32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Ohm's law
Voltage equals current times resistance (V = IR). In AC circuits, use RMS values and replace resistance with impedance magnitude for reactive loads.
Three-phase power formula
For a balanced three-phase load, real power equals √3 times line voltage times line current times power factor. Reactive power uses the sine of the angle.
Per-unit system
A method of normalizing voltages, currents, and impedances to base values so transformer ratios disappear and multi-voltage networks simplify. Base impedance is V²/S.
Series resonance
Occurs when inductive and capacitive reactances are equal; impedance is minimum and current is maximum. Resonant frequency is 1/(2π√(LC)).
Conduit fill limit
For three or more conductors, the total cross-sectional area may not exceed 40% of the conduit interior area. One conductor is limited to 53%, two to 31%.
Box fill calculation
Conductor volume allowances plus device, clamp, and ground allowances must not exceed the box's cubic-inch capacity. Allowances vary by conductor size.
Equipment grounding conductor color
The equipment grounding conductor is identified by green, green with yellow stripes, or bare copper. The grounded neutral is white or gray.
NM cable restrictions
Nonmetallic-sheathed cable is prohibited in wet locations, in most commercial occupancies, and where subject to physical damage unless protected.
Standard OCPD sizes
Common standard ratings include 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 200, 225, 250, 300, 350, and 400 amperes.
Next-size-up rule
A breaker may exceed conductor ampacity only if the ampacity is nonstandard, the next standard size does not exceed 800 A, and the load does not exceed ampacity.
Concrete-encased electrode
A grounding electrode consisting of at least 20 feet of ½-inch rebar or 4 AWG bare copper encased in at least 2 inches of concrete at the bottom of a footing.
GFCI trip threshold
A ground-fault circuit interrupter trips when it detects a current imbalance of about 5 milliamperes between the ungrounded and grounded conductors, protecting people from shock.
Motor FLC tables
Motor full-load current for sizing conductors and overloads comes from NEC tables based on horsepower and voltage, not the motor nameplate current.
Motor overload sizing
Overload protection is typically set at 125% of nameplate current for motors with a service factor of 1.15 or less, and 115% for higher service factors.
Seal-in contact
A holding contact wired in parallel with the start pushbutton keeps the motor starter coil energized after the button is released, maintaining the circuit.
Motor rotation reversal
For a three-phase motor, interchange any two supply leads. For a single-phase motor, reverse the leads of the start winding to change rotation.
Transformer turns ratio
The voltage ratio equals the turns ratio, while current ratio is inverse. Apparent power is approximately conserved, ignoring losses and magnetizing current.
Delta-wye transformer
A transformer connection providing a neutral and a 30-degree phase shift. It is common for distribution because it supplies both three-phase and single-phase loads.
Voltage drop formula
Single-phase voltage drop equals 2 × K × I × L divided by circular mils. Use √3 instead of 2 for three-phase circuits.
Triplen harmonics
Odd multiples of the third harmonic add in phase in the neutral of wye systems, causing neutral overheating and requiring oversized or separate neutrals.
Arc-flash boundary
The distance at which incident energy equals 1.2 cal/cm², the threshold for second-degree burn. Inside it, arc-rated PPE is required.
Limited approach boundary
A shock-protection boundary that unqualified persons may not cross. It depends on voltage and whether the exposed conductor is fixed or movable.
Lockout/tagout
A procedure that isolates energy sources, applies locks and tags by each worker, and verifies de-energization before work begins to prevent unexpected energization.
Classified locations
Areas with flammable gases, vapors, dust, or fibers. Class I covers gases, Class II dust, and Class III fibers; divisions or zones define hazard likelihood.
Insulation resistance test
A megohmmeter applies a DC voltage to measure insulation resistance. Values are temperature-corrected and trended; a decreasing trend indicates deterioration.
CAT ratings
Meter safety categories: CAT III for distribution circuits and CAT IV for service entrances. The rating must match or exceed the environment being measured.
Phase rotation meter
An instrument that verifies the ABC phase sequence of a three-phase supply before connecting a motor, preventing reverse rotation and equipment damage.
Thermographic inspection
Infrared imaging reveals loose connections and overloaded conductors by their elevated temperature. Compare similar phases and investigate significant temperature differences.
RMS value
The effective value of an AC waveform equal to the DC value producing the same heating. For a sine wave, RMS is peak divided by √2.
Wye versus delta
In a wye connection, line voltage is √3 times phase voltage. In a delta connection, line current is √3 times phase current.
Expansion fitting
A fitting installed in a raceway to absorb thermal expansion and contraction, required where raceways cross expansion joints or where temperature changes are significant.
Selective coordination
Coordination of overcurrent devices so that the device nearest a fault trips first, limiting outage scope. Time-current curves and adjustable settings are used to verify.