High-Performance Building Design

  • Whole-building energy use intensity (EUI) = annual site energy (kBtu or kWh) divided by gross conditioned floor area; compare against a climate-specific baseline, not a single national number.

  • Passive design order of operations: reduce loads (massing, orientation, envelope, glazing ratio) before sizing or selecting active systems; load reduction lowers every downstream capital and operating cost.

  • Window-to-wall ratio (WWR) drives cooling and lighting trade-offs: raising WWR increases solar gain and perimeter cooling but can cut lighting energy; optimum is climate- and orientation-dependent.

  • Orientation rule: long axis east-west minimizes west-facing glazing, which receives low-angle afternoon sun that is hardest to shade with overhangs.

  • Overhang effectiveness depends on latitude and window height; a horizontal projection blocks high summer sun but admits low winter sun only if the projection depth is tuned to solar altitude angles.

  • Envelope metric: assembly U-factor (W/m2-K or Btu/h-ft2-F) governs conduction; SHGC governs solar heat gain; both must be specified per orientation for high-performance envelopes.

  • Daylight autonomy and useful daylight illuminance (UDI) are preferred over simple daylight factor for design decisions because they capture hourly availability and glare risk.

  • Thermal bridging at slab edges, balconies, and shelf angles can dominate envelope heat loss; continuous insulation and thermal breaks are required to meet low U-factors.

Quick reference

Energy Analysis and Modeling

  • Whole-building energy balance: Q_total = Q_envelope + Q_infiltration + Q_internal + Q_solar + Q_HVAC; each term must close to zero over an annual simulation for a valid model.

  • Degree-day estimate: annual heating energy ≈ (UA + infiltration UA) × HDD × 24 / efficiency; useful for screening, not for design decisions.

  • Model calibration target: ASHRAE Guideline 14 accepts normalized mean bias error (NMBE) within ±5% and coefficient of variation of RMSE (CV(RMSE)) within ±15% for monthly data.

  • Baseline vs. proposed comparison must hold weather, schedules, internal loads, and utility rates constant; only design measures change between runs.

  • Parametric sensitivity: rank measures by annual energy savings per unit first cost, then check interactive effects-savings from combined measures are not additive.

  • Free cooling / economizer hours depend on climate bin data and changeover setpoint; bin method approximates hourly simulation for early-stage screening.

  • Peak demand drives utility cost under demand charges; a measure that cuts annual kWh can raise peak kW if it shifts load to on-peak hours.

  • Uncertainty: Monte Carlo or scenario analysis on weather, occupancy, and plug loads communicates model risk better than a single deterministic EUI value.

Quick reference

Indoor Environmental Quality

  • Ventilation rate procedure: outdoor air per person (Rp) plus per floor area (Ra); design OA = Rp × occupants + Ra × area, adjusted by zone air distribution effectiveness.

  • CO2-based demand-controlled ventilation uses steady-state mass balance: indoor CO2 ≈ outdoor CO2 + (generation rate)/(outdoor air rate); use it to trim OA when occupancy is low, not to justify below-minimum rates.

  • Thermal comfort (ASHRAE 55) is defined by operative temperature, humidity, air speed, metabolic rate, and clothing; PMV/PPD predicts dissatisfaction, and 80% acceptability is the common design target.

  • Glare control: daylight glare probability (DGP) above roughly 0.35–0.40 indicates perceptible glare; automated shading and light shelves reduce it without sacrificing daylight.

  • Acoustic design: background noise from HVAC (NC/RC ratings) and reverberation time in occupied rooms both affect speech privacy and perceived comfort; address them at the same time as ventilation design.

  • Filtration and ventilation together control indoor pollutants; MERV 13+ filters reduce particulates, but source control (low-VOC materials, sealing) is more energy-efficient than dilution.

  • Moisture control: keep interior dew point below surfaces to avoid condensation; vapor retarder placement depends on climate zone and assembly orientation.

Quick reference

Commissioning and Operations

  • Commissioning process: pre-design, design, construction, acceptance, and post-occupancy phases; each phase has documented owner's project requirements (OPR) and basis of design (BOD).

  • Functional performance testing verifies systems under part-load, full-load, and failure modes; a test that only confirms full-load operation misses most real-world faults.

  • Retrocommissioning targets existing buildings: investigate, prioritize no/low-cost fixes, then implement and verify; typical savings come from schedule and setpoint corrections.

  • Monitoring-based commissioning uses trend data and fault detection (FDD) to catch simultaneous heating and cooling, stuck valves, and schedule overrides continuously.

  • Measurement and verification follows IPMVP options (A–D); option selection depends on whether savings are measured at the whole-building or component level.

  • Sequence of operations is the control document that commissioning verifies; unclear or missing sequences are a leading cause of persistent energy waste.

  • Seasonal and post-occupancy recommissioning is required because occupancy, tenant fit-outs, and control overrides degrade performance over time.

Quick reference

Water and Materials Efficiency

  • Indoor water savings are measured against a baseline of fixture flow rates and flush volumes; high-efficiency fixtures cut both potable demand and wastewater volume.

  • Net zero water hierarchy: reduce demand, then reuse (rainwater, greywater, condensate), then treat and recharge; capture potential depends on rainfall and roof area.

  • Cooling tower water use: cycles of concentration (CoC) set blowdown; higher CoC cuts makeup water but raises scaling risk and requires appropriate treatment.

  • Embodied carbon = material quantity × carbon factor (kgCO2e per unit); compare assemblies on a whole-building life-cycle basis, not single materials in isolation.

  • Life-cycle assessment stages: cradle-to-gate (A1–A3) covers extraction and manufacture; cradle-to-grave adds construction, use, and end-of-life (A4–C4).

  • Material selection rules: prioritize reused and recycled content, low-VOC and low-toxicity finishes, and locally sourced or rapidly renewable materials where performance is equal.

  • Construction waste diversion is measured as diverted mass or volume divided by total waste generated; track it during construction, not after.