Ohm's law
Current through a resistance equals voltage divided by resistance (I = E/R). In AC circuits, impedance Z replaces R, and the relationship must account for phase angle.
Three-phase power formula
For a balanced three-phase load, real power equals the square root of three times line voltage times line current times power factor.
RMS voltage
The effective value of a sine wave, equal to peak voltage divided by the square root of two. It produces the same heating effect as an equal DC voltage.
Parallel circuit rules
Voltage is the same across all branches, total current is the sum of branch currents, and total resistance is found from the sum of the reciprocals.
Conductors in parallel
Each paralleled conductor must be 1/0 AWG or larger, of the same material, length, insulation, and termination, and arranged so current divides equally.
Box fill calculation
Count each conductor, each device yoke, each clamp, and equipment grounding conductors, then compare the total to the marked cubic-inch capacity of the box.
NM cable support
Nonmetallic sheathed cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet along the run.
Conduit expansion fittings
Expansion fittings are required where thermal expansion of a conduit run exceeds a quarter inch, such as long PVC runs exposed to temperature change.
Continuous load factor
A load operating three hours or more is calculated at 125 percent for branch-circuit and feeder sizing; noncontinuous loads are taken at 100 percent.
Dwelling lighting load
General lighting in dwellings is calculated at 3 volt-amperes per square foot of floor area, plus small-appliance and laundry branch circuits at 1,500 VA each.
Dwelling service demand factors
Apply 100 percent to the first 3,000 VA, 35 percent to the next 117,000 VA, and 25 percent to any amount above 120,000 VA.
Receptacle spacing rule
In dwelling habitable rooms, no point along the floor line may be more than 6 feet from a receptacle, and wall spaces 2 feet or wider require one.
Voltage drop recommendation
Keep branch-circuit voltage drop under 3 percent and the combined feeder plus branch drop under 5 percent for reasonable efficiency of connected equipment.
Neutral bonding location
The grounded conductor is bonded to the equipment grounding system only at the service disconnecting means; downstream panels keep neutral and ground bars separate.
Next-higher overcurrent rule
Where conductor ampacity does not match a standard device rating, the next higher standard rating may be used if the load does not exceed conductor ampacity.
Equipment grounding conductor sizing
The equipment grounding conductor size is selected from the table keyed to the rating of the overcurrent device protecting the circuit, not the phase conductor alone.
GFCI required locations
Ground-fault protection is required for dwelling bathroom, kitchen countertop, garage, outdoor, and unfinished basement receptacles, among other specified locations.
AFCI protection
Arc-fault circuit-interrupter protection is required for most 120-volt branch circuits in dwelling living areas, including bedrooms, using listed devices.
Rough-in inspection
The inspection performed after wiring is installed but before walls or ceilings are covered, verifying box fill, support, and routing that will later be concealed.
Correction notice content
A correction notice should state the code section, the exact location, and the corrective action required so the installer can respond without ambiguity.
Insulation resistance test
A megohmmeter applies a high DC voltage to measure insulation resistance; readings below one megohm per 1,000 test volts warrant investigation.
Polarity verification
Testing confirms the grounded conductor is not switched, the equipment grounding conductor is continuous, and neutral and ground are separated downstream of the service.
Working clearance depth
At least 36 inches of clear depth, 30 inches wide and 6 feet 6 inches high is required in front of electrical equipment, with greater depth at higher voltages.
Dedicated equipment space
The space above and in front of switchboards and panelboards must be kept clear of piping, ducts, and foreign systems not related to the electrical installation.
Available fault current check
Plan review confirms that the available fault current at each point does not exceed the interrupting rating of the overcurrent devices installed there.
Adopted code edition
The locally adopted code edition and amendments govern enforcement; a permit is evaluated against the edition in effect at the time of application.
Hazardous location classes
Class I covers flammable gases and vapors, Class II covers combustible dust, and Class III covers ignitable fibers and flyings present in the area.
Division 1 versus Division 2
Division 1 describes a location where the hazard exists under normal operating conditions; Division 2 describes one where it exists only under abnormal conditions.
Hazardous location seals
Conduit seals prevent gases or vapors from passing through the conduit system and are installed at specified distances from enclosures in classified areas.
Health care critical branch
The critical branch in a health care facility supplies selected patient care areas and must be kept separate from the general care branch circuits.
Inspector conflict of interest
An inspector must disclose any financial interest in the work being inspected and decline the assignment where a conflict could affect the decision.
Inspection record retention
Inspection records should be retained for the period the jurisdiction requires, because they document the code basis for each approval or rejection.