Design indoor cooling condition
ARI standard rating condition is 80°F dry bulb and 67°F wet bulb indoors, with 95°F dry bulb outdoor air.
Nominal cooling airflow
400 cfm per ton of cooling capacity is the nominal value; the acceptable range is roughly 350 to 450 cfm per ton.
Evaporator temperature split
The dry-bulb temperature difference between return air and supply air; typical cooling range is 16°F to 22°F at design airflow.
Superheat charging method
Used with fixed-orifice or piston metering devices; measure suction line temperature minus saturation temperature, targeting about 8°F to 12°F.
Subcooling charging method
Used with thermostatic expansion valves; measure liquid line temperature minus saturation temperature, targeting about 8°F to 12°F per manufacturer.
Dry bulb vs wet bulb
Dry bulb measures sensible air temperature; wet bulb measures temperature with evaporative cooling and indicates moisture content and latent load.
Heat pump balance point
Outdoor temperature where heat pump capacity equals building heat load; below it, auxiliary or emergency heat must supplement.
TXV sensing bulb
The bulb clamps to the suction line and senses evaporator outlet temperature; it modulates refrigerant flow to maintain superheat.
Filter drier arrow
The arrow on the filter drier marks refrigerant flow direction; bi-flow driers are required on heat pumps for reverse-cycle operation.
Suction line insulation
Vapor suction lines are insulated to prevent heat gain and condensation; liquid lines are generally not insulated except in high-humidity spaces.
Condensate trap depth
The trap depth must exceed the blower's negative static pressure in inches of water column, typically 2 to 4 inches.
Reversing valve function
A pilot-operated valve that swaps evaporator and condenser roles by redirecting refrigerant flow for heating or cooling.
Crankcase heater purpose
Keeps compressor oil warm when idle to prevent refrigerant migration and liquid slugging at startup.
Accumulator purpose
Installed on the suction line of heat pumps to hold liquid refrigerant and prevent it from reaching the compressor.
ASHRAE 62.2 ventilation rate
Whole-house ventilation formula: Q = 0.03A + 7.5(N+1) cfm, where A is floor area and N is bedrooms.
MERV filter rating
MERV rates particle capture; MERV 8 is common residential, MERV 13 offers higher filtration with higher pressure drop.
Return air prohibition
Return air must not be drawn from bathrooms, kitchens, garages, or rooms with combustion appliances unless specifically engineered.
Indoor relative humidity range
Comfort and mold prevention typically target 30% to 50% relative humidity; sustained levels above 60% support biological growth.
Carbon monoxide exposure limits
EPA limits are 9 ppm for 8 hours and 35 ppm for 1 hour; combustion appliance testing uses these as reference thresholds.
Filter pressure drop
A clean residential filter typically drops 0.1 to 0.2 inches water column; excessive drop reduces airflow and capacity.
Ohm's law
Voltage equals current times resistance (E = I × R); power equals voltage times current (P = E × I).
Run capacitor tolerance
A run capacitor is normally good within plus or minus 6% to 10% of its rated microfarad value; bulging indicates replacement.
Thermostat C terminal
The common terminal provides 24-volt power to the thermostat; it completes the control circuit and supports smart thermostats.
Disconnect location rule
The service disconnect must be within sight of and not more than 50 feet from the equipment it controls.
MCA and MOP
Minimum circuit ampacity is the minimum conductor rating; maximum overcurrent protection is the largest breaker or fuse permitted.
Winding resistance balance
Compressor run, start, and common winding resistances should balance within about 10%; a large imbalance suggests a damaged winding.
Sensible heat formula
Sensible Btu/h = 1.08 × cfm × dry-bulb temperature difference at sea level; 1.08 derives from air density and specific heat.
Total heat formula
Total Btu/h = 4.5 × cfm × enthalpy difference; 4.5 equals 60 minutes times 0.075 pounds per cubic foot.
Total external static pressure
TESP is the sum of supply and return static pressures measured across the blower; residential equipment typically rates near 0.5 inches water column.
Evacuation micron level
A properly evacuated system holds below 500 microns with the vacuum pump isolated; a rising reading indicates leaks or moisture.
Nitrogen leak test pressure
Pressure-test with dry nitrogen, commonly 150 to 300 psi for residential split systems, never with refrigerant or oxygen.
Low superheat diagnosis
Low superheat with high suction pressure suggests overcharge or excess airflow; low superheat with low suction suggests restriction or low load.