NITC Master Plumber flashcards
NITC Master Plumber · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Fixture unit (FU)
- A dimensionless measure that converts dissimilar fixtures into a common load value for sizing drainage and water supply; one fixture unit equals roughly 1 gpm of demand.
- Developed length
- The total measured length of pipe along its centerline including all horizontal and vertical runs; fitting equivalents are added as a percentage during preliminary sizing.
- Hunter's curve
- A probability-based relationship between total fixture units and probable peak water demand; it accounts for non-coincident fixture use so peak flow is far below the arithmetic sum.
- Static pressure gain
- The pressure increase from elevation drop, equal to 0.433 psi per foot of fall (1 psi per 2.31 ft); used to check pressure at lower floors in tall buildings.
- Thermal expansion tank
- A device installed on closed domestic water systems downstream of a backflow preventer to absorb the volume increase as heated water expands, preventing relief valve discharge and pipe stress.
- Copper tube type selection
- Type K is used underground and for service lines, Type L for typical domestic distribution, and Type M only where code permits above-ground use; wall thickness decreases from K to M.
- Trap arm length limit
- The maximum developed length from the trap weir to the vent fitting, which varies with pipe size (for example 6 ft for 1-1/2 in pipe); exceeding it causes self-siphonage.
- Backwater valve
- A one-way device installed on drainage serving fixtures below the upstream manhole cover elevation to prevent sewage from reversing into the building during a surcharge.
- Air admittance valve
- A one-way vent that admits air into the drainage system when negative pressure develops and seals closed otherwise; it must be listed to ASSE 1050 or 1051 and located per code.
- Vent stack sizing
- Vent diameter is chosen from the total fixture units served; for example a 2 in vent serves up to 24 fixture units and a 3 in vent up to 84 under typical code tables.
- Roof drain flow formula
- Storm flow in gallons per minute equals roof area in square feet times rainfall intensity in inches per hour times 0.0104; intensity is taken from local 100-year, one-hour data.
- Secondary roof drainage
- A backup system of scuppers or additional drains that carries the design storm if primary roof drains become blocked; required by most codes for commercial roofs.
- Grease interceptor sizing
- Capacity is set by fixture units or flow rate and retention time, typically two hours for restaurant waste; it separates fats, oils, and grease before discharge to the sanitary sewer.
- Air gap
- The unobstructed vertical distance between a potable water outlet and the flood-level rim of a receptor; minimum is 1 in or twice the effective opening, whichever is greater.
- Flood-level rim
- The edge of a fixture at which water overflows onto the floor; it is the reference point for measuring air gaps and backflow protection critical levels.
- Water closet spacing
- Minimum 15 in from the centerline of a water closet to a side wall or partition and 30 in clear width in front; these dimensions come from accessible fixture clearance requirements.
- Trap seal depth
- The vertical distance between the trap weir and the dip of the trap, normally 2 to 4 in; too shallow risks evaporation and sewer gas, too deep risks slow drainage.
- First-hour rating
- The volume of hot water a storage water heater can deliver in one hour starting from a fully heated tank; it combines tank capacity with recovery rate and must meet peak-hour demand.
- Recovery rate formula
- Gallons per hour recovered equals input BTU/hr times efficiency divided by 8.33 times the temperature rise; it expresses how fast a heater reheats water.
- T&P relief valve
- A temperature and pressure relief valve set typically at 210 F and 150 psi that discharges full-size by gravity to a safe receptor with an air gap and no traps or reducers.
- Combustion air requirement
- Confined spaces need 50 cubic feet of air per 1,000 BTU/hr of input, supplied through two openings, one near the top and one near the bottom of the enclosure.
- Rough-in inspection
- The inspection performed after piping is installed but before it is concealed by walls, ceilings, or slabs; the system must pass a pressure or water test first.
- Authority having jurisdiction
- The official or agency that enforces the plumbing code, issues permits, conducts inspections, and approves variances or alternate materials in a given jurisdiction.
- Model code adoption
- A model code such as the IPC or UPC becomes enforceable law only when a jurisdiction formally adopts it, often with local amendments that change specific requirements.
- Reduced pressure zone assembly
- A testable backflow preventer with two check valves and a relief valve that protects against both backpressure and backsiphonage; used for health-hazard connections.
- Pressure vacuum breaker
- A testable assembly that protects against backsiphonage only; it must be installed at least 12 in above the highest downstream outlet and cannot be used where backpressure exists.
- Double check valve assembly
- A testable backflow preventer with two check valves that protects against backpressure and backsiphonage for non-health hazards only; not approved for toxic or health-hazard connections.
- DWV water test
- A test in which the drainage system is filled with water to a 10 ft head above the highest point and held at least 15 minutes before inspection to reveal leaks.
- Smoke test
- A test that introduces smoke into the drainage system to locate leaks and improper connections; escaping smoke reveals open joints or missing vent connections.
- Trap seal loss causes
- Evaporation, capillary action, wind effect, momentum, and backpressure each can break a trap seal; diagnosis identifies which cause applies before selecting a remedy.
- Trench protective system
- A shoring, shielding, or sloping system required for excavations 5 ft deep or more; spoil piles must be kept at least 2 ft back from the trench edge.
- Labor unit estimating
- A method that multiplies installed quantity by a published labor unit in hours per unit, then applies a productivity factor for site conditions to estimate total labor hours.