The NICET Electrical Power Testing (EPT) certification is a professional credential for technicians who test, inspect, and commission electrical power systems and the equipment that supports them. NICET offers EPT exams at three levels - I, II, and III - so a person can enter the program early in a field career and progress to senior responsibility as experience and judgement grow. The NICET EPT study guide has 7 sections and about 2,265 words.

01

Electrical Safety, Codes, and Standards

NFPA 70 (the NEC) governs how equipment is installed ; NFPA 70E governs how people work on it safely . A frequent trap is a stem describing an installation requirement that offers a 70E article as the answer, or vice versa.

322 words, about 2 min
02

Power System Fundamentals and Circuit Analysis

The single most valuable set of formulas: S = √3 × V LL × I L for three-phase, and S = V × I for single-phase, with P = S × power factor. Impedance base conversions follow Z base = V LL² / S and I base = S / (√3 × V LL).

344 words, about 2 min
03

Transformers, Switchgear, and Distribution Equipment

Know the turns ratio (V₁/V₂ = N₁/N₂), the difference between additive and subtractive polarity, and cooling class designations: ONAN, ONAF, OFAF. Nameplate kVA is based on a stated temperature rise and ambient; forcing more cooling raises usable capacity.

289 words, about 1 min
04

Rotating Machinery and Motor Controls

Synchronous speed = 120 × f / P. A 4-pole machine at 60 Hz runs at 1800 rpm synchronous and, at 2% slip, about 1764 rpm at full load.

322 words, about 2 min
05

Protective Relaying, Instrumentation, and Control

IEEE C37.2 numbers appear constantly: 50 (instantaneous overcurrent), 51 (AC time overcurrent), 87 (differential), 27/59 (under/overvoltage), 81 (frequency), 49 (thermal), 86 (lockout), 25 (synch check), 64 (ground fault). Differential protection (87T, 87B, 87G) compares currents entering and leaving a zone and is inherently selective; it does not provide backup for downstream faults.

323 words, about 2 min
06

Cables, Grounding, and Insulation Systems

Conductor ampacity starts with the Table 310.16 value at the reference ambient and is then corrected for ambient temperature and adjusted for the number of current-carrying conductors in a raceway. Continuous loads are sized at 125% of load.

337 words, about 2 min
07

Field Testing, Commissioning, and Documentation

Acceptance testing proves a new installation is sound before energization; maintenance testing establishes condition over time. NETA ATS covers acceptance, NETA MTS covers maintenance.

328 words, about 2 min