- Ohm's law
- Current equals voltage divided by resistance (I = E/R). Rearranged, E = I × R and R = E/I. Used to solve branch currents, voltage drops, and resistor values in circuit analysis.
- Three-phase power formula
- For a balanced three-phase load, P = √3 × E(line) × I(line) × power factor. Line voltage and line current are used regardless of wye or delta connection.
- Voltage drop formula
- Single-phase VD = 2 × K × I × L / CM. K is approximately 12.9 for copper and 21.2 for aluminum; L is one-way length in feet and CM is circular mils.
- Box fill calculation
- Count conductors, devices, and grounding conductors per NEC Table 314.16(B). Each device yoke counts as two conductors; compare total volume to the box's listed cubic-inch capacity.
- Dwelling general lighting load
- NEC Table 220.12 requires 3 VA per square foot for dwelling general lighting. Small-appliance and laundry branch circuits each add 1,500 VA before demand factors apply.
- Motor overload protection
- NEC 430.32 sizes overload protection based on motor nameplate current, while branch-circuit short-circuit protection uses Table 430.52 and conductors use 125% of Table 430.250 FLC.
- Termination temperature limitation
- NEC 110.14(C) limits conductor ampacity to the temperature rating of terminations. Conductors rated 90°C may be derated but final ampacity is capped by the termination rating.
- Demand factor
- A ratio applied to connected load to reduce the calculated load based on expected diversity. NEC Table 220.42 provides demand factors for dwelling lighting and appliance loads.
- New Jersey Uniform Construction Code
- N.J.A.C. 5:23 adopts the NEC as the electrical subcode. Enforcement is by the local construction official and electrical subcode official, not the licensing board.
- Authority having jurisdiction
- The organization or individual responsible for approving equipment and enforcement. In New Jersey this is the municipal or county construction office administering the UCC.
- NEC Article 90 scope
- Article 90 states the Code's purpose and scope and grants the AHJ interpretive authority under 90.4. Informational notes in the Code are explanatory and not enforceable requirements.
- GFCI requirements
- NEC 210.8 requires ground-fault circuit-interrupter protection for dwelling bathroom, kitchen, laundry, garage, outdoor, and unfinished-basement receptacles, plus other specified locations.
- AFCI requirements
- NEC 210.12 requires arc-fault circuit-interrupter protection for most 120-volt branch circuits in dwelling units, including bedrooms, living areas, and similar rooms.
- Grounding electrode conductor sizing
- NEC Table 250.66 sizes the grounding electrode conductor based on the largest service-entrance conductor. Equipment grounding conductors are sized per Table 250.122 using the overcurrent device rating.
- Conductor ampacity table
- NEC Table 310.16 lists allowable ampacities for not more than three current-carrying conductors at 30°C ambient. Ambient correction and conductor adjustment apply before final sizing.
- Raceway fill tables
- NEC Chapter 9 Table 1 limits conduit fill to 53% for one conductor, 31% for two, and 40% for three or more. Annex C gives precalculated fill for common conductor types.
- NM-B cable restrictions
- Nonmetallic-sheathed cable is permitted in dwellings but prohibited in wet locations, masonry block, and where subject to physical damage. It must be secured within 12 inches of boxes.
- EMT support spacing
- Electrical metallic tubing must be supported within 3 feet of each box and at intervals not exceeding 10 feet, per NEC 358.30, unless listed supports allow otherwise.
- Working clearance
- NEC 110.26 requires a working space 30 inches wide, 36 inches deep, and 6 feet 6 inches high in front of electrical equipment, increasing with higher voltages.
- Receptacle spacing rule
- In dwelling units, no point along the floor line may be more than 6 feet from a receptacle. Kitchen counter receptacles must be spaced so no point exceeds 24 inches.
- Splice accessibility
- Splices and joints must be made in listed boxes or fittings and must remain accessible. Junction boxes may not be buried in walls or ceilings without access.
- Bonding metal water piping
- NEC 250.104 requires bonding of metal water piping systems. A bonding jumper must bypass water meters and insulating joints to ensure a continuous path.
- Construction site GFCI
- NEC 590.6 requires GFCI protection for temporary receptacles and portable tools on construction sites, or an assured equipment grounding conductor program with recorded tests.
- MC cable support
- Metal-clad cable must be supported every 6 feet and within 12 inches of boxes. In wet locations, the jacket and fittings must be corrosion-resistant and listed for the location.
- PVC conduit support
- Rigid PVC conduit Schedule 40 must be supported at intervals not exceeding 3 feet, per NEC 352.30, with closer spacing where the conduit is exposed to temperature change.
- Electrical Contractors Licensing Act
- N.J.S.A. 45:5A, the Electrical Contractors Licensing Act of 1962, created the Board of Examiners of Electrical Contractors and requires licensure to perform electrical contracting.
- Electrical Contractor license
- Only a licensed Electrical Contractor may bid, contract, or advertise electrical work in New Jersey. The business must have a qualified licensee responsible for supervision.
- Qualified Journeyman license
- A journeyman license allows the holder to perform electrical work under the supervision of a licensed electrical contractor. Applicants must meet Board experience and exam requirements.
- Board disciplinary authority
- The Board may refuse, suspend, or revoke a license for fraud, gross negligence, incompetence, or violations of the Act, and may impose civil penalties.
- Apprentice registration
- Apprentices must be registered with the Board and work under direct supervision. Documented apprentice hours count toward the experience required for journeyman licensure.
- License renewal and CE
- New Jersey electrical licenses require periodic renewal and continuing education as set by the Board. Lapsed licenses may not be used until reinstated under Board rules.
- Unlicensed contracting penalty
- Performing electrical contracting without a license violates N.J.S.A. 45:5A and subjects the offender to civil penalties and possible injunctive action by the Board.