OH HVAC Contractor study materials
OH HVAC Contractor study resources

OH HVAC Contractor: HVAC and Refrigeration Trade Competency

OH HVAC Contractor · Work through your exam, one topic at a time.

All guide sections

HVAC and Refrigeration Trade Competency

What the exam tests

The HVAC and refrigeration portion of the Ohio contractor exam tests whether you can apply trade theory to field decisions: building heat gain/loss, equipment and duct selection, refrigerant-cycle diagnosis, combustion and venting, controls, and safe recovery/evacuation. Questions often give a field scenario and ask for the next diagnostic step or the calculation that supports a recommendation.

Core rules and concepts

  • Sensible heat in air is approximated by Qs = 1.08 × cfm × ΔT; total heat adds latent load, so do not use the sensible formula for a wet coil.
  • The refrigeration cycle moves heat from evaporator to condenser. Superheat is measured at the evaporator outlet; subcooling at the condenser outlet. Target values come from the equipment manufacturer, not a universal number.
  • Airflow is a prerequisite for charging. A dirty filter, restricted coil, or wrong blower speed can mimic a refrigerant problem.
  • Duct sizing uses available static pressure and friction loss; manual dampers and balancing are part of commissioning.
  • Refrigerant handling requires recovery, nitrogen purge while brazing, and evacuation measured in microns. Never use refrigerant to purge or leak-test.
  • Combustion appliances need adequate combustion air and proper venting; check draft and CO after service.

Worked example

A 400-cfm air handler has 75°F return air and 55°F supply air. Sensible capacity is 1.08 × 400 × (75−55) = 8,640 Btu/h. If the measured capacity is far below the equipment rating, first verify airflow and temperature measurement locations. The formula does not include latent capacity, so a wet coil can have a higher total capacity than the sensible result.

Traps

Charging by gauge pressure alone; assuming a 20°F ΔT is always correct; adjusting refrigerant before checking airflow; ignoring superheat/subcooling targets; and treating a vacuum decay test as optional.