NICET EPT key terms
NICET EPT · Get comfortable with the vocabulary.
- Arc flash boundary
- Related: Incident energy, PPE arc rating
The distance from energized equipment at which an arc flash could cause second-degree burns to unprotected skin; it sets where barricades go and what protective clothing is required.
- Incident energy
- Related: Arc flash boundary, PPE arc rating
The thermal energy per unit area deposited on a surface during an arc flash, usually stated in calories per square centimeter; it determines the arc rating of clothing workers must wear.
- Limited approach boundary
- Related: Arc flash boundary
A shock-protection boundary around exposed energized parts that unqualified people may not cross; only qualified workers using proper protective equipment and a plan may enter.
- Lockout/tagout
- Related: Arc flash boundary
A formal procedure for isolating energy sources, attaching locks and tags, and confirming zero energy before work starts, preventing unexpected energization or release of stored energy.
- PPE arc rating
- Related: Incident energy, Arc flash boundary
The arc thermal performance value of protective clothing: the incident energy at which there is a 50 percent chance of second-degree burn through the fabric.
- Ohm's law
- Related: Kirchhoff's voltage law
The relationship stating that voltage equals current times resistance in a resistive circuit, so any one of the three quantities can be calculated when the other two are known.
- Kirchhoff's current law
- Related: Kirchhoff's voltage law
The principle that total current entering a junction equals total current leaving it, since charge cannot pile up at a node; it is the basis for nodal circuit analysis.
- Kirchhoff's voltage law
- Related: Kirchhoff's current law, Ohm's law
The principle that the algebraic sum of all voltage rises and drops around any closed loop is zero, reflecting conservation of energy in a circuit.
- Power factor
- Related: Symmetrical components
The ratio of real power in watts to apparent power in volt-amperes in an AC circuit, equal to the cosine of the angle between voltage and current.
- Symmetrical components
- Related: Protective relay
A method that resolves an unbalanced three-phase set of voltages or currents into three balanced sets called positive, negative, and zero sequence, used for fault and relay studies.
- Transformer turns ratio
- Related: Transformer polarity, Percent impedance
The ratio of primary winding turns to secondary winding turns, which determines the ratio of primary to secondary voltage and the inverse ratio of currents.
- Percent impedance
- Related: Transformer turns ratio
The percentage of rated voltage that must be applied to one winding to circulate rated current through the other winding short-circuited; it limits available short-circuit current.
- Transformer polarity
- Related: Vector group, Transformer turns ratio
The instantaneous voltage direction relationship between primary and secondary windings, marked additive or subtractive, which must be known to parallel transformers or build three-phase banks.
- Vector group
- Related: Transformer polarity, Transformer turns ratio
A code such as Dyn11 that describes a three-phase transformer's winding connections and the phase angle displacement between high-voltage and low-voltage windings, needed for paralleling.
- Tap changer
- Related: Transformer turns ratio
A mechanism that changes the number of active turns in a transformer winding to adjust its voltage ratio, either with the unit de-energized or under load.
- Metal-clad switchgear
A medium-voltage assembly with drawout circuit breakers in separate grounded metal compartments, automatic shutters, and interlocks, built for safe operation and easy breaker removal.
- Variable frequency drive (VFD)
- Related: Motor control center, Overload relay
An electronic controller that changes the frequency and voltage fed to an AC motor, adjusting speed and torque while reducing starting current and energy use.
- Locked rotor current
- Related: Overload relay
The current an induction motor draws at rated voltage when its shaft is stalled, typically five to eight times full-load current; it is used for protection and voltage-drop studies.
- Overload relay
- Related: Locked rotor current, Motor control center
A protective device that senses sustained motor overcurrent, usually thermally or electronically, and opens the control circuit before the motor winding insulation is damaged.
- Motor control center
- Related: Overload relay, Variable frequency drive (VFD)
A sectionalized lineup of motor starters, feeders, and protective devices connected to a common bus, used to control and protect many motors from one location.
- Phase rotation
The order in which the three phase voltages reach their positive peaks; an incorrect sequence reverses a motor's direction, so it must be checked before connecting equipment.
- Current transformer
- Related: Burden, Protective relay
An instrument transformer that reduces line current to a standard secondary value, usually 5 A or 1 A, while isolating meters and relays from the high-voltage circuit.
- Potential transformer
- Related: Burden, Current transformer
An instrument transformer that steps high voltage down to a safe, standardized value for meters and relays while preserving an accurate voltage ratio and phase relationship.
- Burden
- Related: Current transformer, Potential transformer
The total load in volt-amperes and impedance connected to an instrument transformer secondary; exceeding the rated burden causes ratio and phase-angle errors.
- Protective relay
- Related: Current transformer, Time-current curve, Differential protection
A device that monitors current, voltage, or other quantities and trips a circuit breaker when conditions exceed settings, isolating faults to limit damage and outage scope.
- Time-current curve
- Related: Protective relay, Overload relay
A graph of operating time versus current for a protective device, used to coordinate relays and fuses so the device nearest a fault trips first.
- Differential protection
- Related: Protective relay, Current transformer
A scheme that compares currents entering and leaving a protected zone and trips when they differ, detecting internal faults while ignoring load and through-fault current.
- Insulation resistance test
- Related: Polarization index, Megohmmeter
A DC test using a megohmmeter to measure insulation resistance, revealing moisture, contamination, or deterioration; results are corrected to a standard temperature for comparison over time.
- Polarization index
- Related: Insulation resistance test, Megohmmeter
The ratio of insulation resistance measured at ten minutes to the value at one minute; a result below about 2.0 suggests moisture or contamination in the insulation.
- Megohmmeter
- Related: Insulation resistance test, Polarization index
An instrument that applies a selected DC voltage, often 250 to 5000 volts, and measures insulation resistance in megohms or higher for cables, motors, and transformers.
- Grounding electrode
- Related: Equipment grounding conductor
A conductive element such as a rod, plate, or building steel in direct contact with earth, providing a low-impedance path to ground for fault and lightning current.
- Equipment grounding conductor
- Related: Grounding electrode, Touch potential
The conductor connecting the metal frames of equipment to the grounding system, giving fault current a low-impedance return path so overcurrent devices open quickly.
- Touch potential
- Related: Step potential, Equipment grounding conductor
The voltage difference between a grounded metal structure a person can touch and the earth underfoot during a ground fault; high values endanger people near substations.
- Step potential
- Related: Touch potential
The voltage difference between two points on the earth's surface about one step apart, caused by fault current spreading through soil; it can shock a person walking nearby.
- Partial discharge
- Related: Insulation resistance test, Hi-potential test
Small localized electrical discharges inside insulation voids or along surfaces, measured to find incipient defects before breakdown; detected with electrical, acoustic, or ultrasonic sensors.
- Commissioning
- Related: Factory acceptance test, Punch list
A systematic process that verifies installed systems meet design intent and owner requirements, covering pre-functional checks, functional performance tests, and final documentation.
- Factory acceptance test
- Related: Commissioning, Punch list
Testing of equipment at the manufacturer's plant before shipment to confirm it meets specifications, often witnessed by the owner so defects can be fixed off-site.
- Punch list
- Related: Commissioning
A documented list of incomplete work or deficiencies found during inspection and commissioning that the contractor must correct before final acceptance and project closeout.
- Hi-potential test
- Related: Insulation resistance test, Partial discharge
A field test that applies a high voltage above rated to insulation to prove dielectric strength; AC or DC, it can damage aged insulation if voltage is too high.
- Calibration
- Related: Commissioning
The comparison of an instrument's reading with a known reference standard and adjustment to reduce error, documented with records traceable to national standards.