LEW · Keep the key ideas within reach.

Quick reference

Electrical Fundamentals and Circuit Theory

  • Ohm's law: V = I × R; power P = V × I = I²R = V²/R. In AC, use RMS values for these relations.

  • Series circuit: same current everywhere, resistances add, voltages divide in proportion to resistance. Parallel: same voltage, conductances add, currents divide inversely with resistance.

  • Three-phase power: P = √3 × V_LL × I × PF for balanced loads; single-phase P = V × I × PF. Reactive power Q = √3 × V_LL × I × sin θ.

  • Impedance Z = R + jX; |Z| = √(R² + X²), phase angle θ = arctan(X/R). Inductive reactance X_L = 2πfL; capacitive X_C = 1/(2πfC).

  • Resonance occurs where X_L = X_C, giving f_r = 1/(2π√(LC)); impedance is minimum (series) or maximum (parallel) at resonance.

  • Wye (star) connection: V_line = √3 × V_phase, I_line = I_phase. Delta: V_line = V_phase, I_line = √3 × I_phase.

  • Per-unit method: divide actual quantities by base values; base impedance Z_base = V_base² / S_base. Per-unit simplifies multi-voltage transformer networks.

  • Kirchhoff's laws: KCL - sum of currents at a node equals zero; KVL - sum of voltages around a closed loop equals zero. Use superposition or Thevenin for linear networks.

Quick reference

Wiring Methods, Materials, and Installation Practices

  • Conductor ampacity depends on insulation temperature rating, ambient temperature correction, and conduit fill adjustment (NEC Table 310.15 series).

  • Conduit fill limits: 1 conductor 53%, 2 conductors 31%, 3 or more 40% of interior cross-sectional area (NEC Chapter 9).

  • Box fill is calculated from conductor volume allowances plus devices, clamps, and grounds; see NEC Table 314.16(B) for cubic-inch allowances per conductor size.

  • Bending radius: for cable, not less than 5× diameter for ≤1 in and 10× for larger; conduit bends typically 6× trade diameter for one-shot and 4× for field bends (verify with NEC 344/352).

  • Support intervals: rigid metal conduit every 10 ft and within 3 ft of boxes; EMT every 10 ft and within 3 ft; cable types per NEC 334.30 (typically 4.5 ft).

  • Conductor color code (NEC 310.110): grounded conductor white/gray, equipment grounding conductor green or green with yellow stripe, ungrounded typically black/red/blue.

  • Expansion fittings are required where raceway crosses building expansion joints or where thermal expansion exceeds design limits; PVC needs expansion fittings per temperature change.

  • Wet locations require conductors and fittings listed for wet use; NM cable is prohibited in wet locations and in most commercial occupancies per NEC 334.12.

Quick reference

Overcurrent Protection, Grounding, and Bonding

  • Standard OCPD sizes (NEC 240.6): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A, etc.

  • Next-size-up rule (NEC 240.4(B)) applies only when the ampacity does not correspond to a standard size, the next size does not exceed 800 A, and the load does not exceed the conductor ampacity.

  • Ground-fault protection for equipment (GFPE) at 1,000 A or more, 480Y/277 V services is required per NEC 230.95; trip threshold typically 1,200 A maximum with a delay.

  • Equipment grounding conductor sizing is based on the OCPD rating (NEC Table 250.122); it may need upsizing if conductors are increased for voltage drop.

  • Grounding electrode system: metal water pipe (10 ft contact), metal frame of building, concrete-encased electrode (20 ft of ½ in rebar or 4 AWG bare copper in 2 in concrete), ground ring, and rod/pipe electrodes.

  • Bonding jumpers around water meters, insulating joints, and flexible connections must maintain continuity; bonding to gas piping is prohibited except as allowed by NEC 250.104(B).

  • GFCI protects people (5 mA trip threshold typical); AFCI protects against parallel and series arcing; both have specific required locations per NEC 210.8 and 210.12.

  • Selective coordination requires time-current curves to overlap so downstream OCPDs trip first; study curves and settings for adjustable trip units.

Quick reference

Motors, Controls, and Utilization Equipment

  • Motor full-load current comes from NEC Tables 430.247–430.250 (by horsepower and voltage), not from nameplate current, for sizing branch-circuit conductors and overloads.

  • Branch-circuit short-circuit and ground-fault protection (NEC Table 430.52): inverse-time breaker typically 250% of FLC; dual-element fuse 175%; non-time-delay fuse 300%.

  • Overload protection is sized to nameplate current: typically 125% for continuous-duty motors with service factor ≤1.15, or 115% with higher service factor (NEC 430.32).

  • Motor disconnecting means must be within sight of the controller and motor, or capable of being locked open (NEC 430.102).

  • NEMA starter sizes correlate with horsepower at 460 V: Size 0 ≈ 5 hp, Size 1 ≈ 10 hp, Size 2 ≈ 25 hp, Size 3 ≈ 50 hp; verify with the manufacturer's table.

  • Across-the-line starting draws 6–8× FLC; reduced-voltage, wye-delta, soft-start, and VFD methods reduce inrush. VFDs require shielded cable and proper grounding to control EMI.

  • Control circuits are typically 120 V AC or 24 V DC; a holding contact (seal-in) maintains the coil circuit after the start pushbutton is released.

  • Motor rotation reversal: swap any two of the three supply leads for a three-phase motor; for a single-phase motor, reverse the start winding leads.

Quick reference

Transformers, Distribution, and Power Quality

  • Transformer turns ratio: V_primary/V_secondary = N_primary/N_secondary; current ratio is inverse; apparent power is conserved (ignoring losses).

  • Delta-wye transformers provide a neutral and a 30° phase shift; paralleling transformers requires matched voltage ratio, polarity, impedance, and phase sequence.

  • Transformer protection: primary OCPD typically 125% of primary FLA for continuous rating (NEC 450.3); secondary protection may be required when the primary device exceeds certain thresholds.

  • Voltage drop approximation: VD = (2 × K × I × L) / CM for single-phase; use √3 factor for three-phase. K ≈ 12.9 for copper, 21.2 for aluminum (ohm-cmil/ft).

  • Power factor correction capacitors reduce reactive current; place them at the load to avoid leading power factor and overvoltage during light load.

  • Harmonics from VFDs and switching supplies cause neutral overheating (triplen harmonics add in the neutral) and transformer derating; use K-rated transformers.

  • Short-circuit calculation: use transformer impedance (%Z) with base kVA to find fault current; I_sc ≈ (kVA × 1000) / (√3 × V × %Z/100).

  • Voltage unbalance causes motor heating; NEMA derates motors when voltage unbalance exceeds 1%; 3.5% unbalance can cause ~25% temperature rise.

Quick reference

Electrical Safety, Codes, and Standards

  • NFPA 70E establishes arc-flash and shock protection boundaries: limited approach, restricted approach, and arc-flash boundary, based on voltage and incident energy.

  • Arc-flash incident energy is expressed in cal/cm²; PPE categories (or arc ratings) are selected to exceed the calculated incident energy at the working distance.

  • Approach boundaries: for 480 V, the limited approach boundary is typically 10 ft for movable conductors and 3 ft 6 in for fixed; restricted approach is 1 ft (verify with current tables).

  • Lockout/tagout requires an energy-isolating device, verification of de-energization, and application of locks by each worker; test-before-touch confirms absence of voltage.

  • NEC Article 90 establishes that the Code is not a design manual or instruction manual; local amendments and the AHJ govern enforcement.

  • Classified locations are divided into Class I (gases/vapors), Class II (dust), and Class III (fibers/flyings); divisions or zones define the likelihood of hazard.

  • Temporary wiring, GFCI protection on construction sites, and assured equipment grounding conductor programs are required by OSHA 1926 Subpart K.

  • Standards hierarchy: NFPA 70 (installation), NFPA 70E (workplace safety), NFPA 70B (maintenance), UL standards (product listing), and NEMA (equipment ratings).

Quick reference

Testing, Inspection, and Troubleshooting

  • Insulation resistance testing uses a megohmmeter at a test voltage appropriate to the winding (500 V for 480 V equipment, 1,000 V for medium voltage); record values and temperature-correct them.

  • Continuity and low-resistance testing confirms bonding and equipment grounding paths; a reading above a few tenths of an ohm indicates a poor connection.

  • A clamp-on ammeter measures load current without breaking the circuit; a split-core or flexible Rogowski coil works for large conductors.

  • A multimeter's CAT rating (CAT III, CAT IV) must match the environment; CAT IV is required at service entrances and outdoor feeders.

  • Phase rotation meters verify ABC sequence before connecting motors; a reversed phase causes reverse rotation and potential damage.

  • Thermographic inspection finds loose connections and overloaded conductors; compare similar phases/loads and investigate temperature differences above ~10 °C.

  • Troubleshooting sequence: verify the symptom, isolate the circuit, test from the source toward the load, and confirm the repair with a functional test.

  • Ground-fault loop impedance and breaker trip-time testing verify OCPD performance; a breaker that trips below its rating may indicate a fault or a failing breaker.