 to 200 psig. At 100 psig its output should be:

  1. 16 mA
  2. 8 mA
  3. 10 mA
  4. 12 mA Correct answer.

Explanation

100 psig is 50 percent of the 0-200 psig span, which corresponds to 50 percent of the 4-20 mA output. Halfway between 4 mA and 20 mA is 12 mA.

Question 9Calibration

Hysteresis error is the difference in indicated value when:

  1. Two different instruments measure the same input
  2. The instrument is read at two different ambient temperatures
  3. The same input is approached from opposite directions Correct answer.
  4. The input is held constant for a long period

Explanation

Hysteresis is the maximum difference in output for the same input when that input is reached first by increasing and then by decreasing it. It is revealed by comparing upscale and downscale readings at each test point.

Question 10Calibration

Repeatability describes the instrument's ability to:

  1. Respond linearly across its full range
  2. Recover its original output after an overrange
  3. Indicate the true value within a stated tolerance
  4. Give the same output for the same input each time Correct answer.

Explanation

Repeatability is the closeness of agreement among repeated outputs for the same input, applied in the same direction under the same conditions. It says nothing about how close the readings are to the true value.

Question 11Calibration

Linearity error is measured as the maximum deviation between the actual calibration curve and:

  1. The output at 50 percent of span
  2. The hysteresis loop traced by the instrument
  3. The manufacturer's stated accuracy
  4. A straight reference line through the range Correct answer.

Explanation

Linearity compares the actual input-output curve with a straight reference line, which may be drawn between the endpoints or fitted to the data. The largest deviation from that line is the linearity error.

Question 12Calibration

Deadband is the range through which an input can be changed without:

  1. Exceeding the stated accuracy of the instrument
  2. Causing any permanent damage to the sensor
  3. Changing the ambient temperature of the instrument
  4. Producing a detectable change in output Correct answer.

Explanation

Deadband is the finite input change required to produce a detectable output change after a reversal of direction. It is a distinct specification from accuracy, resolution and environmental sensitivity.

Question 13Calibration

A 0-100 psig transmitter indicates 51 psig when the true pressure is 50 psig. The error expressed as a percentage of span is:

  1. 0.5 %
  2. 5 %
  3. 1 % Correct answer.
  4. 2 %

Explanation

The error is 1 psig, and the span is 100 psig, so the error is 1 percent of span. Percentage of span is calculated against full span, not against the individual reading.

Question 14Calibration

The commonly applied test accuracy ratio rule requires the calibration standard to be:

  1. At least as accurate as the instrument under test
  2. Re-calibrated before every use
  3. Traceable to the manufacturer's factory
  4. At least four times more accurate than the instrument Correct answer.

Explanation

The widely used 4:1 rule holds that the standard's uncertainty should be no more than one quarter of the tolerance of the instrument under test. This keeps the uncertainty contributed by the standard small relative to the tolerance being verified.

Question 15Calibration

As-found calibration data are recorded to:

  1. Satisfy the purchase order for a new instrument
  2. Replace the need for a calibration certificate
  3. Show the instrument's condition after adjustment
  4. Record the performance before any adjustment Correct answer.

Explanation

As-found data capture how the instrument behaved before any adjustment and are used to judge drift and the validity of prior measurements. As-left data describe the condition after adjustment.

Question 16Calibration

Cold junction compensation in a thermocouple measurement is needed because the:

  1. Output depends on both junction temperatures Correct answer.
  2. Hot junction is exposed to the process fluid
  3. Thermocouple wire resistance changes with length
  4. Sensor output is nonlinear over its range

Explanation

A thermocouple produces a voltage proportional to the temperature difference between its hot and reference junctions. Cold junction compensation corrects for the actual temperature at the reference junction so the hot junction temperature can be determined.

Question 17Calibration

A loop calibration differs from an instrument calibration in that it:

  1. Checks the transmitter, wiring and receiver together Correct answer.
  2. Uses a portable calibrator instead of a bench standard
  3. Is performed only on digital transmitters
  4. Requires the process to stay at operating temperature

Explanation

Loop calibration verifies the entire measurement or control path, including the transmitter, wiring, input card and receiving device. Instrument calibration verifies the transmitter alone, away from the rest of the loop.

Question 18Calibration

Before recording calibration data on an instrument moved from a hot truck into a cool plant, the technician should:

  1. Apply full span pressure immediately to seat the seals
  2. Shorten the test leads to reduce electrical noise
  3. Allow time for the instrument to reach ambient temperature Correct answer.
  4. Zero the instrument while it is still warm

Explanation

Sensors and electronics need time to equalize with the surrounding temperature, otherwise thermal gradients cause transient zero and span errors. Data taken before stabilization are not representative of installed performance.

Question 19Calibration

A transmitter has an accuracy of ±0.5 % of span and a range of 0-200 °C. The maximum allowable error at a reading of 50 °C is:

  1. ±2.0 °C
  2. ±0.5 °C
  3. ±0.25 °C
  4. ±1.0 °C Correct answer.

Explanation

A percentage-of-span specification applies across the whole range, so the allowable error is 0.5 percent of 200 °C, or 1.0 °C. It does not shrink at lower readings the way a percentage-of-reading specification would.

Question 20Calibration

A calibration certificate should include, at a minimum, the:

  1. Results, the standard used and its traceability Correct answer.
  2. The purchase price and delivery date
  3. The process fluid and line pressure
  4. The operator's name and shift

Explanation

A usable certificate identifies the instrument, states as-found and as-left results, and identifies the reference standard with its traceability and uncertainty. This is what allows the calibration to be trusted and audited.

Question 21Calibration

A transmitter with a 0-500 °F span has an accuracy of ±1 % of reading. At a reading of 100 °F, the allowable error expressed as a percentage of span is:

  1. 5.0 %
  2. 0.2 % Correct answer.
  3. 1.0 %
  4. 0.5 %

Explanation

One percent of the 100 °F reading is 1 °F. Dividing that by the 500 °F span gives 0.2 percent of span, which is why percentage-of-reading specifications tighten at low readings.

Question 22Calibration

A 4-20 mA transmitter ranged 0-200 °C outputs 11.6 mA at a true 100 °C. The as-found error as a percentage of span is:

  1. −2.5 % Correct answer.
  2. −0.25 %
  3. −0.4 %
  4. −4.0 %

Explanation

The ideal output at midspan is 12 mA, so the deviation is 0.4 mA. Dividing 0.4 mA by the 16 mA span and multiplying by 100 gives 2.5 percent of span, in the negative direction.

Question 23Calibration

An instrument has a tolerance of ±2.0 psi. A calibrator with an uncertainty of ±0.25 psi gives a test uncertainty ratio of:

  1. 4:1
  2. 2:1
  3. 16:1
  4. 8:1 Correct answer.

Explanation

The ratio is the instrument tolerance divided by the standard's uncertainty, or 2.0 divided by 0.25, which equals 8. A ratio well above 4:1 keeps the standard's contribution small compared with the tolerance being verified.

Question 24Calibration

An instrument is found out of tolerance during a routine calibration. The most important follow-up action is to:

  1. Recalibrate it and file the certificate without further review
  2. Shorten the calibration interval for all plant instruments
  3. Replace the instrument regardless of its condition
  4. Review measurements made since the last good calibration Correct answer.

Explanation

An out-of-tolerance finding raises doubt about every measurement the instrument produced since its last valid calibration. The impact on product, safety and compliance must be assessed before the instrument is simply adjusted.

Question 25Calibration

As-found data for a 0-500 °F, 4-20 mA transmitter are 4.10 mA at 0 °F and 19.80 mA at 500 °F. The span error is approximately:

  1. +1.9 % of span
  2. −1.9 % of span Correct answer.
  3. +0.6 % of span
  4. −0.6 % of span

Explanation

The measured span is 19.80 minus 4.10, or 15.70 mA, against an ideal 16.00 mA. The difference of 0.30 mA divided by 16.00 mA gives about 1.9 percent, and the sign is negative because the measured span is short.

Question 26Calibration

A key advantage of a 4-20 mA live-zero signal over a 0-20 mA signal is that it:

  1. allows an open circuit to be detected Correct answer.
  2. eliminates the need for a calibrator
  3. increases the resolution of the signal
  4. reduces the power required by the loop

Explanation

With a live zero, valid zero-scale operation still requires about 4 mA of current, so a current near 0 mA indicates a broken wire, lost power, or a failed transmitter. A 0-20 mA signal cannot distinguish a failed loop from a legitimate zero reading.

Question 27Calibration

Metrological traceability of a calibration means the measurement result can be related to:

  1. a national standard through an unbroken chain of comparisons Correct answer.
  2. the least accurate instrument connected in the same loop
  3. the manufacturer's published accuracy specification for the model
  4. the plant's historical calibration records for that tag

Explanation

Traceability requires an unbroken, documented chain of calibrations, each with stated uncertainty, linking the working standard to a national or international reference. The chain is what allows the result to be compared meaningfully with measurements made elsewhere.

Question 28Calibration

A Pt100 RTD has a nominal resistance of 100 ohms at:

  1. 20 °C
  2. 100 °C
  3. 0 °C Correct answer.
  4. −50 °C

Explanation

The '100' in Pt100 refers to 100 ohms at the ice point, 0 °C, with platinum as the element material. Resistance rises with temperature at roughly 0.385 ohm per ohm per °C for the common curve.

Question 29Calibration

A 4-20 mA signal measured across a 250 ohm precision resistor produces an output voltage range of:

  1. 4-20 V
  2. 1-5 V Correct answer.
  3. 0-10 V
  4. 2-10 V

Explanation

Ohm's law gives 4 mA × 250 ohm = 1 V and 20 mA × 250 ohm = 5 V, so the signal is converted to a 1-5 V range. This conversion is common when a voltage input is used for calibration checks.

Question 30Calibration

Zero drift in an instrument is a change in:

  1. the total resistance of the loop wiring
  2. the output at zero input over time Correct answer.
  3. the ambient temperature of the enclosure
  4. the span with no change in the zero

Explanation

Zero drift is a shift of the low-end output with no input applied, so the curve moves up or down without changing its slope. Span drift, by contrast, changes the slope of the input-output relationship.

Question 31Calibration

After a successful shop calibration, an instrument is normally identified in the field with:

  1. a revised P&ID drawing for the loop
  2. a dated calibration label Correct answer.
  3. a new serial number assigned by the shop
  4. a replacement nameplate from the vendor

Explanation

A calibration label records the date of calibration and the next due date so that field personnel can confirm the instrument's status at a glance. It ties the physical device to the calibration record.

Question 32Calibration

As-left calibration data describe an instrument's performance:

  1. after adjustment and verification Correct answer.
  2. at the factory before shipment
  3. during the next scheduled calibration
  4. before any adjustment was made

Explanation

As-left data are recorded after adjustments have been made and the instrument has been rechecked, showing the condition in which it returns to service. As-found data, in contrast, capture the condition before any adjustment.

Question 33Calibration

A pressure transmitter is ranged 20 to 100 psig with a 4-20 mA output. At a true pressure of 20 psig, the expected output is:

  1. 20 mA
  2. 8 mA
  3. 4 mA Correct answer.
  4. 12 mA

Explanation

The lower range value always corresponds to the 4 mA live zero, even when the zero is suppressed as it is here. Only at 100 psig, the upper range value, should the output reach 20 mA.

Question 34Calibration

When adjusting a transmitter that is out of tolerance at both zero and span, the technician should:

  1. adjust the span first, then zero, and stop
  2. adjust zero, then span, then repeat Correct answer.
  3. replace the transmitter with a new unit
  4. adjust the span only and leave the zero

Explanation

Zero and span adjustments interact on most transmitters, so zero is corrected first, span second, and the sequence is repeated until both points fall within tolerance. This iteration converges on a correct curve without over-adjusting either pot.

Question 35Calibration

A manufacturer specifies accuracy at reference conditions of 23 °C ± 2 °C. If a calibration is performed in an area at 40 °C, the technician should expect:

  1. the calibrator to correct the reading automatically
  2. a lower zero reading but an unchanged span
  3. no change, because transmitters are compensated at any temperature
  4. extra uncertainty from temperature effects Correct answer.

Explanation

The published accuracy applies only within the stated reference conditions, so operating outside them adds a temperature-effect uncertainty to the result. Good practice is to calibrate at or near reference conditions, or to include the effect in the reported uncertainty.

Question 36Calibration

A periodic check confirms that an instrument still indicates within tolerance and no adjustment is made. This activity is best described as:

  1. a verification check Correct answer.
  2. a span adjustment
  3. a full calibration
  4. a functional overhaul

Explanation

Verification confirms that an instrument meets its tolerance without adjusting it, whereas calibration documents and corrects the relationship between input and output. A successful verification may still be recorded as part of the calibration history.

Question 37Calibration

A 0-100 inH2O transmitter reads 26.0 inH2O at a true pressure of 25.0 inH2O. The error expressed as a percentage of span is:

  1. 1.0 % Correct answer.
  2. 0.1 %
  3. 25 %
  4. 4.0 %

Explanation

The error is 26.0 − 25.0 = 1.0 inH2O, and the span is 100 inH2O, so the error is 1.0/100 × 100 = 1.0 % of span. Expressing error against span gives a single figure that applies across the range.

Question 38Calibration

A five-point calibration performed both upscale and downscale is primarily used to reveal:

  1. response at intermediate points Correct answer.
  2. the polarity of the loop wiring at the terminals
  3. the transmitter's serial number and model code
  4. the loop power supply voltage under load

Explanation

Testing at 0, 25, 50, 75, and 100 % in both directions checks the shape of the curve at points other than the endpoints and reveals hysteresis between the ascending and descending runs. A zero-and-span check alone can miss errors in the middle of the range.

Question 39Calibration

A pH loop is calibrated with pH 7.00 and pH 4.01 buffers. The pH 7.00 buffer is used to set the:

  1. temperature compensation setting
  2. zero, or isopotential, point Correct answer.
  3. response time of the electrode
  4. span, or slope, of the electrode

Explanation

A pH electrode produces zero millivolts near pH 7, so the pH 7.00 buffer establishes the zero point. The second buffer, here pH 4.01, is then used to set the slope or span.

Question 40Calibration

An I/P transducer with a 4-20 mA input and a 3-15 psi output is being calibrated. At 12 mA the expected output is:

  1. 7 psi
  2. 8 psi
  3. 9 psi Correct answer.
  4. 6 psi

Explanation

The 4-20 mA input and 3-15 psi output are both linear spans, so midscale current produces midscale pressure: 3 + 0.5 × (15 − 3) = 9 psi. The 12 mA point is exactly 50 % of the current span.

Question 41Calibration

The reported uncertainty of a calibration should account for:

  1. only the accuracy of the calibration standard
  2. all significant sources of measurement error Correct answer.
  3. the purchase cost of the calibration service
  4. only the resolution of the instrument display

Explanation

An uncertainty statement combines every significant contribution, including the standard, the resolution and repeatability of the unit under test, and environmental effects. Reporting only one contributor understates the true uncertainty of the result.

Question 42Calibration

An instrument is consistently found drifting in the same direction at each calibration. The most appropriate action is to:

  1. remove the instrument from service permanently
  2. shorten its calibration interval Correct answer.
  3. increase the transmitter span
  4. extend its calibration interval

Explanation

A repeatable drift pattern shows that the instrument may move out of tolerance before the next scheduled calibration, so the interval should be shortened. Intervals are adjusted from observed as-found results rather than held fixed forever.

Question 43Calibration

A differential pressure flow transmitter uses square-root extraction. At 25 % of the differential pressure span, the indicated flow should be:

  1. 12.5 %
  2. 75 %
  3. 25 %
  4. 50 % Correct answer.

Explanation

Flow is proportional to the square root of differential pressure, so 25 % DP corresponds to 0.5 × 100 = 50 % flow. This is why calibration points for a flow loop must be chosen in flow units, not DP units.

Question 44Calibration

When calibrating a pressure switch, the technician must record both the:

  1. port size and thread type of the fitting
  2. ambient temperature and relative humidity
  3. set point and reset point Correct answer.
  4. supply voltage and loop current at the switch

Explanation

A pressure switch is characterised by the pressure at which it trips and the pressure at which it resets, and the difference between them is the switch deadband. Recording both values confirms that the device performs as specified in both directions.

Question 45Calibration

As-found data for a 0-200 psig, 4-20 mA transmitter are 4.5 mA at 0 psig and 20.5 mA at 200 psig. The zero error and span error, as percentages of output span, are approximately:

  1. 3.1 % zero error, 3.1 % span error
  2. 3.1 % zero error, 0 % span error Correct answer.
  3. 1.6 % zero error, 1.6 % span error
  4. 0 % zero error, 3.1 % span error

Explanation

The zero error is 4.5 − 4.0 = 0.5 mA, which is 0.5/16 × 100 = 3.1 % of output span. The output span is 20.5 − 4.5 = 16.0 mA, identical to the ideal 16 mA, so the span error is zero and a zero shift alone explains the data.

Question 46Calibration

A smart transmitter's analog output reads 4.05 mA and 20.10 mA while its digital process variable is known to be correct. The appropriate action is to:

  1. perform a 4-20 mA output trim Correct answer.
  2. perform a sensor trim on the primary element
  3. replace the transmitter's sensor module
  4. change the ranged values in the transmitter

Explanation

When the digital value is correct but the analog current is offset, the error lies in the output stage, so an output trim aligns the 4 mA and 20 mA endpoints with the digital value. A sensor trim would be used when the digital process variable itself is wrong.

Question 47Calibration

A closed-tank differential pressure level transmitter has its high leg on the bottom tap and its low leg on the vapor space, and the wet leg is full of condensate. This installation requires:

  1. no zero adjustment, because the legs cancel
  2. square-root extraction, because the tank is closed
  3. zero elevation, because the wet leg adds pressure Correct answer.
  4. zero suppression, because the high leg has a static head

Explanation

At zero level, the condensate in the low leg applies a static head that makes the measured differential pressure negative, so the transmitter must be elevated to output 4 mA at that negative value. Zero elevation applies a negative bias that is removed as the level rises.

Question 48Calibration

A flowmeter is calibrated by comparison against a reference meter with an uncertainty of ±0.25 % of reading, while the meter under test is rated at ±1.0 % of reading. The resulting test uncertainty ratio is about:

  1. 4:1 Correct answer.
  2. 1:4
  3. 1:2
  4. 2:1

Explanation

The test uncertainty ratio is the tolerance of the unit under test divided by the uncertainty of the standard: 1.0 % / 0.25 % = 4:1. A ratio of at least 4:1 is commonly required so that the standard's contribution to the result is small.

Question 49Calibration

A technician simulates a 3-wire RTD with a resistance decade box but connects it to the transmitter using only two of the leads. The effect on the indicated temperature is that it:

  1. has no effect at any practical lead length
  2. doubles the sensitivity of the RTD element
  3. adds lead resistance as a positive offset Correct answer.
  4. cancels the lead resistance completely

Explanation

A 3-wire connection lets the transmitter measure and cancel the resistance of one lead, but with only two leads the total lead resistance adds directly to the element resistance. The result is an apparent temperature higher than the true value.

Question 50Calibration

A calibration standard has a stated expanded uncertainty of ±0.08 % of reading. What is the smallest instrument tolerance for which a 4:1 test uncertainty ratio is maintained?

  1. ±0.32 % of reading Correct answer.
  2. ±0.02 % of reading
  3. ±0.64 % of reading
  4. ±0.08 % of reading

Explanation

A 4:1 test uncertainty ratio requires the instrument tolerance to be at least four times the standard's uncertainty. Multiplying ±0.08 % by 4 gives ±0.32 % of reading, which is the minimum tolerance that satisfies the ratio.