OK General Contractor: Thermal, Moisture, and Openings

OK General Contractor · Work through your exam, one topic at a time.

All guide sections

Thermal, Moisture, and Openings

What is tested

Thermal, moisture, and openings tests envelope performance: insulation, air and vapor control, flashing, roofing, waterproofing, windows, doors, and glazing.

Core rules

  • R-value is thermal resistance; U-factor is thermal transmittance; U = 1 ÷ total R. Add resistances in series, including surface films.
  • Control layers: water, air, vapor, and thermal. The vapor retarder goes on the warm side in cold climates; in mixed climates, use a material or placement that allows drying.
  • Flashings manage water at roofs, walls, windows, and penetrations. Window pan flashing, sill seal, and back dams are common exam points.
  • Openings: check fire rating, egress size, safety glazing, and weather seal. Store windows upright and protect them.
  • Roofing: slope, underlayment, drip edge, and counterflashing matter more than surface appearance.

Worked example

A wall has R-13 cavity insulation, R-5 continuous insulation, and R-0.68 interior plus R-0.17 exterior surface films. Total R = 13 + 5 + 0.68 + 0.17 = 18.85. U = 1 ÷ 18.85 = 0.053 Btu/(h·ft²·°F). Reasoning: thermal resistances add; U is the reciprocal of total R.

Traps

Putting a vapor retarder on both sides; treating caulk as flashing; ignoring pan flashing at windows; mixing R and U; forgetting thermal bridging of framing.