- Lockout/tagout verification
- Before servicing an air handler or VFD, isolate all energy sources, apply locks and tags, and confirm zero voltage at the disconnect with a tested meter. Stored energy in capacitors and springs must be released.
- Fall protection threshold
- General industry requires fall protection at 6 feet (1.8 m); construction and shipyard work at 4 feet (1.2 m). Duct installation above walking surfaces triggers the requirement for guardrails, harnesses, or nets.
- Ladder setup angle
- Use a 4:1 ratio: one foot of horizontal distance for every four feet of working height. Extend the ladder three feet above the landing and secure the top before climbing.
- Confined space atmospheric testing
- Test for oxygen (19.5–23.5%), flammable gas (below 10% LEL), carbon monoxide, and hydrogen sulfide before entry. A standby attendant remains outside and maintains communication with entrants.
- Sensible heat equation
- Qs = 1.08 × CFM × ΔT in English units at sea level. For example, 1,000 CFM with a 20°F rise carries 21,600 Btu/h of sensible heat.
- Latent heat equation
- QL = 0.68 × CFM × ΔW, where ΔW is the moisture difference in grains per pound. Total heat uses 4.5 × CFM × Δh with enthalpy in Btu/lb.
- Equal friction sizing method
- Size each duct section for a constant pressure drop per 100 feet, typically 0.08–0.10 in. w.c. This method is simple and self-balancing for many systems.
- Static regain method
- Size duct so that velocity pressure recovered at each branch offsets friction loss, keeping static pressure nearly constant. It requires larger downstream duct but lowers fan energy.
- Duct velocity limits
- Main trunks near occupied space: 1,200–1,500 fpm. Branch runs: 600–900 fpm. Diffuser necks: 300–500 fpm. Higher velocities raise noise and friction loss.
- Duct leakage class
- SMACNA classes range from 3% to 30% of design airflow depending on pressure class and seal class. Lower leakage class numbers indicate tighter, better-sealed duct systems.
- Galvanized coating designations
- G90 means 0.90 oz of zinc per square foot of steel. G90 is standard HVAC; G60 suits dry indoor use; G210 is used in coastal or industrial corrosive environments.
- SMACNA pressure classes
- Pressure classes include 0.5, 1, 2, 3, 4, 6, and 10 in. w.c. Gauge, reinforcement, and hanger spacing are selected from tables based on the class and duct size.
- Flexible duct installation limits
- Keep flex runs as short as possible, fully extended, with sag no more than 0.5 in./ft. Support every 4–5 ft with saddle hangers; compressed or sagging flex sharply increases pressure loss.
- UL 181 closure systems
- UL 181A covers rigid duct closures; UL 181B covers flexible duct and duct board. Tape and mastic must be listed for the specific duct material and application.
- Duct board shiplap closure
- Fiberglass duct board joints use a 2-inch shiplap with pressure-sensitive tape and mastic. The closure system must be UL 181 listed for the board and application.
- Hanger spacing rules
- Rectangular duct: 8 ft maximum spacing. Round duct: 10 ft maximum. Place a hanger within 2 ft of each joint or fitting to prevent sag and joint separation.
- Radiused elbow ratio
- Use elbows with centerline radius at least 1.5 times the duct diameter (R/D ≥ 1.5) to minimize pressure loss. Square throated elbows require turning vanes.
- Branch takeoff angle
- A 45° branch entry has lower pressure loss than a 90° straight tap. Install a volume damper in each branch for balancing and lock it after adjustment.
- Fire damper access
- Fire dampers installed in rated walls or floors require an accessible inspection door. They must be inspected and tested after installation and periodically per NFPA 80.
- Smoke damper requirements
- Smoke dampers are installed where ducts cross smoke barriers and must be accessible for testing. NFPA 105 governs their installation and periodic testing.
- Diffuser throw
- Throw is the distance from the diffuser to where air velocity drops to 50 fpm. Space diffusers at roughly 1.0–1.5 throw for uniform mixing without drafts.
- NC noise criteria targets
- NC 25–30 suits residential spaces, NC 35–40 offices, and NC 45 industrial areas. Higher neck velocity and turbulent fittings raise the NC level.
- Proportional balancing method
- Set total fan airflow first, then adjust branch dampers starting from the farthest terminal. This method divides airflow proportionally and reduces repeated re-adjustment.
- Flow hood accuracy
- A calibrated flow hood reads terminal airflow within roughly ±3–5%. Calibration should be verified annually and the hood zeroed before each balancing session.
- Opposed vs parallel dampers
- Opposed-blade dampers modulate airflow linearly and are used for control. Parallel-blade dampers are used for two-position or shutoff service because they concentrate flow.
- Seal class A
- Seal class A covers all transverse joints, longitudinal seams, and duct penetrations. Class B covers joints and seams; class C covers transverse joints only.
- Vapor barrier placement
- Place the vapor barrier on the warm side of the insulation. In cooling climates that is the exterior; a torn or compressed barrier causes condensation and mold.
- Duct insulation R-values
- R-6 for ducts in conditioned space, R-8 for unconditioned attics, and R-13 for exterior runs are common targets. Insulation must stay continuous through hangers.
- Pitot tube traverse
- Take velocity pressure readings at multiple points across two perpendicular diameters. Average the readings, then V = 4005 × √VP to obtain velocity in feet per minute.
- Fan affinity laws
- Airflow varies linearly with fan speed, static pressure with the square of speed, and horsepower with the cube. A 10% speed increase raises power about 33%.
- TAB sequence
- Verify fan rotation and airflow direction first, set total airflow at the fan, balance branches from the farthest, then adjust terminal devices. Record all final readings.
- SMACNA duct construction standard
- SMACNA HVAC Duct Construction Standards defines pressure classes, gauge tables, reinforcement, hanger spacing, and seal classes used to build and install duct systems.
- ASHRAE 62.1 ventilation
- ASHRAE 62.1 sets minimum outdoor air rates in cfm per person plus cfm per square foot. It also defines the ventilation rate procedure and indoor air quality procedure.
- NFPA 90A scope
- NFPA 90A governs air distribution in commercial buildings, covering duct materials, fire and smoke dampers, and clearance from combustible construction.
- IECC duct leakage limit
- The IECC limits duct leakage to about 4 cfm per 100 square feet of duct surface in many climate zones, with a higher allowance for tested systems.