Arc flash boundary
The distance from exposed live parts at which a person without arc-rated protection would receive second-degree burns, defined as an incident energy of 1.2 cal/cm².
Restricted approach boundary
An NFPA 70E boundary inside which only qualified persons using shock protection and insulated tools may reach, and crossing which requires an energized electrical work permit.
CAT III rating
A measurement category for test instruments used on distribution circuits such as panelboards and feeders; the instrument rating must meet or exceed the location category and voltage.
Live-dead-live test
A three-step verification of de-energization: test the instrument on a known live source, test the isolated conductors, then retest the known source to prove the meter still works.
Incident energy
The thermal energy impressed on a surface at a stated working distance during an electric arc, expressed in calories per square centimeter or joules per square centimeter.
Per-unit impedance
Actual impedance divided by base impedance, where base impedance equals base voltage squared divided by base apparent power; per-unit values are unchanged across a transformer.
Symmetrical components
A method that resolves an unbalanced three-phase set of phasors into balanced positive-, negative-, and zero-sequence sets so faults can be solved with single-phase networks.
Power factor correction
Adding shunt capacitors to supply reactive power locally; required capacitive kVAR equals real power times the difference between tangents of the original and target power-factor angles.
Wye connection relations
In a balanced wye, line current equals phase current and line-to-line voltage equals the square root of three times line-to-neutral voltage, with line voltage leading by 30 degrees.
X/R ratio
The ratio of reactance to resistance at the fault point, which determines DC offset and therefore the peak asymmetrical first-cycle current the equipment must withstand.
Subtractive polarity
The ANSI standard transformer polarity in which the H1 and X1 bushings are diagonally opposite; when H1 is instantaneously positive, X1 is also positive.
Percent impedance
The voltage, as a percentage of rated, that must be applied to the primary to circulate rated current with the secondary shorted; it fixes available fault current and regulation.
Turns ratio test
A field test that applies a known voltage to one transformer winding and measures the induced voltage on the other to verify nameplate ratio and polarity.
Buchholz relay
A gas-actuated device installed in the pipe between an oil-filled transformer tank and its conservator; it alarms on accumulated gas and trips on a sudden oil surge.
Close-and-latch rating
The maximum asymmetrical current a switchgear assembly can withstand while closing and holding closed, covering the first-cycle mechanical duty of a fault.
Synchronous speed
The speed of the rotating magnetic field, equal to 120 times frequency divided by the number of poles; at 60 Hz with four poles it is 1800 rpm.
Polarization index
The ratio of insulation resistance at ten minutes to that at one minute; a value below 2.0 suggests moisture, contamination, or degradation in the winding insulation.
NEMA Design B motor
The general-purpose AC induction motor design with normal starting torque and locked-rotor current typically five to seven times full-load current; the most common industrial motor.
Inverter duty motor
A motor whose insulation and bearings are designed to withstand the fast voltage pulses and high rate of voltage rise produced by pulse-width-modulated variable-frequency drives.
Motor overload relay
A device that models winding heating with an inverse-time current-squared characteristic and trips at a level set from the motor nameplate full-load amperes.
Device 87
The ANSI device number for differential protection, which compares currents entering and leaving a protected zone and trips when the difference exceeds a restraint-based threshold.
Harmonic restraint
A differential relay feature that blocks tripping when second-harmonic content in the measured current indicates magnetizing inrush rather than an internal fault.
Secondary injection test
A relay test in which precise currents and voltages are injected at the relay terminals to verify pickup, timing, and logic without energizing primary equipment.
Live zero 4-20 mA
An analog signal convention in which 4 mA represents the minimum value and 20 mA the maximum, so a broken wire reads 0 mA and is distinguishable from a valid low reading.
Very low frequency test
A cable withstand test applying 0.1 Hz AC, preferred over DC hi-potential testing for shielded XLPE cable because it limits trapped space charge and insulation damage.
Fall-of-potential test
A three-point ground resistance measurement with the potential probe at 62 percent of the distance to the current probe; flat readings at 52 and 72 percent confirm validity.
Wenner four-pin method
A soil resistivity test using four equally spaced pins in a straight line, where resistivity in ohm-meters equals two pi times the pin spacing times the measured resistance.
Time domain reflectometry
A cable fault-location method that launches a pulse and measures the round-trip echo time, giving distance as half the product of propagation velocity and elapsed time.
As-found test data
Measurements recorded before any adjustment or repair of the equipment; they establish baseline condition and are compared against acceptance criteria in the test report.
Factory acceptance test
A structured test program performed at the manufacturer's facility before shipment to demonstrate that equipment meets specification and contract requirements.
Point-to-point check
A continuity verification that each field conductor is landed on the terminal shown on the drawings, performed before energization to prevent misoperation or equipment damage.
Baseline thermographic survey
An infrared scan of energized equipment under load that records normal temperature patterns for later comparison, typically requiring at least 40 percent of rated load.