Armenia Engineer Attestation flashcards
Armenia Engineer Attestation · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Building code hierarchy
- In Armenia, legal force descends from the Constitution to laws such as the Urban Development Law, then government decrees, ministerial orders and finally technical norms; a lower act cannot contradict a higher one.
- Territorial planning documents
- Urban planning proceeds through a hierarchy: territorial plan for the region, general (master) plan for settlements, zoning plan, and detailed plan fixing plots, density and permitted use.
- State expert review
- Mandatory appraisal of design documentation for large or technically complex objects, checking compliance with norms, structural safety and cost; a negative conclusion blocks the building permit and construction.
- Commissioning certificate
- An acceptance act issued by the state commission confirming that the completed object matches the approved design and norms; operating a building before this certificate is issued is unlawful.
- Licensed design activity
- Architectural and engineering design in Armenia requires a licence from the authorised ministry, granted on evidence of qualified staff, office equipment and an operating quality control system.
- Urban planning conditions
- A pre-design document issued by the local authority stating the permitted use, maximum density and height, setbacks, and connection points for water, sewer, power and gas.
- Technical regulation
- A legally binding act setting mandatory requirements only for safety, health, environment and consumer protection; compliance is compulsory, while the underlying standards remain voluntary.
- AST national standard
- A voluntary standard adopted by the Armenian national standards body (SARM); it becomes binding when cited in a technical regulation, a contract or a design specification.
- Declaration of conformity
- A supplier's documented self-assessment, supported by test evidence, that a product meets the applicable technical regulation; it is registered and replaces third-party certification for lower-risk products.
- Partial safety factor gamma-f
- A multiplier converting a characteristic load into a design load: about 1.05 to 1.1 for dead load, 1.2 for imposed floor load, and 1.4 for wind and snow in the fundamental combination.
- Ultimate limit state
- A condition of loss of load-bearing capacity, such as rupture, buckling, overturning, fatigue or collapse; structures are checked so design action effects remain below design resistance.
- Serviceability limit state
- A condition of loss of function or comfort, such as excessive deflection, cracking, vibration or drift; it is checked with characteristic unfactored loads against limits like span/250 for floors.
- Design base shear
- Total seismic lateral force V = K·S·W, where K reflects intensity and structural type, S the soil and spectral shape, and W the weight; it is distributed over height proportional to W times height.
- Seismic joint width
- The separation gap between adjacent blocks, sized from the sum of their computed lateral deflections plus a margin so that pounding cannot occur; no rigid element may bridge the joint.
- Soft storey irregularity
- A storey markedly less stiff or strong than the one above it, typically an open ground floor; it concentrates inelastic demand and is either banned or requires special three-dimensional analysis and detailing.
- Behaviour factor q
- A factor reducing the elastic response spectrum to account for ductility and overstrength: roughly 4 to 5 for ductile reinforced-concrete frames, 2 to 3 for infilled frames, 1.5 to 2 for masonry.
- Design concrete strength fcd
- fcd = alpha-cc times fck divided by gamma-c, with alpha-cc about 0.85 to 1.0 and gamma-c = 1.5 for persistent situations; fck is the characteristic cylinder strength at 28 days.
- Column reinforcement ratio
- Longitudinal steel lies between the larger of 0.10 times NEd/fyd and 0.002 times Ac, and 0.04 times Ac, with at least four bars and laps staggered between sections.
- Bearing capacity of footing
- qu = c-prime Nc + q-prime Nq + 0.5 gamma-prime B Ngamma, where Nq = e^(pi tan phi-prime) tan-squared(45 degrees + phi-prime/2); designed with partial factors or a safety factor near 3.
- Steel partial factor gamma-M2
- gamma-M2 = 1.25 is applied to the resistance of net sections at bolt holes and to welded or bolted connection design, whereas gamma-M0 = 1.0 governs gross cross-section resistance.
- Concrete cube test
- 150 mm cubes, cured and tested at 28 days, give the characteristic cube strength; a set of at least three specimens is taken per batch or per 50 to 100 cubic metres placed.
- Compaction coefficient
- The ratio of achieved dry density to maximum laboratory dry density; backfill and subgrade are accepted at 0.95 or higher, with 0.98 for road bases, verified by field density tests.
- Slump test
- A standard cone test measuring concrete workability; the measured slump must fall within the specified target range, usually with a tolerance near plus or minus 30 mm, or the batch is rejected.
- Vent stack
- A vertical pipe continuing the drainage stack above the roof; it admits air so flowing water does not siphon trap seals and is required on stacks serving several fixtures.
- Residual current device 30 mA
- A protective device that disconnects a circuit when earth-leakage current exceeds 30 milliamps; it is required for socket outlets and wet areas to prevent electric shock.
- Air change rate
- The volumetric outdoor air supplied to a space divided by its volume, per hour; dwellings typically need 0.5 to 1.0 per hour, or 20 to 30 cubic metres per hour per person in living rooms.
- Overhead and estimated profit
- Overhead covers site and company administration not tied to one work item, while estimated profit is the contractor's planned margin; both are applied as percentages of direct cost in the estimate.
- Resource method of estimating
- Unit prices are built from measured quantities of labour, machines and materials at current market prices, rather than from fixed base-period rates later adjusted by cost indices.
- Value added tax in Armenia
- VAT is charged at 20 percent on construction works and is added to the estimated cost after direct costs, overhead and profit, forming the total contract price.
- Hidden works act
- A signed record confirming that concealed work such as reinforcement, embedded services, waterproofing or subgrade was inspected and accepted before covering; without it the work must be opened up.
- Author's supervision
- Periodic site visits by the designer to verify that construction follows the approved design; findings are recorded in a journal and non-conformities must be corrected by the contractor.
- Fall protection threshold
- Work at height in Armenian and CIS practice starts at 1.8 metres above the surface; guardrails at 1.1 metres with a mid-rail, or personal fall-arrest systems, then become mandatory.