Mistake 1

Treating flex duct as if it can be run with long slack loops and sharp 90-degree bends at the boot, then expecting design airflow at the register.

Candidates memorize 'use flex sparingly' but never learn the actual pressure-loss consequence: sagging or sharply bent flex collapses the effective diameter, and a single tight bend can multiply resistance far beyond the straight-run value. The exam tests whether you can predict the airflow and pressure effect, not just recite a rule.

What to do instead

Learn the qualitative rule cold: keep flex runs short, fully extended, supported at manufacturer spacing, with gradual bends and no kinks or compression at terminations. Practice predicting which of two layouts has higher static pressure loss and why, and be able to explain the effect in terms of effective diameter and friction rate.

Mistake 2

Using total external static pressure as if it were velocity pressure, or mixing up which pressure reading corresponds to which duct location when interpreting a manometer setup.

The three pressures (static, velocity, total) are defined by where the sensing probe points and how it is oriented, and candidates often study them as vocabulary rather than as measurement geometry. Exam items describe probe orientation or tap location and expect you to identify the reading.

What to do instead

Build a mental picture of each probe: static pressure sensed perpendicular to flow through a side-wall tap, total pressure sensed facing into the airstream, velocity pressure as the difference. Practice converting between them with the velocity-pressure relationship and rehearse which tap location yields which reading on a supply, return, and fan inlet.

Mistake 3

Sizing a return or transfer path without accounting for the pressure drop of the return grille, filter, and door undercut, then concluding the system is balanced when the supply side checks out.

Candidates focus on supply duct sizing and skip the return path because it is less visible in the design narrative. Real systems fail on return-side restriction, and exam items deliberately put the bottleneck on the return or in the transfer air path.

What to do instead

Always trace the complete air path from return grille through filter, fan, supply duct, and back through transfer openings. Practice adding up pressure drops across every component in series and identifying the highest-resistance element. Know that a starved return shows up as low airflow everywhere, not just at one register.

Mistake 4

Selecting a duct sealant or mastic class without checking the pressure class and temperature of the system it will serve, or assuming tape alone satisfies sealing requirements.

Sealing requirements are tied to pressure class and location in the system, and candidates often treat 'seal the ducts' as a single generic step. The exam tests whether you know that seal level and sealant rating must match the pressure class and that some joints require mechanical fastening plus sealant.

What to do instead

Study the sealing requirement tables by pressure class and location (connections to equipment, transverse joints, longitudinal seams). Memorize that pressure-sensitive tape alone is generally not acceptable as the primary seal on higher-pressure systems and that mastic or approved tape systems must be rated for the service. Practice matching a described system to its required seal level.

Mistake 5

Confusing duct insulation R-value requirements with vapor barrier placement, and installing the vapor retarder on the wrong side of the insulation in a humid climate.

Candidates learn R-values as numbers to memorize but do not connect them to condensation control. The vapor retarder must be on the warm side of the insulation to prevent moisture migration to the cold duct surface, and exam items test the consequence of getting it backwards.

What to do instead

Reason from the physics: the vapor barrier goes on the outside (warm side) of the insulation so dew point is never reached at the duct surface. Practice identifying which surface condenses when the barrier is misplaced, and know that a damaged or unsealed jacket at joints and penetrations defeats the barrier regardless of R-value.

Mistake 6

Reading a ductulator or friction chart and picking a size without verifying that the resulting velocity is within the acceptable range for the application and that the total pressure drop fits the available fan static.

Candidates treat the ductulator as a lookup tool and stop at the first size that gives an acceptable friction rate, forgetting that equal-friction sizing must still be checked against velocity limits and cumulative pressure drop. Exam items give a CFM and friction rate and expect a defensible size with justification.

What to do instead

Practice the full check: pick size from the chart, then confirm velocity is appropriate for the duct's location (main vs. branch, supply vs. return) and that the run's cumulative loss plus all components stays within available static. Be able to explain why a smaller duct at higher velocity may be unacceptable even when the friction rate looks fine.

Mistake 7

Skipping the pre-task safety review and lockout/tagout steps when a question describes working near a fan, heater, or electrical disconnect, and answering only the technical installation step.

Candidates treat safety items as common sense and rush to the technical answer. Exam items embed a hazard in an otherwise technical scenario, and the correct answer is often the isolation or verification step that comes before the work.

What to do instead

For every scenario question, ask what must be de-energized, isolated, or verified before the described task. Memorize the lockout/tagout sequence and the requirement to verify absence of energy, plus fall protection and confined-space triggers. Practice spotting the embedded hazard in installation and testing scenarios.

Mistake 8

Confusing balancing damper adjustment with system commissioning, and assuming that opening all dampers fully and measuring at the air handler completes the balance.

Candidates equate 'balancing' with 'adjusting dampers until the numbers look right' and skip the proportional balancing method and the documentation trail. Exam items test the sequence: measure, adjust proportionally, re-measure, and record, with the air handler verified first.

What to do instead

Learn the order of operations: verify fan speed and total airflow first, then proportionally balance branches starting from the index run, then confirm the total. Know that adjusting one damper changes others and that final readings must be recorded on a balance report with conditions noted. Practice describing the sequence for a multi-branch system.

Mistake 9

Treating a duct leakage test as a pass/fail formality without knowing how test pressure, test section boundaries, and allowable leakage are established for the specified pressure class.

Candidates memorize that ducts must be leak-tested but not how the test is set up: which section is isolated, what pressure is applied relative to design, and how leakage limit scales with duct surface area and pressure class. Exam items ask for the setup or the interpretation of a result.

What to do instead

Study the leakage test procedure: seal and isolate the section, cap openings, pressurize to the specified test pressure, and compare measured leakage to the allowable for that pressure class and area. Practice computing allowable leakage from surface area and class, and know that a failed section must be sealed and retested before closeout.

Mistake 10

Answering code and documentation questions from field habit rather than from the adopted code or standard, and ignoring which edition or local amendment governs.

Candidates learn installation practice from the job and assume the exam accepts the same shortcuts. Exam items are written against a specific adopted code or standard, and habit-based answers often conflict with the minimum requirement or the documentation obligation.

What to do instead

Anchor answers in the governing code or standard and note when a local amendment could change the answer. Memorize the documentation set that must be delivered: submittals, test reports, balance reports, and as-built drawings. For any 'is this acceptable' item, ask whether the practice meets the minimum code requirement and is documented.